30
IQ23x Series Controllers Installation Instructions TG200539 Issue 2 , 23-Feb-2012
IQ23x
Installation Instructions
13 ReplaCIng an IQ131+ WITH an IQ233
(continued)
9
Check Setup
Note address
Note baud rate settings
Is a node fitted?
new (TMN type) board or not?
Note input link settings
Check for
Link Headers
Link Header type
5V, 15V, 10mA
?
CNC, CNC2, PNC, PNC2
MNC, TMN
ANC, AND, XN28, XNC
Note that a CNC used to
connect a local supervisor or
NDP to the network may be
discarded
19k2 baud
9k6 baud
1k2 baud
e.g.
Address = 2 + 16 = 18
SET
NOT SET
Input channels
1 to 4 (T, I, V)
5 to 16 (T, I , V, D)
17 to 20 (D only, no links)
10
If node Fitted Remove node Card
11
Remove IQ131+
12
Replace with IQ233
Same mounting centres
If mounted in small box (380 x 380 x 80 mm) using semi-
circular cutout fixings, redrill - see section ‘3.1 Installation
- Mounting’, step 3
14
Connect network
if noted in step 6 above.
Network connections should plug in directly - see section
‘3.1 Installation - Mounting’, step 5
13
Connect power
Check mains supply can provide 60 VA
Plug in power lead - section ‘3.1 Installation - Mounting’, step
4
15
Connect Inputs
If fast sequenced digital inputs were connected to IQ131+
input channels 17 to 20, they should be rewired to input
channels 1 to 4 and strategy modified accordingly.
Otherwise,
signal leads should plug in channel for channel -
see section ‘3.1 Installation - Mounting’, step 6
16
Connect outputs
Otherwise, signal leads should be plugged in channel for
channel - see section ‘3.1 Installation - Mounting’, step 7