VI. a - INTRODUCTION/OVERVIEW:
The Traulsen Even Thaw is designed to be used as a
thawing cabinet.  While it may be utilized in a
refrigeration mode, that is not its intended use.  Its
function is to hold the cabinet temperature in the
range from 38 to 40 degrees to thaw product within
the food-safe temperature zone.  It has not been
configured to hold colder product temperatures in the
35 to 38 deg F range as desired by some customers.

Frozen product placed into the unit will pull the
cabinet temperature below the heater set point (37
deg.) and the unit will begin to function in the thaw
mode. This prompts the refrigeration system to turn
OFF, and the heaters to turn ON. The fans remain ON,
circulating this cold air around the product, allowing
for rapid thawing. When cabinet air temperature
reaches the upper set point (38 deg. although the
product is actually much colder), the heaters turn OFF.

As the cabinet temperature reaches the heater set
point, the heat will be cycled off while the internally
generated heat from the circulation fans continues to
add heat to the cabinet.  If sufficient cold capacity or
possibly other frozen product is added to the unit and
subsequently lowers the cabinet temperature more
than 1 degree below the heater set point, the heat will
again turn on to thaw the product.

If the cold capacity of the product no longer sufficiently
pulls down the cabinet temperature below the heater
set point, the cabinet temperature will slowly rise to
attain the evaporator coil cut-in set point (41 deg.) and
energize the refrigeration system.  The unit will remain
in the refrigeration mode until the cabinet
temperature pulls down to the compressor cut-out set
point (38 deg.).  The unit will continue to operate and
cycle in the refrigeration mode.

The units incorporate a mode switch located behind
the louvered panel.  Switching to the Refrigeration
mode (switch OFF) will turn off two internal blower fans
and will reduce the Thaw mode (switch ON)
performance.  Subsequently, switching to the Thaw
mode will have reduced refrigeration performance.

The controller has been preset at the factory and
should not require any adjustments. Traulsen
engineering EXPECTS no changes be made to any set
points or parameter settings without discussing the
situation and obtaining approval to do so. Modifying
the default set points could disrupt the operation/
functional programming algorithm and result in erratic
unit operation.

VII. GENERAL USE, OPERATION & SERVICE SUMMARY

VI. b - LOADING GUIDELINES:
The Even-Thaw model can accommodate any size
partial load, or up to (28) 18

 x 26

 pans of product (for

example approximately 672 lbs. of chicken). Use of alu-
minum pans is highly recommended. Product should be
placed on pans in one layer only to allow for proper air-
flow. With a full load thaw time will be between 22 & 24
hours. Overloading and/or double wrapping product will
extend thaw times.

VI. c - LED LIGHTS

:

The controller has two LED lights that can be useful. One
is marked H, which will be lit when in the Refrigeration
mode.  The other is marked G and will be lit during the
Thaw mode. When the H LED is lit the controller will
supply line voltage to the compressor relay coil closing
the N/O contacts in turn supplying line voltage to the
condensing unit. When the G LED is lit the controller
will supply between 3 to 30 VDC to the solid-state relay
coil closing the N/O contacts in turn supplying line
voltage to the mullion heater.

VI. d - CALL SERVICE LIGHT:
If lit, this indicates that one of the two temperature
sensors is either OPEN or SHORTED. To check the
resistance value per given temperature is correct place
the sensor in an ice bath (32 deg.). The resistance value
should be 100 ohms + 2%. There is a cabinet sensor
inside the heater/blower chamber and another sensor in
the evaporator coil.

Summary of Contents for RET132EUT-FHS

Page 1: ...ed to the unit Should you need service however call us on our toll free number 800 825 8220 between 7 30 am and 4 30 pm CST Monday thru Friday It is our pleasure to help and assist you in every possible way OWNER S MANUAL OWNER S MANUAL OWNER S MANUAL OWNER S MANUAL OWNER S MANUAL Instructions for the installation operation and maintenance of all Traulsen INSTALLER COMPLETE THE FOLLOWING INFORMATI...

Page 2: ... heat I THE SERIAL TAG 1 FORT WORTH TX SERIAL MODEL VOLTS Hz PH TOTAL CURRENT AMPS MINIMUM CIRCUIT AMPS MAXIMUM OVERCURRENT PROTECTION AMPS LIGHTS WATTS HEATERS AMPS REFRIGERANT TYPE OZ DESIGN PRESSURE HIGH LOW REFRIGERANT TYPE OZ DESIGN PRESSURE HIGH LOW 370 60294 00 REV A READING THE SERIAL TAG Serial The permanent ID of your Traulsen Model The model of your Traulsen Volts Voltage Hz Cycle PH Ph...

Page 3: ...nal installa tion The bolts can then be removed with a 3 4 socket wrench Avoid laying the unit on its front side or back for removal of the pallet NOTE Traulsen does not recommend laying the unit down on its front side or back However if you must please be certain to allow the unit to remain in an up right position afterwards for 24 hours before plugging it in so that the compressor oils and refri...

Page 4: ...erator with two important additional features 1 the ability to introduce small amounts of heat into the cabinet and 2 increased air flow indicated by the presence of blowers mounted be hind the mullion The Even Thaw refrigerator operates continually the intro duction of frozen product lowers the cabinet temperature below the heater setpoint temperature 37 F This prompts the refrigeration system to...

Page 5: ... screws which hold it in place On solid door units the top hinge s contains a microswitch for controlling the interior lighting To reassemble the hinge reverse the previous procedure Fig 3 Fig 4 4 IV g ADJUSTING THE TEMPERATURE SCALE The Traulsen Even Thaw model is preset at the factory to operate within strict temperature parameters Should these settings require adjustment please contact our Serv...

Page 6: ... MAINTENANCE cont d V c REPLACING THE GASKETS To remove the gasket to be replaced grasp it firmly by one corner and pull it out Before attempting to install a new gasket both the unit and the gasket it self must be at room temperature Insert the four cor ners first by using a rubber mallet or hammer with a block of wood After the corners are properly inserted work your way towards the center from ...

Page 7: ... switch located behind the louvered panel Switching to the Refrigeration mode switch OFF will turn off two internal blower fans and will reduce the Thaw mode switch ON performance Subsequently switching to the Thaw mode will have reduced refrigeration performance The controller has been preset at the factory and should not require any adjustments Traulsen engineering EXPECTS no changes be made to ...

Page 8: ...r loading has been eliminated as a possible cause for extended thaw cycle times there are several system checks which can be done to diagnose the Traulsen Even Thaw unit First the amp draw should be checked early in the thaw cycle Shortly after loading the unit with frozen product the electronic control LED G should be illuminated as the cabinet temp will probably be in the 30 to 34 degree F range...

Page 9: ...EM HERE REMEDY 1 Condensing unit fails to start a Check if cord plug has been disconnected 2 Condensing unit operates for a Are doors closing properly prolonged periods or continuously b Dirty condenser or filter Clean properly c Evaporator coil iced Needs to defrost d Shortage of refrigerant call service 3 Food compartment is too warm a Check doors and gaskets for proper seal 4 Condensation on th...

Page 10: ...0308 00 All Models Sensor Probe 337 60309 00 RET132EUT RET232NUT Transformer 337 60309 01 RET232EUT Transformer 337 60311 00 RET132EUT RET232NUT Solid State Relay 337 60311 01 RET232EUT Solid State Relay 337 29447 00 All Models Defogger Switch 344 60126 00 All Models Thermometer 378 60013 00 All Models Call Service Light 346 28924 42 All Models Lock Keys T 42 346 13186 42 All Models Lock Cylinder ...

Page 11: ... 10 XI WIRING DIAGRAM ALL ONE SECTION MODELS ONLY ...

Page 12: ... 11 XII WIRING DIAGRAM MODELS RET232NUT FHS RET232NUT HHS ONLY ...

Page 13: ... 12 XIII WIRING DIAGRAM MODELS RET232EUT FHS RET232EUT HHS ONLY ...

Page 14: ...O THE EQUIPMENT OR ITS SALE OPERATION OR USE AND TRAULSEN NEITHER ASSUMES NOR AUTHORIZES ANYONE ELSE TO ASSUME FOR IT ANY OBLIGATION OR LIABILITY IN CONNECTION WITH THE EQUIPMENT OR ITS SALE OPERATION OR USE OTHER THAN AS STATED HEREIN INTERNATIONAL COMMERCIAL WARRANTY for Canadian warranties see domestic US warranty TRAULSEN CO INC warrants to the original purchaser the Refrigeration Equipment ma...

Page 15: ... 4 I Inside Door Pan 4 Interior Arrangements 3 J K L LED Lights 6 Legs 2 Loading Guidelines 6 Louver Assembly 4 M Mullion Air Ducts 6 N O Operational Troubleshooting 7 P Power Supply 3 Process Loading 4 Product Mix Issues 6 R Refrigerations System 3 Return Authorization 2 S Serial Tag 1 Spare Parts List 9 T Temperature Scale Adjustment 4 Troubleshooting 6 7 Tray Slides 3 7 U V Vinyl Protective Cov...

Page 16: ...Blue Mound Road Fort Worth TX 76106 Phone 800 825 8220 Fax Svce 817 740 6757 Website www traulsen com HOURS OF OPERATION Monday thru Friday 7 30 am 4 30 pm CST Quality Refrigeration 2005 Traulsen All Rights Reserved ...

Reviews: