background image

Page  11

Demand Defrost Control Checkout

SYMPTOMS

CHECKS

YES/NO

ACTIONS

 1. LED off.

1. 24V R-B & Y-B at board, with unit running?

N

Repair low voltage wiring.

Y

Complete Check #2.

2.Short FRC_DFT pin to TEST_COMMON pin.

Is defrost cycle initiated?

N

Replace defrost control.

Y

LED is bad but control will still function.

 2. LED flashing very rapidly (greater
than 4 times/sec) or appears to be on
continuously.

TEST_COMMON pin shorted to TST pin?

Y

Remove short.

N

Replace defrost control.

 3. Control does not initiate a normal

defrost.

OD Temp. below 49°F.
OD Coil temp. below 35°F.?
"Delta" T increasing?

N

Check refrigerant circuits for balanced
distribution of refrigerant if OD coil is
frosting and delta T is not increasing

1. LED flashing?

N

Refer to SYMPTOM #1.

Y

Complete Check #2.

2. Check for 24V Y-B at board with unit running.

N

Repair low voltage wiring.

Y

Complete Check #3.

3. Check sensors for correct mounting

(connection) and resistance.

Remount or replace sensor if necessary.

4. Short FRC_DFT pin to TEST_COMMON pin.
 Is defrost cycle initiated?

N

Replace defrost control.

Y

Y-B signal or control may be intermittent

 4. Control does not initiate a forced

defrost.

24V R-B & Y-B at board with unit running?

N

Repair low voltage wiring.

Y

Replace defrost control.

 5. Defrost initiates manually but terminates in less than 10 seconds.

Replace defrost control.

 6. Defrost initiates manually but
terminates on time.

1. Coil sensor circuit open or reading at a very

high resistance?

Y

Replace coil sensor.

2. Does OD fan cycle off in defrost?

N

Replace defrost control.

3. Windy weather preventing normal
termination?

 7. Defrost initiates on approximately

15/25 minute intervals.

Be sure OD coil is clean.

N

Complete Check #2.

1. Coil sensor open or reading a very

high resistance?

Y

Replace coil sensor.

2. Ambient sensor reading less than normal?

N

Complete Check #3.

Y

Replace ambient sensor.

3. OD fan off in defrost?

N

Replace defrost control.

 8. Defrost initiates on approximately

30/45 minute intervals.

1.TEST_COMMON pin shorted to TST pin?

Y

 Remove short.

2. Do both sensors check OK?

N

Replace defective sensor (Clear coil and
reset Emergency heat light).

Y

Complete SYMPTOM #3.

3. Verify correct system charge.

Adjust as needed.

4. Verify a "forced defrost" terminates less than

15 minutes.

N

Replace defrost control.

5. OD fan motor off in defrost.

See SYMPTOM #9.

6. Verify proper SOV operation.

Replace if necessary.

 9. OD fan runs during defrost.

Replace defrost control.

10. No SOV delay on defrost

termination.

Has J1 been cut?

Y

The soft-switch time is defeated when J1

is cut.

N

Replace defrost control.

11. ODS-A burned out.

1. B to T greater than 10 volts?

Y

Check low voltage wiring for miswire.

N

Check for short in low voltage wiring.

12. On SCROLL bearing units,

compressor does not operate.

1. 24V  R-B at board & 24V Y-B at board?

N

Repair low voltage wiring.

2. Check protective devices in YO circuit . 24V
YO-B present after 30 seconds.

N

Y-B signal or control may be intermittent

13.  On SCROLL bearing units, no 30

second off delay at defrost initiation.

Check voltage between control terminals 2 and
7,force a defrost cycle. Is 24V present for 30
seconds and 0V thereafter?

N

Replace defrost control.

Summary of Contents for WCH024C1

Page 1: ... conducting electri cal current are grounded If grounding wires screws straps clips nuts or washers used to complete a path to ground are removed for service they must be returned to their original position and properly fastened ALL phases of this installation must comply with NATIONAL STATE and LOCAL CODES These instructions do not purport to cover all variations in systems nor to provide for eve...

Page 2: ...ade to deflect the warm discharge air from under the overhang See Figures 1 2 and 5 The unit must also be situated to permit easy and unrestricted access for service Install internal accessories to the unit at the shop if practical Position the unit so roof run off water does not pour directly onto the unit CAUTION MUST ALWAYS BE TAKEN TO AVOID PER SONAL INJURIES AND OR DAMAGE TO THE EQUIPMENT In ...

