5
ServoPac GDPS – Power supply unit
Chapter 1 - Specifications
1.3 – MAIN TECHNICAL DATA
Operating voltage
400 V
AC
Operating voltage
230 V
AC
Mains operating voltage
400 - 480 V
AC
+10%/-15%*
230 V
AC
+10%/-15%
Mains specifications
three-phase, 50 to 60 Hz,
TN or TT system with grounded neutral point.
IT system supported but not recommended
(phase-ground voltage must be balanced)
Voltage unbalance
Max. 3 % of the mains voltage fundamental
Mains filter
integrated
Peak output power
GDPS 16 kW
GDPS 32 kW
45 kW
90 kW
25 kW
45 kW
Rated output power
GDPS 16 kW
GDPS 32 kW
16 kW
32 kW
8 kW
16 kW
Static output DC voltage
V
DC
=
√
2
×
V
AC
V
DC
=
√
2
×
V
AC
Dynamic output DC voltage according to the mains
voltage / regenerative phase
480 - 800 V
DC
275 - 400 V
DC
Triggering threshold of the braking system
790 V
±
5%
390 V
±
5%
Minimum braking resistor value
GDPS 16 kW
GDPS 32 kW
33
Ω
16.5
Ω
16.5
Ω
7.5
Ω
Peak power of the braking system
GDPS 16 kW
GDPS 32 kW
20 kW
40 kW
10 kW
20 kW
Maximum continuous power of the
braking system (I²t limited)
GDPS 16 kW
GDPS 32 kW
4 kW
8 kW
2 kW
4 kW
Undervoltage threshold
200V
±
5%
100V
±
5%
Overvoltage threshold
950V
±
5%
450V
±
5%
Maximum surrounding air temperature
- operation: +5°C to +50°C (from 40°C, the rated power
must be reduced by 3 % per additional °C)
- storage: -20°C to +70°C.
*
For special applications, the input voltage range can be extended to 230 Vac - 480 Vac (see chapter 2.4 for
reducing the undervoltage threshold to 100 Vdc).