Mantel Requirements
•
Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured
from the face of the fireplace) must fall in the shaded portion of the table.
•
Any material that protrudes more than 3/4” (19mm) from the non-combustible facing is considered a
mantel and must meet the mantel requirements.
Examples: • If you wish to have an 8" (203mm) deep mantel, it must be at least 8" (203mm) above the fireplace face which is 44-3/4" (1137mm) above the
base. • If you wish to have a mantel 6" (152mm) above the fireplace face, it must be no deeper than 6" (152mm).
36-3/4"
933mm
a
b
Base of the Fireplace
Combustible mantel columns (legs) that protrude
more than 3/4" (.75mm) from the glass frame must
meet the sidewall clearance. If they protrude 3/4"
(.75mm) or less, they must meet the facing
clearance, 2-1/4" (57mm) from the glass frame - to
the side of the fireplace, not in front of it.
Non-combustible mantel columns do not have a
minimum clearance.
Mantel
(combustible or non-combustible)
Maximum Mantel Depth (b)
Mantel
Height
Above
Face (a)
0mm (0")
25mm (1")
51mm (2")
203mm (8")
178mm (7")
152mm (6")
127mm (5")
102mm (4")
76mm (3")
229mm (9")
254mm (10")
279mm (11")
305mm (12")
330mm (13")
356mm (14+")