7

RT-PRC006-EN

Features and
Benefits

Foil-Faced Insulation

All panels in the evaporator section of the
unit have cleanable foil-faced insulation.
All edges are either captured or sealed to
ensure no fibers get into the airstream.

Factory Built Roof Curbs

Available for downflow units. Only two
roof curbs for the entire Precedent line
simplifies curb selection.

Flexibility

Units are built to order in our standard
“shortest in the industry” ship cycle time.

Fresh Air

0 - 25% manual or 0 - 50% motorized
outside air hoods are available.

High Pressure Cutout

This factory-installed option is offered for
units that do not have High Pressure
Cutout as standard. All 3-phase units with
scroll compressors include High Pressure
cutout as standard.

High Static Drive Accessory

Available on many models, this high
static drive accessory extends the
capability of the standard motor. Avoid
expensive motors and operating costs by
installing this optimized sheave
accessory.

Hinged Access Doors

These doors permit easy access to the
filter, fan/heat,
and compressor/
control sections.
They reduce the
potential roof
damage from
screws or sharp
access door
corners.

LonTalk

®

Communications
Interface

The LonTalk
communications
interface allows
the unit to
communicate as a Tracer™LCI-V device
or directly with generic LonTalk Network
Building Automation System Controls.

Phase Monitor

Phase monitor shall provide 100%
protection for motors and compressors
against problems caused by phase loss,
phase imbalance, and phase reversal.
Phase monitor is equipped with an LED
that provides an ON or FAULT indicator.

Power Exhaust Option

This option is available on downflow units
and provides exhaust of the return air,
when using a downflow economizer, to
maintain proper building pressurization.
Great for relieving most building
overpressurization problems.

Progressive Tubular Heat Exchanger

The compact cabinet features a tubular
heat exchanger in low, medium and high
heat capacities.
The heat exchanger is fabricated using
stainless steel burners and corrosion-
resistant aluminized steel tubes as
standard on all models. It has an induced
draft blower to pull the gas mixture
through the burner tubes. The heater has
a direct spark ignition system which
doubles as a safety device to prove the
flame.
Gas electric Precedent models exceed all
California seasonal efficiency
requirements. They also perform better
than required to meet the California NOx
emission requirements.

Quick-Access Panels

Remove two screws for access to the
standardized internal components and
wiring.

Quick-Adjust Idler Arm

With the Quick-Adjust Idler Arm, the belt
and sheaves can be quickly adjusted
without moving the mounted fan motor.
The result is a major savings in time and
money.

Reference or Comparative Enthalpy

Measures and communicates humidity
while maximizing comfort control.

Sloped Drain Pans

Every Precedent unit has a non-
corrosive, removable,
double-sloped
drain pan that’s
easy to clean and
reversible to allo w
installation of drain
trap on either side
of the unit.

Standardized
Components

Components are placed
in the same location on
all Precedent units.
Familiarize yourself with one Precedent
and you are familiar with every
Precedent.
Due to standardized components
throughout the Precedent line,
contractors/owners can stock fewer
parts.

Supply and/or Return Air Smoke
Detector

 With this option installed, if smoke is
detected, all unit operation will be shut

down. Reset will be
manual at the unit. Return
Air Smoke Detectors

require minimum
allowable airflow when

used with certain models.

Thermal Expansion Valve

Available for a wider
range of applications.

Trane Communication
Interface (TCI)

Available factory or field installed. This
module when applied with the ReliaTel™
easily interfaces with Trane’s Integrated
Comfort

TM

 System.

Summary of Contents for YSC060A1

Page 1: ...Packaged Gas Electric Rooftop Units Precedent 3 10T ons 60 Hz RT PRC006 EN October 2004...

Page 2: ...lity as the original Micro with additional benefits for greater application flexibility With its sleek compact cabinet rounded corners and beveled top Precedent continues to provide the highest standa...

Page 3: ...cation Considerations Selection Procedure Model Number Description General Data Performance Data Cooling Performance Fan Performance Heating Performance Controls Electric Power Dimension andWeights Me...

Page 4: ...Disconnect Switch Two Inch Pleated Filters Factory or Field Installed Options Clogged Filter Fan Failure Switch Differential Pressure Switches DischargeAir Sensing Kit Economizer Electric Heaters Fros...

Page 5: ...jumper betweenTest 1 andTest 2 terminals on the LowVoltage Terminal Board and the unit will walk through its operational steps automatically The unit automatically returns control to the zone sensor a...

Page 6: ...wires and diagnosing the unit Outstanding Standard and Optional Components Compressors Precedent contains the best compressor technology available to achieve the highest possible performance Our compr...

Page 7: ...overpressurization problems ProgressiveTubular Heat Exchanger The compact cabinet features a tubular heat exchanger in low medium and high heat capacities The heat exchanger is fabricated using stain...

Page 8: ...moke detector or fire control panel The ventilation override kit is available as a field installed accessory Zone Sensors Available in programmable automatic and manual styles Precedent offers ultimat...

Page 9: ...Electrical option with an Electrical Heater the heater must be factory installed Powered or Unpowered Convenience Outlet This option is a GFCI 120v 15amp 2 plug convenience outlet either powered or u...

Page 10: ...ge Cooling Standard or High Efficiency Cooling available Economizer Equipped with either dry bulb reference or comparative enthalpy sensing this feature provides free cooling as the outdoor temperatur...

Page 11: ...unit return air section also increases opening the dampers and relieving the conditioned space NOTE THE EFFECTIVENESS OF BAROMETRIC RELIEF DAMPER DURING ECONOMIZING OPERATION IS SYSTEM RELATED PRESSUR...

Page 12: ...hen round up to the nearest unit size 58 MBh 12 MBh approx 5 tons Step 3 Examine gross capacity Table PD 13 shows that aYHC060A4 has a gross cooling capacity of 62 4 MBh and 48 4 MBh sensible capacity...

Page 13: ...52 25 db 57 84 wb Step 3b Determine leaving unit temperature in standard cooling mode Repeat Step 3a substituting net sensible or latent capacity for gross sensible or latent capacity to find the lea...

Page 14: ...Oversized Motor 2 Optional Belt Drive Motor DIGIT 16 Hinged Service AccessFilters 0 Standard Panels Standard Filters A Hinged Access Panels Standard Filters B Standard Panels 2 Pleated Filters C Hing...

Page 15: ...on Pipe Size in 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 Compressor No Type 1 Hermetic 1 Hermetic 1 Scroll 1 Scroll Outdoor Sound Rating dB 6 83 83 86 82 Outdoor Coil Type Lanced Lanced Lanced...

Page 16: ...basedonARIStandard210 240exceptAK 380V 60Hz 2 EER and or SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Stand...

Page 17: ...10 0 14 0 10 0 14 0 10 0 14 0 Gas Connection Pipe Size in 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 3 4 Compressor No Type 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 6 84 84 88 Outdoor Coil Type Lanced...

Page 18: ...10 240 or 360 Units are rated at 80 F ambient 80 F entering dry bulb and 67 F entering wet bulb at ARI rated cfm 4 Heating Performance limit settings and rating data were established and approved unde...

Page 19: ...81 80 81 81 81 No Burners 3 3 4 3 3 4 3 3 4 No Stages 1 2 2 1 2 2 1 2 2 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 4 5 14 0 4 5 14 0 LP minimum maximum 10 0 14 0 10 0 14 0 10 0 14 0 Gas...

Page 20: ...ceptAK 380V 60Hz units 2 EER and or SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Standard 210 240 or 360 Uni...

Page 21: ...utput Btu 121 500 162 000 202 500 AFUE 5 81 81 81 Steady State Efficiency 81 81 81 No Burners 3 4 5 No Stages 2 2 2 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 LP minimum maximum 10 0 14...

