2.2. Electrical system design
Figure 2-3 wiring diagram of the whole
TRB4000TL/5000TL/6000TL/8000TL/9000TL/010KTL system.
Please refer to chapter 4 for the detail connecting and install methods.
2.3. The illustration of derating and limit the input power
To avoid inverter to be damaged by over temperature or over current.
Not output power when the temperature of power devices is over 85
℃
or the
ambient temperature is over 76
℃
.
Derate the output power linearly when the temperature of power devices is
between 81-85
℃
or the ambient temperature is between 70-76
℃
.