Modulating Water Valves
(Option)
The modulating control valve option
provides optimum control of hot and
chilled water flow in various heating
and cooling applications. They are
designed to provide sinusoidal valve
actuator travel and operate silently,
resisting water hammer.
The actuator on the valve is a 24V, 3-
point floating type. See Table 3 for more
technical data.
Isolation Valves
(Option)
The isolation valves are two position
24V, spring return type. They provide
added control in heating and cooling
applications when used in conjunction
with the face and bypass damper.
On heating coils and two-pipe change-
over applications, the valve is a normal-
ly open type to prevent the coil from
freezing in case of power loss.
For cooling, the valve is normally
closed and opens when there is a call
for cooling. See Table 4, for more tech-
nical data.
Power Supply
24V - 50/60 Hz
Power Consumption
4W
Maximum Duty Cycle
15%
Nominal Timing
120 sec.
Operating Ambient
Temperature
0 to 65 C
32 to 150 F
Min./Max Fluid
Temperatures
1 to 95 C
34 to 203 F
Operating Pressure
Differential
Max. - 4 bar (60 psi)
Pressure Rating
Static- 20 bar (300psi)
Burst- 100 bar
(1500 psi)
Flow Characteristics
Linear
Power Supply
24V - 50/60 Hz
Power Consumption
5W
Max. Fluid Temp.
200 F/ 94 C
Min. Fluid Temp.
34 F / 1 C
Max. Operating
Pressure
300 psi
Max. Close-off
Pressure
1/2” = 30 psi
3/4” = 20 psi
1” = 15 psi
Table 3:
Technical Data for
Modulating Water Valves
Table 4:
Technical Data for Isolation
Water Valves
Summary of Contents for UV-SVN02B-EN
Page 38: ...38 UV SVN002 EN Wiring Diagrams Figure 44 Power Diagram For 480V 3 Phase 4 Wire Electric Heat...
Page 40: ...40 UV SVN002 EN Wiring Diagrams Figure 46 End Device Package 120V Hot Water DX Cooling...
Page 41: ...UV SVN002 EN 41 Wiring Diagrams Figure 47 208V or 240V 3 Phase 3 Wire Electric Heat DX Cooling...
Page 50: ...50 UV SVN002 EN Accessories Wall Boxes Figure 59 Vertical wallbox V1 V3 V2 V6 dimensions...