Operation
27
© Travis Industries
4012412
100-01270_000
Start-Up Sequence (Igniter)
The stove enters a start-up sequence whenever there is a call for heat and the unit isn’t in Run mode.
This is ensures proper operation through all possible settings and operational states (hot or cold, pellets
burning or not burning, etc.), and overrides all user settings (except the OFF position). During this period
the START light will flash. The stove will not enter start-up if you are loading pellets into the hopper.
During the start-up sequence, the pellets will load into the fire platform, the flame will ignite, and the
room air blower will come on when the heater comes up to the selected temperature.
NOTE:
If the heater doesn’t light 2 times in a row, both the START and STOP lights will turn on. The
combustion blower will run for about an hour before shutting off. Check to make sure there are pellets
in the hopper. We recommend cleaning the burn pot and making sure all air ports are clear of debris.
Reset the unit by unplugging it and then plugging it back in.
Power Outages
If a power outage occurs when the unit is hot and in Manual Mode, it will enter the start-up sequence;
otherwise, it will enter a cool-down phase to clear away smoke. If a power outage occurs at any time
while in TSTAT Mode, the unit will enter the start-up sequence only if there is a call for heat from the
thermostat.
Because this stove relies upon a blower to
evacuate the smoke, some smoke may
enter the home during a power outage. To
keep to a minimum, leave the door closed.
NOTE:
Travis Industries recommends a minimum vertical vent of 5’ to ensure adequate draft during a
power outage.