Mechanical
Specifications

General

The units shall be convertible airflow.
The operating range shall be between
115°F and 0°F in cooling as standard
from the factory for units with
microprocessor controls. Operating
range for units with electromechanical
controls shall be between 115°F and
40°F. Cooling performance shall be rated
in accordance with ARI testing
procedures. All units shall be factory
assembled, internally wired, fully
charged with R-22, and 100 percent run
tested to check cooling operation, fan
and blower rotation, and control
sequence before leaving the factory.
Wiring internal to the unit shall be
colored and numbered for simplified
identification. Units shall be UL listed
and labeled, classified in accordance to
UL 1995/CAN/CSA No. 236-M90 for
Central Cooling Air Conditioners.
Canadian units shall be CSA Certified.

Casing

Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned,
phosphatized, and finished with a
weather-resistant baked enamel finish.
Unit’s surface shall be tested 1000 hours
in a salt spray test in compliance with
ASTM B117. Cabinet construction shall
allow for all maintenance on one side of
the unit. Service panels shall have lifting
handles and be removed and reinstalled
by removing only a single fastener
while providing a water and air tight
seal. All exposed vertical panels and top
covers in the indoor air section shall be
insulated with a cleanable foil-faced,
fire-retardent permanent, odorless
glass fiber material.   The base of the unit
shall be insulated with 1/2 inch, 1 pound
density foil-faced, closed-cell material.
All insulation edges shall be either
captured or sealed.The unit’s base pan
shall have no penetrations within the
perimeter of the curb other than the
raised 1

1

/

8

 inch high downflow supply/

return openings to provide an added
water integrity precaution, if the
condensate drain backs up. The base of
the unit shall have provisions for forklift
and crane lifting, with forklift capabilities
on three sides of the unit.

Unit Top

The top cover shall be one piece
construction or where seams exist, it
shall be double-hemmed and gasket-
sealed.  The ribbed top adds extra
strength and prevents water from
pooling on unit top.

Filters

One inch, throwaway filters shall be
standard on all 3-5 ton units. The filter rack
can be converted to two inch capability.
Two inch filters shall be factory supplied
on all 6-10 ton units. Optional 2-inch
pleated filters shall be available.

Compressors

All 3 ton standard units shall have direct-
drive, hermetic, reciprocating type
compressors. The reciprocating type
compressors have a centrifugal oil pump
providing positive lubrication to moving
parts. Motor shall be suction gas-cooled
and shall have a voltage utilization range
of plus or minus 10 percent of unit
nameplate voltage. Crankcase heater,
internal temperature, and current-
sensitive motor overloads shall be
included for maximum protection.
Compressors shall have internal spring
isolation and sound muffling to minimize
vibration transmission and noise. Low
pressure switches shall be standard.

3 ton high efficiency and 4-10 ton
standard and high efficiency units shall
have direct-drive, hermetic, scroll type
compressors with centrifugal type oil
pumps. Motor shall be suction gas-cooled
and shall have a voltage utilization range
of plus or minus 10 percent of unit
nameplate voltage. Internal overloads
shall be provided with the scroll
compressors. Crankcase heaters shall be
included on 7½ ton standard efficiency
units.

Refrigerant Circuits

Each refrigerant circuit offers a choice of
independent fixed orifice expansion
devices or thermal expansion valve.
Service pressure ports, and refrigerant
line filter driers are factory-installed as
standard. An area shall be provided for
replacement suction line driers.

Evaporator and Condenser Coils

Internally finned, 5/16” copper tubes
mechanically bonded to a configured
aluminum plate fin shall be standard.
Coils shall be leak tested at the factory to
ensure the pressure integrity. The
evaporator coil and condenser coil shall
be leak tested to 200 psig and pressure
tested to 450 psig. The condenser coil
shall have a patent pending 1+1+1 hybrid
coil designed with slight gaps for ease of
cleaning. A removeable, reversible,
double-sloped condensate drain pan with
provision for through the base
condensate drain is standard.

