16
PKGP-PRC001-EN
Performance
Data
(20 Ton)
Table PD-4 — Gross Cooling Capacities (MBh)
20 Ton Downflow Three Phase
WCD240B
Ambient Temperature (F)
85
95
105
115
Enter.
CFM
Dry
Entering Wet Bulb (F)
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
Airflow
(F)
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
212.0 177.0 233.0 137.0 243.0 89.7 198.0 173.0 228.0 133.0 244.0 87.3 179.0 164.0 211.0 130.0 239.0 83.1 160.0 154.0 189.0 115.0 225.0 76.8
80
219.0 218.0 234.0 165.0 246.0 122.0 204.0 204.0 229.0 168.0 247.0 123.0 188.0 188.0 212.0 160.0 240.0 118.0 172.0 172.0 190.0 150.0 225.0 112.0
7200
85
229.0 229.0 236.0 197.0 249.0 148.0 220.0 220.0 231.0 202.0 249.0 153.0 205.0 205.0 215.0 196.0 242.0 153.0 189.0 189.0 194.0 186.0 226.0 146.0
90
238.0 238.0 238.0 227.0 252.0 174.0 234.0 234.0 233.0 233.0 252.0 183.0 222.0 222.0 222.0 222.0 242.0 186.0 206.0 206.0 206.0 206.0 227.0 181.0
75
218.0 193.0 237.0 144.0 244.0 91.2 204.0 185.0 232.0 139.0 246.0 89.1 184.0 175.0 216.0 131.0 242.0 85.0 162.0 162.0 193.0 128.0 229.0 78.8
80
224.0 224.0 239.0 173.0 247.0 123.0 213.0 213.0 233.0 176.0 249.0 126.0 196.0 196.0 217.0 170.0 243.0 124.0 180.0 180.0 195.0 160.0 230.0 117.0
8000
85
234.0 234.0 241.0 207.0 250.0 150.0 228.0 228.0 235.0 213.0 252.0 158.0 215.0 215.0 221.0 210.0 244.0 159.0 197.0 197.0 197.0 197.0 230.0 155.0
90
242.0 242.0 245.0 238.0 253.0 178.0 240.0 240.0 240.0 240.0 254.0 190.0 231.0 231.0 231.0 231.0 246.0 195.0 216.0 216.0 216.0 216.0 232.0 193.0
75
223.0 201.0 238.0 148.0 245.0 93.4 209.0 196.0 235.0 145.0 248.0 90.6 189.0 186.0 220.0 138.0 244.0 86.8 168.0 168.0 196.0 136.0 232.0 80.6
80
229.0 229.0 241.0 177.0 248.0 139.0 220.0 220.0 236.0 184.0 250.0 128.0 204.0 204.0 221.0 180.0 246.0 129.0 186.0 186.0 199.0 170.0 233.0 122.0
8800
85
238.0 238.0 244.0 212.0 252.0 152.0 234.0 234.0 239.0 223.0 253.0 161.0 222.0 222.0 226.0 223.0 247.0 165.0 205.0 205.0 205.0 205.0 233.0 164.0
90
245.0 245.0 247.0 245.0 255.0 181.0 245.0 245.0 245.0 245.0 256.0 195.0 238.0 238.0 238.0 238.0 249.0 203.0 224.0 224.0 224.0 224.0 236.0 205.0
75
226.0 208.0 241.0 151.0 246.0 94.2 214.0 206.0 236.0 148.0 249.0 91.4 191.0 191.0 223.0 144.0 245.0 88.6 174.0 174.0 199.0 143.0 235.0 82.4
80
232.0 232.0 243.0 185.0 250.0 126.0 226.0 226.0 238.0 190.0 251.0 115.0 211.0 211.0 225.0 189.0 247.0 123.0 193.0 193.0 203.0 179.0 235.0 127.0
9600
85
241.0 241.0 245.0 222.0 253.0 155.0 239.0 239.0 242.0 231.0 255.0 165.0 229.0 229.0 229.0 229.0 249.0 170.0 212.0 212.0 212.0 212.0 236.0 171.0
90
248.0 248.0 247.0 247.0 256.0 184.0 248.0 248.0 248.0 248.0 258.0 200.0 243.0 243.0 243.0 243.0 252.0 210.0 231.0 231.0 231.0 231.0 239.0 215.0
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
Table PD-5 — Gross Cooling Capacities (MBh)
20 Ton Horizontal Three Phase
WCD240B
Ambient Temperature (F)
85
95
105
115
Enter.
CFM
Dry
Entering Wet Bulb (F)
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
Airflow
(F)
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
217.0 181.0 238.0 140.0 248.0 91.4 202.0 177.0 233.0 136.0 249.0 88.9 183.0 167.0 215.0 132.0 244.0 84.7 163.0 157.0 192.0 117.0 229.0 78.3
80
224.0 223.0 239.0 168.0 250.0 124.0 208.0 208.0 233.0 171.0 251.0 126.0 192.0 192.0 216.0 163.0 245.0 121.0 175.0 175.0 194.0 153.0 229.0 114.0
7200
85
233.0 233.0 241.0 201.0 253.0 151.0 224.0 224.0 235.0 206.0 254.0 156.0 209.0 209.0 219.0 200.0 246.0 156.0 192.0 192.0 198.0 190.0 230.0 149.0
90
242.0 242.0 242.0 230.0 256.0 177.0 238.0 238.0 238.0 238.0 257.0 186.0 226.0 226.0 226.0 226.0 247.0 189.0 210.0 210.0 210.0 210.0 231.0 185.0
75
223.0 197.0 241.0 147.0 249.0 93.5 208.0 188.0 236.0 142.0 251.0 90.8 188.0 178.0 220.0 134.0 247.0 86.6 165.0 165.0 196.0 130.0 233.0 80.3
80
228.0 228.0 244.0 176.0 252.0 126.0 217.0 217.0 237.0 180.0 254.0 128.0 200.0 200.0 221.0 174.0 248.0 126.0 183.0 183.0 199.0 163.0 234.0 119.0
8000
85
238.0 238.0 246.0 211.0 255.0 153.0 233.0 233.0 240.0 217.0 256.0 161.0 219.0 219.0 225.0 214.0 249.0 163.0 201.0 201.0 201.0 201.0 234.0 158.0
90
246.0 246.0 250.0 243.0 258.0 181.0 245.0 245.0 245.0 245.0 259.0 194.0 235.0 235.0 235.0 235.0 251.0 199.0 220.0 220.0 220.0 220.0 236.0 197.0
75
228.0 205.0 243.0 151.0 250.0 95.2 213.0 200.0 239.0 147.0 252.0 92.3 193.0 189.0 224.0 140.0 249.0 88.5 172.0 172.0 200.0 138.0 237.0 82.1
80
233.0 233.0 245.0 181.0 253.0 142.0 224.0 224.0 240.0 187.0 255.0 131.0 208.0 208.0 225.0 183.0 250.0 131.0 190.0 190.0 203.0 173.0 237.0 124.0
8800
85
242.0 242.0 248.0 216.0 256.0 155.0 239.0 239.0 243.0 227.0 258.0 165.0 227.0 227.0 230.0 227.0 252.0 169.0 209.0 209.0 209.0 209.0 238.0 167.0
90
249.0 249.0 252.0 250.0 260.0 184.0 249.0 249.0 249.0 249.0 261.0 199.0 242.0 242.0 242.0 242.0 254.0 207.0 228.0 228.0 228.0 228.0 240.0 208.0
75
231.0 212.0 245.0 153.0 251.0 96.0 218.0 210.0 241.0 151.0 253.0 93.1 195.0 195.0 227.0 146.0 250.0 90.3 177.0 177.0 203.0 146.0 239.0 84.0
80
237.0 237.0 247.0 188.0 254.0 128.0 230.0 230.0 243.0 194.0 256.0 117.0 215.0 215.0 229.0 193.0 251.0 125.0 196.0 196.0 207.0 183.0 240.0 130.0
9600
85
245.0 245.0 249.0 226.0 258.0 158.0 243.0 243.0 246.0 236.0 260.0 168.0 233.0 233.0 233.0 233.0 253.0 173.0 216.0 216.0 216.0 216.0 241.0 175.0
90
253.0 253.0 252.0 252.0 261.0 187.0 253.0 253.0 253.0 253.0 263.0 204.0 247.0 247.0 247.0 247.0 256.0 214.0 235.0 235.0 235.0 235.0 244.0 219.0
Notes:
1. Dry Coil Condition. Total Gross Cooling Capacity (MBh) shown to the left is not applicable. In this case the Sensible Heat Capacity (SHC) is the total capacity.
2. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
3. MBH = Total Gross Capacity
4. SHC = Sensible Heat Capacity
Summary of Contents for Voyager PKGP-PRC001-EN
Page 1: ...PackagedHeatPumps Voyager 12 to 20T ons 60 Hz PKGP PRC001 EN September 2004 ...
Page 34: ...34 PKGP PRC001 EN Typical Wiring 12 20Tons ...
Page 35: ...PKGP PRC001 EN 35 Typical Wiring 12 20Tons ...
Page 36: ...36 PKGP PRC001 EN Typical Wiring 12 20Tons ...