background image

 

 

 

 

 

 

2

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Power supply unit 

ServoPac GDPS

Summary of Contents for ServoPac GDPS

Page 1: ...2 Power supply unit ServoPac GDPS...

Page 2: ...with electrical parts even after power down may involve physical damage Wait for at least 10 minutes after power down before handling the devices a residual voltage of several hundreds of volts may r...

Page 3: ...1 5 SIZING OF THE POWER SUPPLY 6 1 5 1 Continuous power 6 1 5 2 Braking system 7 CHAPTER 2 INPUTS OUTPUTS 9 2 1 X1 CONNECTOR POWER CONNECTOR 9 2 2 X2 CONNECTOR AUXILIARY POWER SUPPLY AND AOK CONNECTOR...

Page 4: ...power values are given for a maximum voltage of 480 VAC 1 2 ORDERING CODE 1 2 1 SERVOPAC GDPS POWER SUPPLY UNIT 1 2 2 ACCESSORIES Connector kit FC GDPS This connector set includes power X1 and auxili...

Page 5: ...C 2 VAC VDC 2 VAC Dynamic output DC voltage according to the mains voltage regenerative phase 480 800 VDC 275 400 VDC Triggering threshold of the braking system 790 V 5 390 V 5 Minimum braking resisto...

Page 6: ...6 ServoPac GDPS Power supply unit Chapter 1 Specifications 1 4 MECHANICAL DIMENSIONS BOTTOM VIEW SIDE VIEW FRONT VIEW Dimensions are given in mm 157 8 VERTICAL MOUNTING IS MANDATORY...

Page 7: ...ses Speed value in rad s Simplified method 1 If the continuous average power cannot be evaluated by the accurate method it may be convenient to use the power of the application motors The electrical p...

Page 8: ...ower regenerated on the motor shaft in W COUPLING Efficiency of the mechanical coupling gearbox If no gearbox is used COUPLING 1 PJOULE Losses in the motor windings in W RMOTOR Winding resistance meas...

Page 9: ...me rules must be observed heat must be evacuated shielded cable or at least twisted wires must be used wires must bear high voltage and high temperature recommended type UL1015 AWG 14 wires must be as...

Page 10: ...ge output 6 DR O Braking resistor connection Recommended wire section 2 5 mm or AWG14 Braking resistor is required 7 DR O 2 2 X2 CONNECTOR AUXILIARY POWER SUPPLY AND AOK CONNECTOR Manufacturer Weidmul...

Page 11: ...nfigure the operation mode of the ServoPac GDPS unit MINISWITCH DESCRIPTION 1 2 3 4 5 6 7 8 0 0 0 0 X X X X Operating voltage 400 VAC default configuration 1 1 0 0 X X X X Operating voltage 400 VAC wi...

Page 12: ...drive TT drive Braking resistor AC 24V isolated 230 V 0 V 24 V AOK AOK L1 L2 L3 DC DC DR DR Power ON Power relay remote control KM1 24 V AOK GDPS AOK AXIS 1 AOK AXIS N STOP km1 KM1 F1 3 2 FUSE RATING...

Page 13: ...voltage is correctly set up according to the mains voltage SW1 configuration When the braking I t protection becomes active it prevents the braking resistor from switching Check that the braking abili...

Reviews: