Changing the TSTAT Program
To adjust temperature press the “STOP” and “TSTAT” button simultaneously while the unit is cold.
The blue Auto-Fan LED light indicates which program you are in – it flashes once for Program 1,
twice for Program 2, and three times for Program 3. The process is described below.
Thermostat Program 1
In Thermostat Mode Program 1 when the thermostat stops calling for heat (the thermostat is open)
the following occurs:
The burn rate decreases to Level 6 (medium) for 15 minutes. If there is no call for heat during that
time…
The burn rate decreases to Level 3 (medium-low) for 15 minutes. If there is no call for heat during
that time…
The burn rate decreases to Level 1 (low) for 15 minutes. If there is no call for heat during that
time…
The unit turns off.
If there is a call for heat by the thermostat (thermostat is closed) at any point during the cool-
down period the burn rate resumes corresponding with the setting on the control panel.
NOTE:
This program is not recommended if you normally burn the stove at a lower setting.
Thermostat Program 2
In Thermostat Mode Program 2 when the thermostat stops calling for heat (the thermostat is open)
the following happens:
The burn rate decreases to Level 1 (low) for 15 minutes. If there is no call for heat during that
time…
The unit turns off.
If there is a call for heat by the thermostat (the thermostat is closed) at any point during this cool-
down period then the burn rate resumes corresponding with the setting on the control panel.
Thermostat Program 3
In Thermostat Mode Program 3 when the thermostat stops calling for heat (the thermostat is open)
the following happens:
The burn rate decreases to Level 1 (low) and remains at this level until there is a call for heat by the
thermostat (the thermostat is closed), then resumes corresponding with the setting on the control
panel.