Figure 7 - Hole locations
Table 5 - Drilling distances
(1) If the threaded rod diameter is smaller than 6 mm, use a washer.
Number of
suspension points
A
B
C
D
Ø hole
Ø threaded
rods (1)
Unit size
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
FCD 101-103
FED 100
3/4
478
463
585.4
338
15.1
6
FCD 203-204
FED 200
3/4
628
463
713.2
338
15.1
6
FCD 304-306
FED 300
3/4
858
463
922.2
338
15.1
6
FCD 406-408
FED 400
3/4
1008
463
1063.2
338
15.1
6
FCD 101-103
FED 100
3/4
478
579
713.2
338
15.1
6
FCD 203-204
FED 200
3/4
628
579
713.2
338
15.1
6
FCD 304-306
FED 300
3/4
858
579
922.2
338
15.1
6
FCD 406-408
FED 400
3/4
1008
579
1063.2
338
15.1
6
FCD 304-306 High
capacity
FED 300 High capacity
4
858
637
1068.5
15.1
6
FCD 406-408 High
capacity
FED 400 High capacity
4
1008
637
1192.5
15.1
6
FCD 508-512-FED 500
4
1158
637
1321.5
15.1
6
FCD 612-FED 600
4
1458
637
1591
15.1
6
FCD 721
4
1458
729
1630
15.1
6
C
D
B
A
Installation
15
UNT-SVX10G-E4
ø 160
250mm
ø 200
Without air duct
connection
With air duct
connection
With or without air
duct connection
Figure 8 - Clearance recommendations
E
(mm)
F
(mm)
G
(mm)
H
(mm)
FCD 101-103-203-204-304-306-406-408-508-512-612
FED 100-200-300-400-500-600
141
143
210
276
FCD 721
141
143
255
253
UNT-SVX10G-BAT1_Mise en page 1 7/26/2013 2:41 PM Page 15