Page 22: ...tandard210 240exceptAK 380V 60Hz 2 EER and or SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Standard 210 240...

Page 23: ...y 8 81 81 81 81 81 81 No Burners 2 2 3 2 2 3 No Stages 1 1 1 1 1 1 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 4 5 14 0 LP minimum maximum 10 0 14 0 10 0 14 0 Gas Connection Pipe Size in...

Page 24: ...ordance with the Unitary Air Conditioner Equipment certification program which is basedonARIStandard210 240 2 SEER are rated at ARI conditions and in accordance with DOE test procedures 3 Heating Perf...

Page 25: ...No Burners 2 2 3 2 2 3 2 3 3 No Stages 1 1 1 1 1 1 1 1 2 Gas Supply Line Pressure Natural minimum maximum 4 5 14 0 4 5 14 0 4 5 14 0 LP minimum maximum 10 0 14 0 10 0 14 0 10 0 14 0 Gas Connection Pip...

Page 26: ...its are certified in accordance with the Unitary Air Conditioner Equipment certification program whichisbasedonARIStandard210 240 2 EER and or SEER are rated at ARI conditions and in accordance with D...

Page 27: ...0 1 750 1 750 1 750 1 750 3 450 Motor Frame Size Standard Oversized 56 56 56 56 56 56 Filters Type Furnished 1 1 Throwaway Throwaway Throwaway No Size Recommended 4 20 x 25 x 2 4 20 x 25 x 2 4 20 x 25...

Page 28: ...31 5 31 7 31 6 36 3 24 2 90 40 2 40 2 40 4 39 2 42 3 30 1 38 8 38 8 38 8 38 8 40 9 30 2 37 1 37 1 37 0 37 0 39 1 30 3 34 6 34 6 34 6 34 6 36 6 30 0 75 36 4 32 6 39 4 23 5 41 1 15 1 33 2 31 0 37 7 23...

Page 29: ...an heat For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 2 Gross Cooling Capacities MBH 4 Ton Single Phase YSC048A1...

Page 30: ...or fan heat For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 5 Gross Cooling Capacities MBH 6 Ton Three Phase YSC072...

Page 31: ...refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity 7 Ton Standard Efficiency Performance Data Table PD 7 Gross Cooling Capacities MBH 7 Ton Dual Compresso...

Page 32: ...o appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 9 Gross Cooling Capacities MBH 10 Ton Three Phase YSC120A3 A4 AW AK AmbientTemperature F 85 95 105 115...

Page 33: ...heat For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 10 Gross Cooling Capacities MBH 3 Ton YHC036A1 A3 A4 AW Ambien...

Page 34: ...For indoor fan heat formula refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 13 Gross Cooling Capacities MBH 5 Ton Three Phase YHC060A3 A4 AW Am...

Page 35: ...la refer to appropriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 15 Gross Cooling Capacities MBH 7 Ton Dual Compressors Three Phase YHC092A3 A4 AW AmbientTem...

Page 36: ...propriate airflow tablenotes 2 MBH Total Gross Capacity 3 SHC Sensible Heat Capacity Table PD 17 Gross Cooling Capacities MBH 10 Ton Three Phase YHC120A3 A4 AW AmbientTemperature F 85 95 105 115 Enter...

Page 37: ...7 0 28 0 94 0 41 0 86 0 47 1080 0 73 0 38 0 50 0 29 0 91 0 43 0 82 0 39 1140 0 69 0 39 0 42 0 29 0 88 0 44 0 77 0 40 3 YSC036A L M 1200 0 66 0 40 0 34 0 30 0 84 0 45 0 74 0 41 Downflow Airflow 1260 0...

Page 38: ...8 0 89 0 41 0 81 0 47 1080 0 68 0 38 0 45 0 29 0 86 0 43 0 77 0 39 1140 0 64 0 39 0 37 0 29 0 83 0 44 0 72 0 40 3 YSC036A H 1200 0 61 0 40 0 29 0 30 0 79 0 45 0 69 0 41 Downflow Airflow 1260 0 55 0 41...

