Parameter
Parameter name
Setting title
Setting
Function
5-01
Term 27 Mode
Input
0
Customer Interlock
5-02
Term 29 Mode
Output
1
Auto bypass
5-10
Term 18 digital input
Start
8
Common run/stop
5-11
Term 19 digital input
Run Permissive
52
Run Permissive
5-12
Term 27 digital input
External Interlock
7
Customer Interlock
5-31
Term 29 digital output
No Alarm
160
Auto bypass
5-40(0)
Relay 1 function
Start Command Active
167
Run Permissive
5-40(0)
Relay 1 off delay
Off Delay
0.00 S
Run Permissive
Table 6.1 Parameter Group 5-** Factory Default Settings
6.1.2 ECB Control Card
The ECB control card (see
) provides input connector X57 for commanding bypass operation remotely and output
connector X59 for reporting the bypass mode of operation, either drive mode or running in bypass.
See
for ECB control card terminal types and functions.
1
130BX232.10
2
3
4
1.
Terminal X58
2.
Terminal X56
3.
Terminal X57
4.
Terminal X59
Electronically Controlled B...
Vertical Bypass/Non Bypass Panel
6-2
MG.13.A1.22 - VLT
®
is a registered Danfoss trademark
6
6