Installation
(for qualified installers only)
© Travis Industries
4100519
100-01197_001
Mantel Requirements
•
The mantel (combustible or non-combustible) must be a minimum 48.5” above the base of the
fireplace (49” above the sub-floor or raised platform - see Figure 24).
•
The maximum mantel depth is 12” (measured from the face).
Max. 12”
Base of the Fireplace
Min. 48.5”
Mantel
(combustible or non-combustible)
Combustible mantel columns (legs) that
protrude more than 3/4” from the glass frame
must meet the sidewall clearance (10-1/4” from
the glass frame). If they protrude 3/4” or less,
they must meet the facing clearance (6” from
the glass frame).
Non-combustible mantel columns do not have a
minimum clearance.
Figure 24