Page 39: ...93 1182 1 00 1214 1 07 1440 1113 0 90 1146 0 97 1178 1 04 1209 1 11 1240 1 18 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data i...

Page 40: ...270 1 21 1299 1 28 1440 1217 1 10 1250 1 18 1281 1 27 1311 1 35 1339 1 43 1 HP Standard Motor Field Supplied High Static Drive 2 Table PD 22 Belt Drive Evaporator Fan Performance 3 Ton YSC036A3 A4 AW...

Page 41: ...1265 1 31 1760 1185 1 19 1215 1 26 1246 1 33 1275 1 41 1304 1 49 1920 1230 1 37 1260 1 45 1 HPStandardMotor Field SuppliedHighStaticDrive 2 For Standard Evaporator Fan Speed RPM reference Table PD 86...

Page 42: ...308 1 34 1338 1 43 1600 1268 1 26 1300 1 35 1331 1 44 1760 1321 1 47 1920 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 Table PD 26 Belt Drive Evaporator Fan Performance 4 Ton YSC048A3 A4 AW L M Lo...

Page 43: ...M BHP RPM BHP 1 HPStandardMotor Drive 1600 1158 1 05 1 190 1 13 1221 1 20 1251 1 27 1281 1 35 1800 1216 1 28 1246 1 35 1276 1 43 2000 2200 2400 For Standard Evaporator Fan Speed RPM reference Table PD...

Page 44: ...ed External Static Pressure Inches of Water 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP 1 HPStandard Motor Drive 1600 1274 1 28 1307 1 37 1338 1 46 1800 2000 2200 2400 Table P...

Page 45: ...0 1 45 1003 1 55 1034 1 66 2 HPOversized Motor Drive Performance Data 6Ton Standard Efficiency For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data includes pressure drop due to stan...

Page 46: ...data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data includes pressur...

Page 47: ...4 2 11 2540 1058 1 56 1090 1 68 1121 1 79 1152 1 90 1184 2 01 1214 2 13 1244 2 24 2880 1093 1 78 1123 1 90 1152 2 02 1181 2 14 1211 2 27 2 HPOversizedMotor Drive For Standard Evaporator Fan Speed RPM...

Page 48: ...786 0 91 818 0 99 857 1 08 900 1 18 939 1 30 976 1 41 1009 1 51 1042 1 61 1073 1 71 1103 1 82 2 HP Standard Motor High Static Drive Table PD 38 Continued External Static Pressure Inches of Water 1 10...

Page 49: ...1208 2 81 1236 2 95 1261 3 07 1287 3 21 1311 3 33 3 HPOversizedMotor Drive 3 HPOversizedMotor For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data includes pressure drop due to stan...

Page 50: ...1126 2 43 1157 2 57 1185 2 70 1212 2 83 3 HPOversizedMotor Drive 2 HPStandardMotor HighStaticDrive or3 HPOversizedMotor Table PD 43 Belt Drive Evaporator Fan Performance 7 Ton YSC090 092A3 A4 AW AK L...

Page 51: ...HP Standard Motor High Static Drive Kit Motor Drive or3 HPOversizedMotor Drive 2400 1101 1 59 1134 1 69 1166 1 80 1 197 1 90 1229 2 02 1259 2 13 1287 2 25 1317 2 37 1344 2 48 1373 2 61 2700 1148 1 92...

Page 52: ...ors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected For Standard Evaporator Fan Speed RPM reference Table PD 86...

Page 53: ...n motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 49 Continued External Static Pressure Inches...

Page 54: ...93 5 06 4800 1139 3 80 1161 4 00 1185 4 22 1208 4 43 1230 4 63 1253 4 85 1275 5 06 1295 5 27 1317 5 49 1337 5 71 5 HPOversizedMotor Drive Table PD 51 Continued External Static Pressure Inches of Water...

