Performance
Data
UNT-PRC001-EN
19
Two-Pipe
Coils
ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a
10 F (5.5 C) DT.
Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a
30 F (17 C) DT.
All performance measured on high speed tap, 115 V, zero ESP, with a throwaway filter. See page 18 for performance groupings.
Table PD-2. Free Discharge Motor, Two-Pipe, Group 1
Cooling
Heating
CFM
TMBH
SMBH
GPM
WPD
TMBH
GPM
WPD
115V
230V
277V
FC
Coil
(L/s)
(TkW)
(SkW)
(L/s)
(kPa)
(TkW)
Q/ITD
(L/s)
(kPa)
Watt
Watt
Watt
2
2CH
240 (113)
5.4 (1.6)
4.2 (1.2)
1.11 (.07)
6.8 (20.4)
15.9 (4.7)
0.14
1.06 (.07)
4.8 (14.4)
60
95
65
3CH
230 (108)
7.3 (2.1)
5.1 (1.5)
1.50 (.09)
17.4 (51.9)
19.6 (5.7)
0.18
1.31 (.08) 10.5 (31.4)
60
95
65
4CH
210 (99)
7.3 (2.1)
5.1 (1.5)
1.49 (.09)
4.2 (12.6)
20.1 (6.0)
0.18
1.34 (.08)
2.8 (8.4)
60
95
65
3
2CH
318 (150)
6.7 (2.0)
5.1 (1.5)
1.39 (.09)
11.3 (33.9)
21.0 (6.2)
0.19
1.40 (.09)
8.8 (26.3)
70
80
83
3CH
314 (148)
8.1 (2.4)
6.0 (1.8)
1.67 (.11)
4.4 (13.2)
25.6 (7.5)
0.23
1.70 (.11)
3.8 (11.3)
85
89
101
4CH
284 (134)
9.7 (2.8)
6.7 (2.0)
1.99 (.13)
7.7 (23.0)
27.1 (7.9)
0.25
1.81 (.11)
5.3 (15.7)
85
89
101
4
2CH
388 (183)
8.6 (2.5)
6.8 (2.0)
1.78 (.11)
4.1 (12.2)
25.6 (7.5)
0.23
1.71 (.11)
3.2 (9.5)
95
96
104
3CH
374 (177)
11.5 (3.4)
8.1 (2.4)
2.37 (.15)
9.5 (28.3)
31.8 (9.3)
0.29
2.12 (.13)
6.4 (19.0)
100
107
106
4CH
350 (165)
13.0 (3.8)
8.7 (2.5)
2.66 (.17)
14.8 (44.4)
34.2 (10.0)
0.31
2.28 (.14)
9.1 (27.3)
100
107
106
6
2CH
611 (289)
14.7 (4.3)
11.1 (3.3)
3.02 (.19)
12.9 (38.6)
40.6 (11.9)
0.37
2.70 (.17)
8.9 (26.5)
110
154
165
3CH
608 (287)
16.6 (4.9)
12.4 (3.6)
3.40 (.21)
4.9 (14.8)
49.7 (14.6)
0.45
3.31 (.21)
4.2 (12.6)
125
130
124
4CH
565 (267)
19.4 (5.7)
13.3 (3.9)
3.96 (.25)
7.8 (23.2)
53.8 (15.8)
0.49
3.59 (.23)
5.7 (17.0)
125
130
124
8
2CH
790 (373)
16.2 (4.7)
13.1 (3.9)
3.32 (.21)
4.2 (12.5)
50.9 (14.9)
0.46
3.39 (.21)
4.0 (11.9)
135
150
159
3CH
731 (345)
20.6 (6.1)
14.7 (4.3)
4.21 (.27)
8.2 (24.4)
61.6 (18.1)
0.56
4.11 (.26)
6.9 (20.7)
120
123
133
4CH
688 (325)
22.8 (6.7)
15.5 (4.5)
4.65 (.29)
11.7 (35.0)
66.8 (19.6)
0.61
4.45 (.28)
9.4 (28.1)
120
123
133
10
2CH
980 (463)
22.5 (6.6)
17.5 (5.1)
4.64 (.29)
8.6 (25.8)
64.8 (19.0)
0.59
4.32 (.27)
6.8 (20.4)
205
250
269
3CH
992 (468)
28.7 (8.4)
20.2 (5.9)
5.89 (.37)
17.0 (50.7)
83.3 (24.4)
0.76
5.55 (.35) 13.4 (40.2)
225
237
230
4CH
930 (439)
29.9 (8.8)
20.1 (5.9)
6.14 (.39)
22.1 (66.0)
90.1 (26.4)
0.82
6.00 (.38) 18.3 (54.8)
225
237
230
12
2CH
1110 (524)
27.0 (7.9)
20.2 (5.9)
5.55 (.35)
12.9 (38.6)
75.0 (22.0)
0.68
4.99 (.32)
9.6 (28.6)
230
246
263
3CH
1082 (511)
31.6 (9.3)
22.5 (6.6)
6.46 (.41)
12.4 (37.0)
91.5 (26.8)
0.83
6.10 (.38) 10.5 (31.4)
220
230
239
4CH
1010 (477)
37.0 (10.8)
24.3 (7.1)
7.55 (.48)
16.7 (49.8)
99.3 (29.1)
0.90
6.62 (.42) 11.8 (35.2)
220
230
239
Table PD-3. Free Discharge Motor, Two-Pipe, Group 2
Cooling
Heating
CFM
TMBH
SMBH
GPM
WPD
TMBH
GPM
WPD
115V
230V
277V
FC
Coil
(L/s)
(TkW)
(SkW)
(L/s)
(kPa)
(TkW)
Q/ITD
(L/s)
(kPa)
Watt
Watt
Watt
2
2CH
211 (100)
5.0 (1.5)
3.8 (1.1)
1.04 (.07)
6.1 (18.2)
14.5 (4.3)
0.13
0.97 (.06)
4.1 (12.3)
60
95
65
3CH
201 (95)
6.8 (2.0)
4.7 (1.4)
1.40 (.09)
15.4 (46.0)
17.7 (5.2)
0.16
1.18 (.07)
8.8 (26.2)
60
95
65
4CH
188 (89)
6.8 (2.0)
4.7 (1.4)
1.40 (.09)
3.7 (11.1)
18.3 (5.4)
0.17
1.22 (.08)
2.4 (7.1)
60
95
65
3
2CH
280 (132)
6.4 (1.9)
4.8 (1.4)
1.32 (.08)
10.3 (30.7)
19.2 (5.6)
0.17
1.28 (.08)
7.5 (22.4)
70
80
83
3CH
277 (131)
7.6 (2.2)
5.6 (1.7)
1.57 (.10)
4.0 (11.8)
23.3 (6.8)
0.21
1.55 (.10)
3.2 (9.5)
85
89
101
4CH
256 (121)
9.1 (2.7)
6.3 (1.8)
1.88 (.12)
7.0 (20.8)
24.8 (7.3)
0.23
1.65 (.10)
4.5 (13.4)
85
89
101
4
2CH
349 (165)
8.1 (2.4)
6.4 (1.9)
1.68 (.11)
3.7 (11.0)
23.8 (7.0)
0.22
1.58 (.10)
2.8 (8.3)
95
96
104
3CH
338 (159)
10.9 (3.2)
7.7 (2.3)
2.25 (.14)
8.6 (25.8)
29.4 (8.6)
0.27
1.96 (.12)
5.5 (16.5)
100
107
106
4CH
320 (151)
12.4 (3.6)
8.2 (2.4)
2.54 (.16)
13.6 (40.7)
31.7 (9.3)
0.29
2.11 (.13)
7.9 (23.7)
100
107
106
6
2CH
544 (257)
13.9 (4.1)
10.4 (3.1)
2.86 (.18)
11.7 (34.9)
37.4 (11.0)
0.34
2.49 (.16)
7.6 (22.8)
110
154
165
3CH
541 (255)
15.5 (4.6)
11.6 (3.4)
3.19 (.20)
4.4 (13.1)
45.4 (13.3)
0.41
3.03 (.19)
3.6 (10.6)
125
130
124
4CH
510 (241)
18.3 (5.4)
12.5 (3.7)
3.74 (.24)
7.0 (20.9)
49.4 (14.5)
0.45
3.29 (.21)
4.8 (14.5)
125
130
124
8
2CH
706 (331)
15.3 (4.5)
12.3 (3.6)
3.14 (.20)
3.8 (11.3)
47.0 (13.8)
0.43
3.13 (.20)
3.4 (10.2)
135
150
159
3CH
659 (311)
19.7 (5.8)
14.0 (4.1)
4.01 (.25)
7.5 (22.3)
56.8 (16.8)
0.52
3.79 (.24)
5.9 (17.8)
120
123
133
4CH
627 (296)
21.8 (6.4)
14.7 (4.3)
4.44 (.28)
10.8 (32.2)
61.8 (18.1)
0.56
4.12 (.26)
8.1 (24.3)
120
123
133
10
2CH
879 (415)
21.2 (6.2)
16.3 (4.8)
4.39 (.28)
7.8 (23.2)
60.0 (17.6)
0.55
4.00 (.25)
5.9 (17.7)
205
250
269
3CH
886 (418)
27.2 (8.0)
19.0 (5.6)
5.60 (.35)
15.4 (46.1)
76.4 (22.4)
0.69
5.09 (.32) 11.4 (34.1)
225
237
230
4CH
840 (397)
28.6 (8.4)
19.1 (5.6)
5.88 (.37)
20.4 (61.0)
82.8 (24.3)
0.75
5.52 (.35) 15.7 (46.8)
225
237
230
12
2CH
996 (470)
25.6 (7.5)
19.0 (5.6)
5.28 (.33)
11.8 (35.1)
69.4 (20.3)
0.63
4.62 (.29)
8.3 (24.7)
230
246
263
3CH
976 (461)
30.0 (8.8)
21.3 (6.2)
6.14 (.39)
11.2 (33.6)
84.3 (24.8)
0.77
5.62 (.35)
9.0 (26.8)
220
230
239
4CH
921 (435)
35.4 (10.4)
23.2 (6.8)
7.23 (.46)
15.4 (46.0)
91.8 (26.9)
0.83
6.12 (.39) 10.2 (30.5)
220
230
239
Note:
1. CFM = Cubic feet per minute
2. TMBH = Total capacity (MBH)
3. GPM = Gallons per minute
4. WPD = Water pressure drop (feet of water)
5. Q/ITD = MBH (kW)/(Entering water temperature - Entering air temperature) when
∆
T and GPM (L/s) remain constant. To determine heating capacities at a different entering water
temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
6. Medium and low speed capacities are approximately 80 percent and 60 percent respectively of the high speed capacity.
Summary of Contents for UniTrane Fan-Coil
Page 16: ...General Data UNT PRC001 EN 16 Piping Packages Automatic Circuit Setter C ...
Page 77: ......
Page 78: ......
Page 79: ......