38 Installation
(for qualified installers only)
Travis Industries
4070620
100-01199_000
Mantel Requirements
•
The illustration below details mantel clearances and maximum mantel depth.
•
Any combustible facing material that protrudes more than 20mm from the face of the fireplace is
considered a mantel and must meet the mantel requirements.
Mantel (combustilbe or non-combustible)
Combustible mantel columns (legs) that
protrude more than 3/4” from the glass
frame must meet the sidewall clearance (1”).
If they protrude 3/4” or less, they may be
placed directly to the side (but not in front) of
the fireplace.
Non-combustible mantel columns do not
have a minimum clearance.
38-1/2”
12”
Maximum
980mm
305mm
Maximum
Combustible mantel column (legs) that
protrude more than 20mm from the glass
frame must meet the sidewall clearance
(25mm). If they produce 20mm or less, they
may be place directly to the side (but not in
front) of the fireplace
Non-combustible mantel columns do not
have a minimum clearance.