Page 3: ...1 INSTALLATION SERVICE CLEARANCE BACK 48 0 LEFT SIDE 24 0 RIGHT SIDE 36 0 TOP 36 0 MODEL APPROX CORNER WTS LBS TOTAL WEIGHT LBS COIL DIMENSION in W1 W2 W3 W4 A B WCH024C 79 73 63 68 282 14 16 WCH030C 80 71 62 70 284 14 16 WCH036C 83 75 66 73 297 14 16 WCH042C 84 79 72 77 312 20 16 ...

Page 4: ...d Clearances WCH048 060F Outline 1 INSTALLATION SERVICE CLEARANCE BACK 48 0 LEFT SIDE 24 0 RIGHT SIDE 36 0 TOP 36 0 MODEL APPROX CORNER WTS LBS TOTAL WEIGHT LBS W1 W2 W3 W4 WCH048F 128 128 97 97 447 WCH060F 115 115 114 114 457 ...

Page 5: ...d The pad must not contact the structure Be sure the outdoor portion of the supply and return air ducts are as short as possible The installation should proceed as follows The unit must be isolated with mounting pads The mounting pads must provide a minimum of 1 4 clearance beneath the unit to permit air circulation and prevent corrosion of the base See Figure 3 Attach the supply and return air du...

Page 6: ...RNING TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL SHOCK OR CONTACT WITH MOVING PARTS LOCK UNIT DISCONNECT SWITCH IN OPEN POSITION BEFORE SERVICING UNIT Do not short thermostat wires since this will damage the control transformer Recommended wire sizes and lengths for installing the unit thermostat are provided in Table 1 Thermostat Wire Size and Maximum Length The total resistance of these low vo...

Page 7: ...perature The outdoor fan motor compressor and evaporatorfan motor will oper ate automatically Start Up Operating Pressures After the unit has operated in the cooling mode for a short time install pressure gauges on the gauge ports of the discharge and suction line valves Check the suction and discharge pressures and compare them to the normal operating pressures provided in the unit s SERVICE FACT...

Page 8: ... fan relay F which starts the indoor fan motor SUPPLEMENTARY HEAT The supplementary electric heat is brought on when the indoor temperature drops 1 1 2 degrees below the thermostat setting TSH 2 contacts close providing power to the W termi nal on the indoor thermostat and to the supplementary heater control circuit NOTE The fan relay F must have been ener gized An outdoor thermostat may have been...

Page 9: ...y dry before re installing them in the unit Replace permanent filters annually if washing fails to clean them or if they show signs of deterioration Use the same type and size as was originally installed Outdoor Coil Unfiltered air circulated through the unit s outdoor coil can cause the coil s surface to become clogged with dust dirt etc To clean the coil stroke the coil surface with a soft brist...

Page 10: ...door ambient temperature with a sensor located outside the outdoor coil A second sensor located on the outdoor coil is used to measure the coil temperature The difference between the ambient and the colder coil temperature is the difference or delta T measurement This delta T measurement is representative of the operating state and relative capacity of the heat pump system By measuring the change ...

Page 11: ...nsor 2 Does OD fan cycle off in defrost N Replace defrost control 3 Windy weather preventing normal termination 7 Defrost initiates on approximately 15 25 minute intervals Be sure OD coil is clean N Complete Check 2 1 Coil sensor open or reading a very high resistance Y Replace coil sensor 2 Ambient sensor reading less than normal N Complete Check 3 Y Replace ambient sensor 3 OD fan off in defrost...

Page 12: ...ally this limited warranty will not apply unless the packaged unit is 1 installed by a licensed or qualified HVAC technician 2 applied and installed in accordance with the manufacturer s recommendations and its Installer s guide and 3 in compliance with all industry standards national state and local codes This limited warranty does not cover failure of your packaged unit if it is damaged while in...

Page 13: ...antor shall not be obligated to pay for the cost of lost refrigerant No liability shall attach to Warrantor until products have been paid for and then liability shall be limited solely to the purchase price of the equipment under warranty shown to be defective This limited warranty does not apply if the packaged unit was purchased direct i e from internet websites or auctions on an uninstalled ba ...

Page 14: ...record the following information to ensure your product registration process is quick and easy Packaged Unit Serial Number_____________________________________________________ Packaged Unit Model Number_____________________________________________________ Date of Installation______________________________________________________________ Dealer_______________________________________________________...

Reviews: