Travis Industries 36 CF II Installation Manual Download Page 9

Installation

  

(for qualified installers only)

9

© Travis Industries

4100519

100-01197_001

Massachusetts Requirements

NOTE: The following requirements reference various Massachusetts and national codes not contained in this document.

Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in
part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent
termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and
porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall
observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the
gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard
wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served
by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the
services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day
period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be
ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight
(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or
equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation
unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the
provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as
adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or
venting system components with the equipment, the instructions provided by the manufacturer for installation of the
equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts
for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the
manufacturer:
• The referenced “special venting system” instructions shall be included with the appliance or equipment installation
instructions; and
• The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a
parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or
equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts requirements.

Summary of Contents for 36 CF II

Page 1: ...do not use any phone in your building Immediately call gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Insta...

Page 2: ...isting Details This appliance was listed by OMNI Test Labs to ANSI Z21 88 report 028 S 57 5 The listing label is attached to the appliance near the gas control valve A copy is shown to the right ICBO...

Page 3: ...ical Connection 17 Battery Pack Learn Switch Installation 18 Remote Synchronization 20 Installation continued Vent Requirements 21 Approved Vent 21 Altitude Considerations 21 Vent Clearances 22 Vent I...

Page 4: ...ane LP Burning the incorrect fuel will void the warranty and safety listing and may cause an extreme safety hazard Direct questions about the type of fuel used to your dealer Check the label and flame...

Page 5: ...not throw this manual away This manual has important operating and maintenance instructions that you will need at a later time Always follow the instructions in this manual Do not touch the hot surfa...

Page 6: ...put Per Hour 50 000 49 000 Minimum BTU Input on Low 28 500 26 900 Dimensions Tabs for lifting handles sku 98500711 Weight 250 Lbs 1 1 2 Includes the required 2 clearance Includes the 1 standoff and 1...

Page 7: ...Direct Vent available only from Travis Industries see page 21 for part numbers Gas Line Equipment shutoff valve pipe etc Installation Overview All requirements below must be met AAAAAAAAAA AAAAAAAAAA...

Page 8: ...for easier vent installation 2 Place the fireplace in place making sure it is level and plumb Attach using the nailing brackets 3 Install the vent gas line electrical connection and battery box 4 Ins...

Page 9: ...building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in p...

Page 10: ...e WARNING Failure to correctly erect the stand offs may lead to a serious fire hazard and will void the listing and warranty of this fireplace Side Stand Offs Bend the side stand off until it is flat...

Page 11: ...doff until the side braces lock into place Rotate the header brackets up The notch in the side brace slides over this screw a c Un fold the side of the header standoff until it is flat both sides Remo...

Page 12: ...e 4 1 4 from the side stand offs see Figure 3 Due to the high temperature the heater should be located out of traffic and away from furniture and draperies Fireplace must be placed so the vents below...

Page 13: ...t must be left clear to provide adequate clearance for the vent A maximum 3 1 2 depth is allowed in this 14 wide area centered along the front of the fireplace 14 Min 50 3 5 Max 56 3 4 25 Minimum 82 F...

Page 14: ...A typical 45 installation uses the framing dimensions shown in the illustration below NOTE all clearances still apply A A A A A A A A A A A A A A A A A A A A A A 59 approximate AAAAAAAAAAA AAAAAAAAAA...

Page 15: ...ation for qualified installers only 15 Travis Industries 4100519 100 01197_001 Nailing Brackets Use screws or nails to secure the fireplace to the framing with the six nailing brackets 1 2 3 4 5 6 7 F...

Page 16: ...ing the fireplace This fireplace is designed either for natural gas or for propane but not for both Check the gas control valve to make sure the correct fuel is used An additional shut off valve is re...

Page 17: ...and must meet all local codes The fireplace must be properly grounded in accordance with local codes or ANSI NFPA 70 1987 Make sure the household breaker is shut off prior to working on any electrical...

Page 18: ...vents the wires from slipping out of the junction box while the batteries are replaced Take care to prevent damage to wires Junction Box not supplied Battery Box and Learn Switch placed inside the jun...

Page 19: ...s Red and White Wires Learn Wires Two White Wires Figure 12 2 Determine a location for the single gang junction box that contains the battery pack and learn switch It must be located within 12 of the...

Page 20: ...WARNING Shut the gas off to the fireplace prior to conducting this process 1 Press the Learn button once The fireplace will beep once 2 Press the Mode button on the remote The fireplace will beep fiv...

Page 21: ...parts are available from Travis Dealers Simpson Part Travis Part 6 Length 68GSS 06 98900024 12 Length 68GSS 12 98900023 24 Length 68GSS 24 98900022 36 Length 68GSS 36 98900021 48 Length 68GSS 48 98900...

Page 22: ...al Sections 4 Clearance Above 2 Clearance To The Side 2 Clearance Below Vent Installation Slide the vent sections together and turn 1 4 turn until the sections lock in place Screws are not required to...

Page 23: ...low In this example the restrictor is set in position 2 Tighten the screws once the restrictor is in the correct position open stock position 1 2 closed 3 Back Wall of Firebox Firebox Roof Figure 13 I...

Page 24: ...AAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA 5 fee...

Page 25: ...AAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAA 5 feet 0 feet 0 fee...

Page 26: ...AA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAAAAAAAAAAAA AAAAA...

Page 27: ...AAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAAAA AAAAAAAAAAAAAAA...

Page 28: ...nce in accordance with local installation codes and the requirements of the gas supplier G Minimum 48 clearance from any adjacent building H Minimum 84 clearance above any grade when adjacent to publi...

Page 29: ...AA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA Min 10 Min 49 5 Min 1 Max 1 1 2 Non Combustible Hearth AAA AAA AAA AAA AAA AAA AAA AAA AAAAAA AAAAA...

Page 30: ...it is near the minimum raised height Min 6 AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA AAAAAAAAAAAAA Side View Fireplace NOTE When building a rai...

Page 31: ...ombustible fiber board to the fireplace and framing as shown WARNING Do not use adhesive to secure the cement board or facing The high temperatures of the fireplace may cause adhesives to emit odors U...

Page 32: ...n combustible facing on the front of the fireplace must extend a minimum 6 to each side of the glass frame Beyond 6 combustibles may be used but may not protrude more than 3 4 from the non combustible...

Page 33: ...AAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AAAA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AA AAAAAAA AAAAAAA Fireplace Drywall Framing AAAAA AAAAA Cement Board AAAAA...

Page 34: ...ee Figure 24 The maximum mantel depth is 12 measured from the face Max 12 Base of the Fireplace Min 48 5 Mantel combustible or non combustible Combustible mantel columns legs that protrude more than 3...

Page 35: ...37 NOTE If using propane LP convert the appliance prior to installing the logs see page 45 for details 2 We recommend you purge the gas line at this time with the glass removed This allows gas to be...

Page 36: ...a cover plate see the illustration below After adjusting the air shutter replace the burner logs and glass and verify the flame quality Front Burner Air Shutter Rear Burner Air Shutter Air Shutter Cov...

Page 37: ...ignition when accessing the firebox Warning The appliance must be completely cool before removing the glass Warning Do not strike or slam the glass The glass frame is held in place with four latches U...

Page 38: ...Install the firebacks following the directions below UP UP Herringbone Pattern Brick Pattern Remove the clip and screw located on the firebox ceiling near the front both sides b Right Floor Fireback...

Page 39: ...ndustries 4100519 100 01197_001 Log Set Installation Overview Below is a picture detailing log placement for this fireplace Follow the directions on the following pages to place the logs correctly Cen...

Page 40: ...40 Finalizing the Installation for qualified installers only Travis Industries 4100519 100 01197_001 Center Log Place the center log as shown below The rear log contacts the side and back fireback...

Page 41: ...Log Place the left lower log as shown below Right Rear Log Place the right rear log as shown below The left lower log rests in front of the burner holes and obscures the pilot The right rear log has a...

Page 42: ...d installers only Travis Industries 4100519 100 01197_001 Upper Left Log Place the upper left log as shown below The upper left log has a notch that fits over the grate The upper left log has a hole t...

Page 43: ...Industries 4100519 100 01197_001 Upper Right Log Place the upper right log as shown below The right rear log has a flat portion that the upper right log rests against The upper right log has a notch...

Page 44: ...t The included rock wool is placed on top of the burner to enhance the glow from the burner The rock wool works best when it is applied in a very thin porous layer The best method for applying the roc...

Page 45: ...ine to ensure proper gas use 1 Remove the glass see page 35 Remove the logs and coals if installed page 38 2 Remove the burner see the illustration below Remove the two screws holding the grate in pla...

Page 46: ...w the two orifices Screw each LP orifice in so the orifice protrudes 15 16 indicating full insertion Look here for the orifice identification Apply thread sealant to the LP orifices prior to installat...

Page 47: ...hood until it is fully secure Figure 29 NOTE The sliding portion of the pilot orifice may be positioned differently Instead of pulling it towards you you may push it away Either way when the hole appe...

Page 48: ...it is in a lower position when switched to LP Figure 31 7 Remove the NG rate screw and replace it with the LP rate screw included in the owner s pack see Figure 32 Take care to not damage the rubber...

Page 49: ...ons so they are evenly spaced and tighten these screws on the brackets to clamp the andirons to the grate If necessary bend the bracket so the andiron points straight up AA AA AA AAA AAA AAA AA AA AA...

Page 50: ...uirements Recessed Hearth 30 Hearth Requirements 29 Horizontal Termination 1 90 Elbow 24 Horizontal Termination 3 90 Elbows 25 Installation Options 6 Installation Overview 7 Listing Details 2 Log Set...

Reviews: