POWER PRECAUTIONS
➢
When you connect the power source, make sure if it may cause overload.
➢
Avoid operating on a wet floor in the open. Make sure the extension cable is in
good condition
➢
Make sure the power switch is off before you start to install the device
2.3
DEVICE’S INSTALLATION FLOW CHART
ILLUSTRATED AS FOLLOWING
Connecting
Grouding
Wire and
Power
Cord
Acquisition
Check
Installing
Device
Setting
Parameter
Running
Device
Connecting
Signal
cable
2.4
ENVIRONMENT REQUIREMENT
Item
Requirement
Machine Hall
Space
When user installs machine frame array in one machine hall, the distance
between 2 rows of machine frames should be 1.2~1.5m and the distance
against wall should be no less than 0.8m.
Machine Hall
Floor
Electric Isolation, Dust Free
Volume resistivity of ground anti-static material: 1X107~1X1010
,
Grounding current limiting resistance: 1M
(Floor bearing should be
greater than 450Kg/
㎡
)
Environment
Temperature
5~40
℃
(sustainable)
,
0~45
℃
(short time)
installing air-conditioning is recommended
Relative
Humidity
20%~80% sustainable 10%~90% short time
Pressure
86~105KPa