![Travis Industries 864 TRV GS2 Installation Manual Download Page 29](http://html1.mh-extra.com/html/travis-industries/864-trv-gs2/864-trv-gs2_installation-manual_1154067029.webp)
Installation
(for qualified installers only)
29
Travis Industries
4121102
100-01301
Top Vent Configuration with Horizontal Termination
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor and
diffuser positions.
Up to four elbows (45° or 90°) may be used.
May use 8" (203mm) or 6-5/8" (168mm) diameter vent (see page for 21 details).
Only one horizontal elbow may be used.
5 feet (1.5m)
0 feet
0 feet
5 feet (1.5m)
0 feet
20 feet (6m)
20 feet (6m)
5 feet (1.5m)
10 feet (3m)
5 feet (1.5m)
10 feet (3m)
0 feet
1
5 feet (4.5m)
20' (6m) max
10 feet (3m)
15 feet (4.5m)
15 feet (4.5m
)
20' (6m) max
10 feet (3m)
15 feet (4.5m)
21' (6.4m) max
21' (6.4m) max
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 2
Exhaust Restrictor # 1 (stock)
Intake Restrictor # 1 (stock)
Diffuser Position # 1 (stock)
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
This is considered a
vertical elbow
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
H1
H2