Gas Heating Section

The heating section shall have a
progressive tubular heat exchanger
design using stainless steel burners and
corrosion resistant steel throughout. An
induced draft combustion blower shall be
used to pull the combustion products
through the firing tubes. The heater shall
use a direct spark ignition (DSI) system.
On initial call for heat, the combustion
blower shall purge the heat exchanger
for 20 seconds before ignition After three
unsuccessful ignition attempts, the entire
heating system shall be locked out until
manually reset at the thermostat/zone
sensor. Units shall be suitable for use with
natural gas or propane (field-installed kit)
and also comply with the California
requirement for low NOx emissions.

Outdoor Fans

The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw-through in the vertical discharge
position. The fan motor shall be
permanently lubricated and shall have
built-in thermal overload protection.

Indoor Fan

All 3-5 ton 3-phase units offer a choice of
direct-drive, FC, centrifugal fans or belt
driven, FC centrifugal fans with
adjustable motor sheaves. 3-5 ton direct
drive oversized motors shall be available
for high static operations. All 6-10 ton
units shall have belt drive motors with an
adjustable idler-arm assembly for quick-
adjustment to fan belts and motor
sheaves. All motors shall be thermally
protected. All indoor fan motors meet the
U.S. Energy Policy Act of 1992 (EPACT).

Summary of Contents for YSC060A1

Page 1: ...Packaged Gas Electric Rooftop Units Precedent 3 10T ons 60 Hz RT PRC006 EN October 2004...

Page 2: ...lity as the original Micro with additional benefits for greater application flexibility With its sleek compact cabinet rounded corners and beveled top Precedent continues to provide the highest standa...

Page 3: ...cation Considerations Selection Procedure Model Number Description General Data Performance Data Cooling Performance Fan Performance Heating Performance Controls Electric Power Dimension andWeights Me...

Page 4: ...Disconnect Switch Two Inch Pleated Filters Factory or Field Installed Options Clogged Filter Fan Failure Switch Differential Pressure Switches DischargeAir Sensing Kit Economizer Electric Heaters Fros...

Page 5: ...jumper betweenTest 1 andTest 2 terminals on the LowVoltage Terminal Board and the unit will walk through its operational steps automatically The unit automatically returns control to the zone sensor a...

Page 6: ...wires and diagnosing the unit Outstanding Standard and Optional Components Compressors Precedent contains the best compressor technology available to achieve the highest possible performance Our compr...

Page 7: ...overpressurization problems ProgressiveTubular Heat Exchanger The compact cabinet features a tubular heat exchanger in low medium and high heat capacities The heat exchanger is fabricated using stain...

Page 8: ...moke detector or fire control panel The ventilation override kit is available as a field installed accessory Zone Sensors Available in programmable automatic and manual styles Precedent offers ultimat...

Page 9: ...Electrical option with an Electrical Heater the heater must be factory installed Powered or Unpowered Convenience Outlet This option is a GFCI 120v 15amp 2 plug convenience outlet either powered or u...

Page 10: ...ge Cooling Standard or High Efficiency Cooling available Economizer Equipped with either dry bulb reference or comparative enthalpy sensing this feature provides free cooling as the outdoor temperatur...

Page 11: ...unit return air section also increases opening the dampers and relieving the conditioned space NOTE THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED PRESSUR...

Page 12: ...hen round up to the nearest unit size 58 MBh 12 MBh approx 5 tons Step 3 Examine gross capacity Table PD 13 shows that aYHC060A4 has a gross cooling capacity of 62 4 MBh and 48 4 MBh sensible capacity...

Page 13: ...52 25 db 57 84 wb Step 3b Determine leaving unit temperature in standard cooling mode Repeat Step 3a substituting net sensible or latent capacity for gross sensible or latent capacity to find the lea...

Page 14: ...Oversized Motor 2 Optional Belt Drive Motor DIGIT 16 Hinged Service AccessFilters 0 Standard Panels Standard Filters A Hinged Access Panels Standard Filters B Standard Panels 2 Pleated Filters C Hing...

Page 15: ...on Pipe Size in 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Compressor No Type 1 Hermetic 1 Hermetic 1 Scroll 1 Scroll Outdoor Sound Rating dB 6 83 83 86 82 Outdoor Coil Type Lanced Lanced Lanced...

Page 16: ...basedonARIStandard210 240exceptAK 380V 60Hz 2 EER and or SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Stand...

Page 17: ...10 0 14 0 10 0 14 0 10 0 14 0 Gas Connection Pipe Size in 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 3 4 Compressor No Type 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 6 84 84 88 Outdoor Coil Type Lanced...

Page 18: ...10 240 or 360 Units are rated at 80 F ambient 80 F entering dry bulb and 67 F entering wet bulb at ARI rated cfm 4 Heating Performance limit settings and rating data were established and approved unde...

Page 19: ...81 80 81 81 81 No Burners 3 3 4 3 3 4 3 3 4 No Stages 1 2 2 1 2 2 1 2 2 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 4 5 14 0 4 5 14 0 LP minimum maximum 10 0 14 0 10 0 14 0 10 0 14 0 Gas...

Page 20: ...ceptAK 380V 60Hz units 2 EER and or SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Standard 210 240 or 360 Uni...

Page 21: ...utput Btu 121 500 162 000 202 500 AFUE 5 81 81 81 Steady State Efficiency 81 81 81 No Burners 3 4 5 No Stages 2 2 2 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 LP minimum maximum 10 0 14...

Page 22: ...tandard210 240exceptAK 380V 60Hz 2 EER and or SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Standard 210 240...

Page 23: ...y 8 81 81 81 81 81 81 No Burners 2 2 3 2 2 3 No Stages 1 1 1 1 1 1 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 4 5 14 0 LP minimum maximum 10 0 14 0 10 0 14 0 Gas Connection Pipe Size in...

Page 24: ...ordance with the Unitary Air Conditioner Equipment certification program which is basedonARIStandard210 240 2 SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Heating Perf...

Page 25: ...No Burners 2 2 3 2 2 3 2 3 3 No Stages 1 1 1 1 1 1 1 1 2 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 4 5 14 0 4 5 14 0 LP minimum maximum 10 0 14 0 10 0 14 0 10 0 14 0 Gas Connection Pip...

Page 26: ...its are certified in accordance with the Unitary Air Conditioner Equipment certification program whichisbasedonARIStandard210 240 2 EER and or SEER are rated at ARI conditions and in accordance with D...

Page 27: ...0 1 750 1 750 1 750 1 750 3 450 Motor Frame Size Standard Oversized 56 56 56 56 56 56 Filters Type Furnished 1 1 Throwaway Throwaway Throwaway No Size Recommended 4 20 x 25 x 2 4 20 x 25 x 2 4 20 x 25...

Page 28: ...31 5 31 7 31 6 36 3 24 2 90 40 2 40 2 40 4 39 2 42 3 30 1 38 8 38 8 38 8 38 8 40 9 30 2 37 1 37 1 37 0 37 0 39 1 30 3 34 6 34 6 34 6 34 6 36 6 30 0 75 36 4 32 6 39 4 23 5 41 1 15 1 33 2 31 0 37 7 23...

Page 29: ...an heat For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 2 Gross Cooling Capacities MBH 4 Ton Single Phase YSC048A1...

Page 30: ...or fan heat For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 5 Gross Cooling Capacities MBH 6 Ton Three Phase YSC072...

Page 31: ...refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity 7 Ton Standard Efficiency Performance Data Table PD 7 Gross Cooling Capacities MBH 7 Ton Dual Compresso...

Page 32: ...o appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 9 Gross Cooling Capacities MBH 10 Ton Three Phase YSC120A3 A4 AW AK AmbientTemperature F 85 95 105 115...

Page 33: ...heat For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 10 Gross Cooling Capacities MBH 3 Ton YHC036A1 A3 A4 AW Ambien...

Page 34: ...For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 13 Gross Cooling Capacities MBH 5 Ton Three Phase YHC060A3 A4 AW Am...

