2
IQ23x Series Controllers Installation Instructions TG200539 Issue 2 , 23-Feb-2012
IQ23x
Installation Instructions
3
Mounting
4
Connecting power
IQ Consumption > 60 VA
5
Connecting network
3.1 Installation - Mounting
(continued)
a
4 x Ø 6 mm
b
263 mm
308 mm
14 mm
12 mm
14 mm
Do noT apply poWeR
230 Vac +15% -10% 50 to 60 Hz
cable supplied
2 wire
4 wire
Network Engineering
Manual 92-1735
polarity independent
Cable
1k2 baud 9k6 baud 19k2 baud
no. of
Wires
Belden 9182
1000 m
1000 m
700 m
2
Belden 9207
1000 m
1000 m
500 m
2
Trend Tp/1/1/22/HF/500
(Belden 8761)
1000 m
700 m
350 m
2
Trend Tp/2/2/22/HF/500
(Belden 8723)
1000 m
500 m
250 m
4
Terminal size 0.5 to 2.5 mm
2
RX
TX
OK
A
D
DP
C
B
1
2
8
4
16
32
64
1K
2
9K
6
19K2
ADDRESS
BAUD
M3 earth stud
12 mm
The 230V supply must include a dedicated 5A fuse complying
with BS1632 and a suitably rated switch in close proximity
and be clearly marked as the disconnecting device for the
unit. A 5A circuit breaker with high breaking capacity may be
used as an alternative .
WaRnIng:
This unit must be earthed
(grounded) via the Earth terminal of the IEC
connector or Mate-N-Lok adaptor.