Page 55: ...8 1342 4 76 1363 4 94 1383 5 11 1401 5 28 4400 1250 4 28 1280 4 52 1307 4 75 1334 4 98 1359 5 20 1384 5 43 1405 5 62 4800 1305 5 03 1334 5 28 1361 5 54 For Standard Evaporator Fan Speed RPM reference...

Page 56: ...00 0 37 0 95 0 68 1 17 0 18 0 97 2400 0 26 0 97 0 55 1 20 960 0 74 0 36 0 56 0 28 0 89 0 38 0 82 0 35 1020 0 69 0 37 0 49 0 28 0 85 0 39 0 77 0 36 1080 0 65 0 38 0 44 0 29 0 82 0 41 0 74 0 38 1140 0 6...

Page 57: ...7 0 50 1 20 960 0 74 0 36 0 56 0 28 0 89 0 38 0 82 0 35 1020 0 69 0 37 0 49 0 28 0 85 0 39 0 77 0 36 1080 0 65 0 38 0 44 0 29 0 82 0 41 0 74 0 38 1140 0 61 0 39 0 37 0 29 0 77 0 43 0 69 0 40 3 YHC036A...

Page 58: ...SheaveAK69required FieldSuppliedBeltmaybe necessary 2 FieldSuppliedFanSheaveAK41required FieldSuppliedBeltmaybe necessary Factory supplied motors in commercial equipment are definite purpose motors sp...

Page 59: ...49 922 0 55 970 0 62 1016 0 69 1059 0 77 1099 0 84 1138 0 92 1174 1 00 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 Table PD 59 Continued External Static Pressure Inches of Water 1 10 1 20 1 30 1...

Page 60: ...ur fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 61 Belt Drive Evaporator Fan Performance...

Page 61: ...247 1 18 1278 1 26 1309 1 35 1337 1 43 1600 1268 1 27 1300 1 35 1332 1 45 1760 1320 1 47 1920 1 HPStandardMotor FieldSuppliedHighStaticDrive 2 Table PD 63 Continued External Static Pressure Inches of...

Page 62: ...tors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 65 Belt Drive Evaporator Fan Performance 5 Ton YH...

Page 63: ...isance tripping or premature motor failure Our product s warranty will not be affected Table PD 67 Continued External Static Pressure Inches of Water 1 10 1 20 1 30 1 40 1 50 CFM RPM BHP RPM BHP RPM B...

Page 64: ...our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 68 Belt Drive Evaporator Fan Performanc...

Page 65: ...Fan Speed RPM reference Table PD 86 Notes Data includes pressure drop due to standard filters and wet coils No accessories or options are included in pressure drop data Refer to Table PD 89 to determi...

Page 66: ...888 1 70 918 1 85 3600 658 0 84 695 0 96 731 1 08 764 1 20 796 1 33 828 1 47 859 1 63 890 1 79 920 1 94 949 2 10 2 HPStandardMotor Drive Table PD 73 Belt Drive Evaporator Fan Performance 7 Ton YHC092...

Page 67: ...rs as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 75 Belt Drive Evaporator Fan Performance 7 Ton YHC0...

Page 68: ...our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 77 Belt Drive Evaporator Fan Performance 8 Ton YHC102A3 A4 AW M M...

Page 69: ...motors as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 79 Belt Drive Evaporator Fan Performance 8 Ton...

Page 70: ...as shown in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected Table PD 81 Belt Drive Evaporator Fan Performance 8 Ton YHC102A...

Page 71: ...964 2 50 991 2 66 1016 2 83 1040 3 00 1065 3 18 1090 3 38 1114 3 58 1138 3 79 1161 4 00 1184 4 22 5 HPOversizedMotor Drive For Standard Evaporator Fan Speed RPM reference Table PD 86 Notes Data inclu...

