VAV-SVN03A-EN
28
Install the Zone Temperature Sensors
Five types of zone temperature sensors are available. The sensors are
shown below in Figure 14:
• sensor with night setback override button, cancel button, and communica-
tions jack
• sensor with adjustable setpoint, night setback override button, cancel
button, and communications jack
• sensor with adjustable setpoint and communications jack
• sensor with night setback override button, cancel button, and communica-
tions jack
• sensor only
• sensor with digital display, adjustable setpoint, night setpoint override
button, cancel button, and communications jack.
Figure 14:
Zone Sensor Options
Location
Proper temperature sensor location is crucial to occupant comfort. The
sensor should be placed in the most critical area of the zone where there is
free circulation of air. It should be mounted on a flat interior surface
approximately 54 inches from the floor, or as specified by the project plans
and specifications.
Avoid locating sensors in the following places:
• areas of direct sunlight
• areas blanketed by air from diffusers or subject to drafts
• surfaces with unconditioned areas behind them (such as an outside wall
or the wall of a storeroom)
Getting Started