UNT-SVX10G-E4
10
Installation
Table 4 - General data - FED with inlet/discharge air connections (Dia. 200mm) and EU3 filter
230V/50Hz/1pH, Reversible coil, 2 Pipes
Speed at ESP = 50Pa
Unit size
200
300
400
500
600
Airflow (1)
(m3/h)
104
376
449
827
963
Standard coil, cooling mode
Air inlet conditions : 27°C/47%, Water : 7/12°C, Constant delta T°
Total / sensible cooling capacity (1)
(kW)
0.65 / 0.5
2.3 / 1.7
3 / 2.2
4.2 / 3.2
6.8 / 5
EER / Eurovent Energy class (2)
84 / B
100 / A
128 / A
78 / B
110 / A
Water flow (1)
(l/s)
0.031
0.11
0.14
0.2
0.33
Water pressure drop (1)
(kPa)
1.2
8.1
14.4
34.7
25.8
Water content
(l)
0.6
1.3
1.5
1.5
2.8
Water connection
1/2" ISO R7 female gas
Standard coil, heating mode
Air inlet : 20°C, Water inlet : 50°C, Water flow from cooling mode
Heating capacity (1)
(kW)
0.81
3
3.6
5.1
7.6
COP / Eurovent Energy class (2)
98 / A
191 / A
148 / A
86 / B
119 / A
Water flow (1)
(l/s)
0.031
0.11
0.14
0.2
0.33
Water pressure drop (1)
(kPa)
0.97
7.1
11.6
20.3
22.4
Electric heater (option)
Electric heater
(W)
500
500 / 750
1000 / 3000
1000 / 3000
1000 / 3000
Power supply
(V-Ph-Hz)
230-1-50
230-1-50
230-1-50
230-1-50
230-1-50
Power absorbed (speeds 1/3/5)
(W)
3.7/8.7/19
4.8/18/43
6/25/46
23/69/100
25/76/109
Absorbed current (min/max)
(A)
2.2
2.2/3.3
4.3/13
4.3/13
4.3/13
Fan motor
Maximun external static pressure
(Pa)
50
70
70
70
70
Sound levels
Supply sound power level (speeds 2 / 3 / 5) (3)
(dB(A))
32/38/47
39/46/56
36/52/58
47/57/60
47/57/60
Return sound power level (speeds 2 / 3 / 5) (3)
(dB(A))
35/40/48
40/47/56
36/52/58
50/60/63
50/60/63
Radiated sound power level (speeds 2 / 3 / 5) (3)
(dB(A))
29/34/42
31/37/46
32/46/51
40/50/53
40/50/53
NR Level (speeds 2 / 3 / 5) (4)
13/17/25
19/26/36
16/34/39
27/37/40
27/37/40
NC Level (speeds 2 / 3 / 5) (4)
10/15/24
17/25/34
14/32/37
25/35/38
25/35/38
Voltage range
Minimum voltage
(V)
2.3
2.6
3
3.5
3
Maximum voltage
(V)
5.8
7.6
9
7
7
Speed 1/5/6 -> speed low/medium/high
(1) At medium speed in compliance with Eurovent conditions
(2) EER Eurovent ratio and class definition (speed (low/medium/high)
(3) Levels according to Eurovent specification 8/2 (ISO 3741/88) and Eurovent FC Certification For 400/500/600 as per voltages declared to Eurovent.
(4) Values calculated from sound levels with hypothetical acoustic attenuation of 20dB
UNT-SVX10G-BAT1_Mise en page 1 7/26/2013 2:41 PM Page 10