Page 72: ...wn in our tabular data will not result in nuisance tripping or premature motor failure Our product s warranty will not be affected 3 HPStandardMotor Drive Table PD 85 Belt Drive Evaporator Fan Perform...

Page 73: ...90 1150 1211 Factory set at 3 turns open Table PD 87 Standard Motor High Static Drive Accessory Sheave Fan Speed Rpm Unit 6Turns 5Turns 4Turns 3Turns 2Turns 1Turn T ons Model No Open Open Open Open Op...

Page 74: ...060A 2000 0 06 0 10 0 10 0 18 0 07 0 18 0 02 2400 0 09 0 14 0 14 0 26 0 10 0 26 0 04 1920 0 04 0 07 0 10 0 01 0 06 0 02 6 Y C072A 2400 0 06 0 09 0 11 0 02 0 08 0 02 2880 0 09 0 12 0 13 0 04 0 10 0 04...

Page 75: ...092A1 A3 A4 AW M 150 0 105 121 5 85 25 55 Y C090 092A1 A3 A4 AW AK H 200 0 140 162 0 113 35 65 Standardand Y C102A1 A3 A4 AW AK L 120 0 84 97 2 68 15 45 8 High Efficiency Y C102A1 A3 A4 AW M 150 0 10...

Page 76: ...6 16 4 16 2 16 0 15 7 15 4 2400 15 6 15 4 15 2 15 1 14 9 14 6 14 3 Tons SCFM 35 40 45 50 55 60 65 2400 16 7 17 3 18 0 18 7 19 3 20 1 20 9 2700 14 9 15 5 16 1 16 7 17 3 18 0 18 7 7 3000 13 1 13 7 14 2...

Page 77: ...ors This sensor includes a digital display of set point adjustment and space temperature in F Fahrenheit or C Celsius Includes FAN and SYSTEM buttons supports the service functions of the standard sen...

Page 78: ...e Heat Anticipator Automatic Changeover One Heat Two CoolThermostat Off Auto System Switch Auto On Fan Switch Programmable Electronic Night Setback Thermostat Heating setback and cooling setup with 7...

Page 79: ...0 14 4 20 13 6 20 YSC048AW 517 633 9 8 15 10 6 15 10 0 15 YSC060A1 187 253 47 3 60 49 0 60 YSC060A3 187 253 31 5 50 33 6 50 30 3 45 5 YSC060A4 414 506 16 0 25 16 3 25 15 6 25 YSC060AW 517 633 12 2 15...

Page 80: ...15 7 7 15 7 7 15 YHC048A1 187 253 29 4 45 31 5 50 YHC048A3 187 253 21 2 30 23 3 35 22 6 35 4 YHC048A4 414 506 11 0 15 12 6 15 11 8 15 YHC048AW 517 633 8 3 15 9 1 15 8 5 15 YHC060A1 187 253 39 5 60 41...

Page 81: ...2 2 Y C036A4 1 460 3 1 0 2 5 16 1 Y C036AW 1 575 3 1 0 1 7 13 2 Y C048A3 1 208 230 3 1 0 5 0 32 2 4 Y C048A4 1 460 3 1 0 2 5 16 1 Y C048AW 1 575 3 1 0 1 7 13 2 Y C060A3 1 208 230 3 1 0 5 0 32 2 5 Y C0...

Page 82: ...1 3450 11 4 64 1 1 40 1 1 4 3 YSC072A3 1 208 230 3 6 3450 19 0 156 1 1 70 3 85 9 30 6 YSC072A4 1 460 3 6 3450 10 1 75 1 1 70 2 50 5 80 YSC072AW 1 575 3 6 3450 7 7 54 1 1 70 1 54 3 60 YSC072AK 1 380 3...

Page 83: ...33 2 0 6 6 5 YHC060A4 1 460 3 4 5 3450 7 8 59 6 1 1 33 1 2 2 5 YHC060AW 1 575 3 4 5 3450 6 2 49 4 1 1 33 0 9 1 5 YHC072A3 1 208 230 3 5 7 3450 20 7 156 1 1 70 3 85 9 30 6 YHC072A4 1 460 3 5 7 3450 10...

Page 84: ...A L M Y C090 092 102A L 1 1 35 3000 3000 208 230 1 0 6 Y C072A H Y C090 092 102A M H 2 1 15 3500 208 230 1 0 42 Y C120A L M H Table ED 8 Electrical Characteristics Power Exhaust T ons Volts Phase HP R...

Page 85: ...cal electrical codes Wiring shown dotted is to be furnished and installed by the customer Typical Number Of Wires ZoneSensors A ManualChangeover 4 Manual AutoChangeover 5 Manual AutoChangeoverwith Sta...

Page 86: ...millimeters 1775 3 4 and 5 Ton Standard Efficiency Low and Medium Heat 3 and 4 Ton High Efficiency Low and Medium Heat 1775 3 4 and 5 Ton Standard Efficiency High Heat 3 and 4 Ton High Efficiency Hig...

Page 87: ...dimensions are in inches millimeters Dimensional Data 3 5 Tons Downflow Airflow Supply and Return Through the Base Utilities 3 5 Tons Unit Clearance and Roof Opening 3 5Tons 3 5 Tons Horizontal Airflo...

Page 88: ...RT PRC006 EN 88 Dimensional Data 3 5 Tons Downflow Duct Connections Field Fabricated 3 5Tons All dimensions are in inches millimeters 3 5 Tons Roof Curb...

Page 89: ...T PRC006 EN Dimensional Data 6 10Tons 6 Ton Standard and High Efficiency 7 Ton Standard Efficiency All dimensions are in inches millimeters 7 Ton High Efficiency 8 and 10 Ton Standard and High Efficie...

Page 90: ...nsional Data All dimensions are in inches millimeters 6 10 Tons Downflow Airflow Supply and Return Through the Base Utilities 6 10 Tons Horizontal Airflow Supply and Return 6 10 Tons Unit Clearance an...

Page 91: ...PRC006 EN Dimensional Data 6 10Tons All dimensions are in inches millimeters 6 10 Tons Roof Curb 6 10 Tons Downflow Duct Connections Field Fabricated 857 857 S U P P L Y R E T U R N ALL FLANGES 1 1 4...

Page 92: ...conomizer Manual or Motorized Damper Hood 3 5 Tons Barometric Relief Damper Hood 3 5 Tons Swing Diameter for Hinged Door s Option 3 5 Tons Height of Gas Pipe required from Inside Base of Unit to Gas S...

Page 93: ...Tons Height of Gas Pipe required from Inside Base of Unit to Gas Shut off assembly Factory Provided 6 10 Tons Economizer and Barometric Relief Damper Hoods 6 10 Tons Power Exhaust 21 3 8 543 MM 17 432...

Page 94: ...0 957 310 252 175 220 40 22 YSC120A 1063 958 317 261 177 202 41 21 10 YHC120A 1203 1060 342 277 197 245 40 22 Notes 1 Corner weights are given for information only 2 Weights are approximate Table W 2...

Page 95: ...it nameplate voltage Crankcase heater internal temperature and current sensitive motor overloads shall be included for maximum protection Compressors shall have internal spring isolation and sound muf...

Page 96: ...ol algorithm maintains accurate temperature control minimizes drift from set point and provides better building comfort A centralized Microprocessor shall provide anti short cycle timing and time dela...

Page 97: ...The assembly includes fully modulating 0 100 percent motor and dampers minimum position setting preset linkage wiring harness with plug spring return actuator and fixed dry bulb control The barometri...

Page 98: ...in hood and screen shall provide up to 50 percent outside air Motorized Outside Air Dampers Manually set outdoor air dampers shall provide up to 50 percent outside air Once set outdoor air dampers sha...

Page 99: ...99 RT PRC006 EN...

Page 100: ...fort trane com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice Literature Order Number File Number Super...

Reviews: