28
PKGP-PRC001-EN
Electrical
Data
*
Indicates both downflow and horizontal units.
Table ED-3 — Unit Wiring With Electric Heat (Single Point Connection)
Standard Indoor Motor
Oversize Indoor Motor
To Use
Heater
Heater
Control
Max Fuse Size or
Max Fuse Size or
Tons
With
Model No.
KW Rating
1
Stages
MCA
Max Circuit Breaker
2
MCA
Max Circuit Breaker
2
208/230 Volts Three Phase
AYDHTRK318A
13.5/18.0
1
113/120
125/125
119/127
125/150
WCD150B3
AYDHTRK336A
27.0/36.0
2
160/175
175/175
166/181
175/200
AYDHTRK354A
40.5/54.0
2
207/229
225/250
213/235
225/250
12½
AYHHTRN318A
13.5/18.0
1
113/120
125/125
119/127
125/150
WCH150B3
AYHHTRP336A
27.0/36.0
2
160/175
175/175
166/181
175/200
AYHHTRP354A
40.5/54.0
2
207/229
225/250
213/235
225/250
AYDHTRK318A
13.5/18.0
1
122/130
125/150
129/136
150/150
WCD180B3
AYDHTRK336A
27.0/36.0
2
169/184
175/200
175/190
175/200
AYDHTRK354A
40.5/54.0
2
216/238
225/250
222/244
225/250
15
AYHHTRN318A
13.5/18.0
1
122/130
125/150
129/136
150/150
WCH180B3
AYHHTRP336A
27.0/36.0
2
169/184
175/200
175/190
175/200
AYHHTRP354A
40.5/54.0
2
216/238
225/250
222/244
225/250
AYDHTRL336A
27.0/36.0
2
190/204
200/225
197/212
200/225
WCD240B3
AYDHTRL354A
40.5/54.0
2
237/258
250/300
244/266
250/300
AYDHTRK372A
54.0/72.0
2
284/312
300/350
291/320
300/350
20
AYHHTRN336A
27.0/36.0
2
190/204
200/225
197/212
200/225
WCH240B3
AYHHTRN354A
40.5/54.0
2
237/258
250/300
177/266
250/300
AYHHTRN372A
54.0/72.0
2
284/312
300/350
224/320
300/350
Notes:
1. Heater kw ratings are at 208/240 for 208/230V unit 480V for 460 V unit
2. HACR type circuit breaker per NEC.