Page 35: ...la refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 15 Gross Cooling Capacities MBH 7 Ton Dual Compressors Three Phase YHC092A3 A4 AW AmbientTem...

Page 36: ...propriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 17 Gross Cooling Capacities MBH 10 Ton Three Phase YHC120A3 A4 AW AmbientTemperature F 85 95 105 115 Enter...

Page 37: ...7 0 28 0 94 0 41 0 86 0 47 1080 0 73 0 38 0 50 0 29 0 91 0 43 0 82 0 39 1140 0 69 0 39 0 42 0 29 0 88 0 44 0 77 0 40 3 YSC036A L M 1200 0 66 0 40 0 34 0 30 0 84 0 45 0 74 0 41 Downflow Airflow 1260 0...

Page 38: ...8 0 89 0 41 0 81 0 47 1080 0 68 0 38 0 45 0 29 0 86 0 43 0 77 0 39 1140 0 64 0 39 0 37 0 29 0 83 0 44 0 72 0 40 3 YSC036A H 1200 0 61 0 40 0 29 0 30 0 79 0 45 0 69 0 41 Downflow Airflow 1260 0 55 0 41...

Page 39: ...93 1182 1 00 1214 1 07 1440 1113 0 90 1146 0 97 1178 1 04 1209 1 11 1240 1 18 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data i...

Page 40: ...270 1 21 1299 1 28 1440 1217 1 10 1250 1 18 1281 1 27 1311 1 35 1339 1 43 1 HP Standard Motor Field Supplied High Static Drive 2 Table PD 22 Belt Drive Evaporator Fan Performance 3 Ton YSC036A3 A4 AW...

Page 41: ...1265 1 31 1760 1185 1 19 1215 1 26 1246 1 33 1275 1 41 1304 1 49 1920 1230 1 37 1260 1 45 1 HPStandardMotor Field SuppliedHighStaticDrive 2 For Standard Evaporator Fan Speed RPM reference Table PD 86...

Page 42: ...308 1 34 1338 1 43 1600 1268 1 26 1300 1 35 1331 1 44 1760 1321 1 47 1920 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 Table PD 26 Belt Drive Evaporator Fan Performance 4 Ton YSC048A3 A4 AW L M Lo...

Page 43: ...M BHP RPM BHP 1 HPStandardMotor Drive 1600 1158 1 05 1 190 1 13 1221 1 20 1251 1 27 1281 1 35 1800 1216 1 28 1246 1 35 1276 1 43 2000 2200 2400 For Standard Evaporator Fan Speed RPM reference Table PD...

Page 44: ...ed External Static Pressure Inches of Water 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 HPStandard Motor Drive 1600 1274 1 28 1307 1 37 1338 1 46 1800 2000 2200 2400 Table P...

Page 45: ...0 1 45 1003 1 55 1034 1 66 2 HPOversized Motor Drive Performance Data 6Ton Standard Efficiency For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data includes pressure drop due to stan...

Page 46: ...data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data includes pressur...

Page 47: ...4 2 11 2540 1058 1 56 1090 1 68 1121 1 79 1152 1 90 1184 2 01 1214 2 13 1244 2 24 2880 1093 1 78 1123 1 90 1152 2 02 1181 2 14 1211 2 27 2 HPOversizedMotor Drive For Standard Evaporator Fan Speed RPM...

Page 48: ...786 0 91 818 0 99 857 1 08 900 1 18 939 1 30 976 1 41 1009 1 51 1042 1 61 1073 1 71 1103 1 82 2 HP Standard Motor High Static Drive Table PD 38 Continued External Static Pressure Inches of Water 1 10...

Page 49: ...1208 2 81 1236 2 95 1261 3 07 1287 3 21 1311 3 33 3 HPOversizedMotor Drive 3 HPOversizedMotor For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data includes pressure drop due to stan...

Page 50: ...1126 2 43 1157 2 57 1185 2 70 1212 2 83 3 HPOversizedMotor Drive 2 HPStandardMotor HighStaticDrive or3 HPOversizedMotor Table PD 43 Belt Drive Evaporator Fan Performance 7 Ton YSC090 092A3 A4 AW AK L...

Page 51: ...HP Standard Motor High Static Drive Kit Motor Drive or3 HPOversizedMotor Drive 2400 1101 1 59 1134 1 69 1166 1 80 1 197 1 90 1229 2 02 1259 2 13 1287 2 25 1317 2 37 1344 2 48 1373 2 61 2700 1148 1 92...

Page 52: ...ors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected For Standard Evaporator Fan Speed RPM reference Table PD 86...

Page 53: ...n motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 49 Continued External Static Pressure Inches...

Page 54: ...93 5 06 4800 1139 3 80 1161 4 00 1185 4 22 1208 4 43 1230 4 63 1253 4 85 1275 5 06 1295 5 27 1317 5 49 1337 5 71 5 HPOversizedMotor Drive Table PD 51 Continued External Static Pressure Inches of Water...

Page 55: ...8 1342 4 76 1363 4 94 1383 5 11 1401 5 28 4400 1250 4 28 1280 4 52 1307 4 75 1334 4 98 1359 5 20 1384 5 43 1405 5 62 4800 1305 5 03 1334 5 28 1361 5 54 For Standard Evaporator Fan Speed RPM reference...

Page 56: ...00 0 37 0 95 0 68 1 17 0 18 0 97 2400 0 26 0 97 0 55 1 20 960 0 74 0 36 0 56 0 28 0 89 0 38 0 82 0 35 1020 0 69 0 37 0 49 0 28 0 85 0 39 0 77 0 36 1080 0 65 0 38 0 44 0 29 0 82 0 41 0 74 0 38 1140 0 6...

Page 57: ...7 0 50 1 20 960 0 74 0 36 0 56 0 28 0 89 0 38 0 82 0 35 1020 0 69 0 37 0 49 0 28 0 85 0 39 0 77 0 36 1080 0 65 0 38 0 44 0 29 0 82 0 41 0 74 0 38 1140 0 61 0 39 0 37 0 29 0 77 0 43 0 69 0 40 3 YHC036A...

Page 58: ...SheaveAK69required FieldSuppliedBeltmaybe necessary 2 FieldSuppliedFanSheaveAK41required FieldSuppliedBeltmaybe necessary Factory supplied motors in commercial equipment are definite purpose motors sp...

Page 59: ...49 922 0 55 970 0 62 1016 0 69 1059 0 77 1099 0 84 1138 0 92 1174 1 00 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 Table PD 59 Continued External Static Pressure Inches of Water 1 10 1 20 1 30 1...

Page 60: ...ur fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 61 Belt Drive Evaporator Fan Performance...

Page 61: ...247 1 18 1278 1 26 1309 1 35 1337 1 43 1600 1268 1 27 1300 1 35 1332 1 45 1760 1320 1 47 1920 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 Table PD 63 Continued External Static Pressure Inches of...

Page 62: ...tors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 65 Belt Drive Evaporator Fan Performance 5 Ton YH...

Page 63: ...isance tripping or premature motor failure Our product s warranty will not be affected Table PD 67 Continued External Static Pressure Inches of Water 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM B...

Page 64: ...our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 68 Belt Drive Evaporator Fan Performanc...

Page 65: ...Fan Speed RPM reference Table PD 86 Notes Data includes pressure drop due to standard filters and wet coils No accessories or options are included in pressure drop data Refer to Table PD 89 to determi...

Page 66: ...888 1 70 918 1 85 3600 658 0 84 695 0 96 731 1 08 764 1 20 796 1 33 828 1 47 859 1 63 890 1 79 920 1 94 949 2 10 2 HPStandardMotor Drive Table PD 73 Belt Drive Evaporator Fan Performance 7 Ton YHC092...

Page 67: ...rs as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 75 Belt Drive Evaporator Fan Performance 7 Ton YHC0...

Page 68: ...our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 77 Belt Drive Evaporator Fan Performance 8 Ton YHC102A3 A4 AW M M...

Page 69: ...motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 79 Belt Drive Evaporator Fan Performance 8 Ton...

Page 70: ...as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 81 Belt Drive Evaporator Fan Performance 8 Ton YHC102A...

Page 71: ...964 2 50 991 2 66 1016 2 83 1040 3 00 1065 3 18 1090 3 38 1114 3 58 1138 3 79 1161 4 00 1184 4 22 5 HPOversizedMotor Drive For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data inclu...

Page 72: ...wn in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected 3 HPStandardMotor Drive Table PD 85 Belt Drive Evaporator Fan Perform...

Page 73: ...90 1150 1211 Factory set at 3 turns open Table PD 87 Standard Motor High Static Drive Accessory Sheave Fan Speed Rpm Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn T ons Model No Open Open Open Open Op...

Page 74: ...060A 2000 0 06 0 10 0 10 0 18 0 07 0 18 0 02 2400 0 09 0 14 0 14 0 26 0 10 0 26 0 04 1920 0 04 0 07 0 10 0 01 0 06 0 02 6 Y C072A 2400 0 06 0 09 0 11 0 02 0 08 0 02 2880 0 09 0 12 0 13 0 04 0 10 0 04...

Page 75: ...092A1 A3 A4 AW M 150 0 105 121 5 85 25 55 Y C090 092A1 A3 A4 AW AK H 200 0 140 162 0 113 35 65 Standardand Y C102A1 A3 A4 AW AK L 120 0 84 97 2 68 15 45 8 High Efficiency Y C102A1 A3 A4 AW M 150 0 10...

Page 76: ...6 16 4 16 2 16 0 15 7 15 4 2400 15 6 15 4 15 2 15 1 14 9 14 6 14 3 Tons SCFM 35 40 45 50 55 60 65 2400 16 7 17 3 18 0 18 7 19 3 20 1 20 9 2700 14 9 15 5 16 1 16 7 17 3 18 0 18 7 7 3000 13 1 13 7 14 2...

Page 77: ...ors This sensor includes a digital display of set point adjustment and space temperature in F Fahrenheit or C Celsius Includes FAN and SYSTEM buttons supports the service functions of the standard sen...

Page 78: ...e Heat Anticipator Automatic Changeover One Heat Two CoolThermostat Off Auto System Switch Auto On Fan Switch Programmable Electronic Night Setback Thermostat Heating setback and cooling setup with 7...

Page 79: ...0 14 4 20 13 6 20 YSC048AW 517 633 9 8 15 10 6 15 10 0 15 YSC060A1 187 253 47 3 60 49 0 60 YSC060A3 187 253 31 5 50 33 6 50 30 3 45 5 YSC060A4 414 506 16 0 25 16 3 25 15 6 25 YSC060AW 517 633 12 2 15...

Page 80: ...15 7 7 15 7 7 15 YHC048A1 187 253 29 4 45 31 5 50 YHC048A3 187 253 21 2 30 23 3 35 22 6 35 4 YHC048A4 414 506 11 0 15 12 6 15 11 8 15 YHC048AW 517 633 8 3 15 9 1 15 8 5 15 YHC060A1 187 253 39 5 60 41...

Page 81: ...2 2 Y C036A4 1 460 3 1 0 2 5 16 1 Y C036AW 1 575 3 1 0 1 7 13 2 Y C048A3 1 208 230 3 1 0 5 0 32 2 4 Y C048A4 1 460 3 1 0 2 5 16 1 Y C048AW 1 575 3 1 0 1 7 13 2 Y C060A3 1 208 230 3 1 0 5 0 32 2 5 Y C0...

Page 82: ...1 3450 11 4 64 1 1 40 1 1 4 3 YSC072A3 1 208 230 3 6 3450 19 0 156 1 1 70 3 85 9 30 6 YSC072A4 1 460 3 6 3450 10 1 75 1 1 70 2 50 5 80 YSC072AW 1 575 3 6 3450 7 7 54 1 1 70 1 54 3 60 YSC072AK 1 380 3...

Page 83: ...33 2 0 6 6 5 YHC060A4 1 460 3 4 5 3450 7 8 59 6 1 1 33 1 2 2 5 YHC060AW 1 575 3 4 5 3450 6 2 49 4 1 1 33 0 9 1 5 YHC072A3 1 208 230 3 5 7 3450 20 7 156 1 1 70 3 85 9 30 6 YHC072A4 1 460 3 5 7 3450 10...

Page 84: ...A L M Y C090 092 102A L 1 1 35 3000 3000 208 230 1 0 6 Y C072A H Y C090 092 102A M H 2 1 15 3500 208 230 1 0 42 Y C120A L M H Table ED 8 Electrical Characteristics Power Exhaust T ons Volts Phase HP R...

Page 85: ...cal electrical codes Wiring shown dotted is to be furnished and installed by the customer Typical Number Of Wires ZoneSensors A ManualChangeover 4 Manual AutoChangeover 5 Manual AutoChangeoverwith Sta...

Page 86: ...millimeters 1775 3 4 and 5 Ton Standard Efficiency Low and Medium Heat 3 and 4 Ton High Efficiency Low and Medium Heat 1775 3 4 and 5 Ton Standard Efficiency High Heat 3 and 4 Ton High Efficiency Hig...

Page 87: ...dimensions are in inches millimeters Dimensional Data 3 5 Tons Downflow Airflow Supply and Return Through the Base Utilities 3 5 Tons Unit Clearance and Roof Opening 3 5Tons 3 5 Tons Horizontal Airflo...

Page 88: ...RT PRC006 EN 88 Dimensional Data 3 5 Tons Downflow Duct Connections Field Fabricated 3 5Tons All dimensions are in inches millimeters 3 5 Tons Roof Curb...

Page 89: ...T PRC006 EN Dimensional Data 6 10Tons 6 Ton Standard and High Efficiency 7 Ton Standard Efficiency All dimensions are in inches millimeters 7 Ton High Efficiency 8 and 10 Ton Standard and High Efficie...

Page 90: ...nsional Data All dimensions are in inches millimeters 6 10 Tons Downflow Airflow Supply and Return Through the Base Utilities 6 10 Tons Horizontal Airflow Supply and Return 6 10 Tons Unit Clearance an...

Page 91: ...PRC006 EN Dimensional Data 6 10Tons All dimensions are in inches millimeters 6 10 Tons Roof Curb 6 10 Tons Downflow Duct Connections Field Fabricated 857 857 S U P P L Y R E T U R N ALL FLANGES 1 1 4...

Page 92: ...conomizer Manual or Motorized Damper Hood 3 5 Tons Barometric Relief Damper Hood 3 5 Tons Swing Diameter for Hinged Door s Option 3 5 Tons Height of Gas Pipe required from Inside Base of Unit to Gas S...

Page 93: ...Tons Height of Gas Pipe required from Inside Base of Unit to Gas Shut off assembly Factory Provided 6 10 Tons Economizer and Barometric Relief Damper Hoods 6 10 Tons Power Exhaust 21 3 8 543 MM 17 432...

Page 94: ...0 957 310 252 175 220 40 22 YSC120A 1063 958 317 261 177 202 41 21 10 YHC120A 1203 1060 342 277 197 245 40 22 Notes 1 Corner weights are given for information only 2 Weights are approximate Table W 2...

Page 95: ...it nameplate voltage Crankcase heater internal temperature and current sensitive motor overloads shall be included for maximum protection Compressors shall have internal spring isolation and sound muf...

Page 96: ...ol algorithm maintains accurate temperature control minimizes drift from set point and provides better building comfort A centralized Microprocessor shall provide anti short cycle timing and time dela...

Page 97: ...The assembly includes fully modulating 0 100 percent motor and dampers minimum position setting preset linkage wiring harness with plug spring return actuator and fixed dry bulb control The barometri...

Page 98: ...in hood and screen shall provide up to 50 percent outside air Motorized Outside Air Dampers Manually set outdoor air dampers shall provide up to 50 percent outside air Once set outdoor air dampers sha...

Page 99: ...99 RT PRC006 EN...

Page 100: ...fort trane com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Literature Order Number File Number Super...

Reviews: