Section III: TSS Installation
Hanging Installation
Thermaco, Inc. supplies the frame and SSOP-70/95 with the HA-70/95. This kit needs to be
installed by a licensed contractor. The contractor is responsible for determining weight loads,
preparation of the floor for installation and any construction necessary for installation of the
suspension kit.
Using the HA-70/95 model, a Trapzilla unit may be suspended from a ceiling be-
low the floor of a kitchen or other room.
Note: Drawing for reference only. Equipment must be installed
in compliance with all applicable laws, regulations and codes,
including plumbing & building codes. Installation should be
performed by a qualified plumber and contractor.
Trapzilla Solids
Separator must be
purchased separately.
Support Stand
Included with
HA-70/95
1
1
2
2
3
3
4
4
A
A
B
B
C
C
D
D
THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL. THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT
WRITTEN CONSENT FROM THERMACO, INC. POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.
POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF
THIS DRAWING. DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.
MATERIAL (UNLESS NOTED)
FINISH (UNLESS NOTED)
646 GREENSBORO STREET
PO BOX 2548, ASHEBORO, NC 27203
VOICE 336-629-4651 FAX 336-626-5739
Decimals
.XX +/- .03
.XXX +/- .015
Unless otherwise specified
Dimensions are in inches
Tolerances
Angular
+/- 1°
CHECKED
SIZE
REV. NO.
DWG NO.
PART NO.
C
SCALE
RELEASE DATE
SHEET OF
ENGINEERING
DRAWN
DATE
THIRD ANGLE PROJECTION
42.00 in
[106.7 cm]
42.00 in
[106.7 cm]
32.00 in
[81.3 cm]
Typical
Support
Rod
Spacing
52.51 in
[133.4 cm]
5.00 in
[12.7 cm]
5.00 in
[12.7 cm]
40.01 in
[101.6 cm]
Top View
Outlet End View
Side View
38.00 in
[96.5 cm]
TYP
42.50 in
[108.0 cm]
13.00 in
[33.0 cm]
Outlet
12.50 in
[31.8 cm]
Inlet
2 Inch
NPT
Vent
4.50 in
[11.4 cm]
4" Nom
Inlet &
Outlet