![Trane VariTrac VAV-SVN03A-EN Installation Manual Download Page 37](http://html1.mh-extra.com/html/trane/varitrac-vav-svn03a-en/varitrac-vav-svn03a-en_installation-manual_1149754037.webp)
VAV-SVN03A-EN
31
2. 3 wires are required for sensor connection. 2 wires are required for 24 Vac power
connection. For wire lengths less than 75 feet, an 18 gage, 5 conductor cable may
be used. For wire lengths greater than 75 feet, use 18 gage, 2 conductor cable for
the power wiring (TB1-TB1), and 18 gage, 3 conductor cable for signal wiring
(TB2-TB3).
Figure 15:
Zone Temperature Sensor Controller Wiring
Zone Temperature Sensor Wiring