Two-Pipe
Coils
ARI cooling performance is based on 80/67 F (27/19 C) entering air temperature, 45 F (7 C) entering chilled water temperature with a
10 F (5.5 C) DT.
Heating performance is based on 70 F (21 C) entering air temperature, 180 F (82 C) entering hot water temperature with a
30 F (17 C) DT.
All performance measured on high speed tap, 115 V, 0.2” (0.05 kPA) ESP, with a throwaway filter. See page 18 for performance
groupings.
Table PD-6. High Static Motor, Two-Pipe, Group 1
Cooling
Heating
CFM
TMBH
SMBH
GPM
WPD
TMBH
GPM
WPD
115V
230V
277V
FC
Coil
(L/s)
(TkW)
(SkW)
(L/s)
(kPa)
(TkW)
Q/ITD
(L/s)
(kPa)
Watt
Watt
Watt
2
2CH
287 (135)
5.9 (1.7)
4.7(1.4)
1.29 (0.08)
8.8 (26.3)
17.9 (5.3)
.16
1.19 (0.08)
6.0 (17.8)
145
145
145
3CH
282 (133)
8.5 (2.5)
6.1 (1.8)
1.80 (0.11)
23.9 (71.3)
22.9 (6.7)
.21
1.52 (0.10)
13.8 (41.2)
145
145
145
4CH
260 (123)
8.7 (2.6)
6.2 (1.8)
1.84 (0.12)
6.1 (18.3)
23.9 (7.0)
.22
1.59 (0.10)
3.8 (11.5)
145
145
145
3
2CH
365 (172)
7.4 (2.2)
5.7 (1.7)
1.58 (0.10)
14.1 (42.2)
23.0 (6.7)
.21
1.53 (0.10)
10.3 (30.8)
140
140
140
3CH
343 (162)
8.8 (2.6)
6.7 (2.0)
1.86 (0.12)
5.4 (16.1)
27.3 (8.0)
.25
1.82 (0.11)
4.3 (12.8)
145
140
135
4CH
318 (150)
10.8 (3.2)
7.6 (2.2)
2.26 (0.14)
9.7 (28.9)
29.7 (8.7)
.27
1.98 (0.12)
6.2 (18.6)
145
140
135
4
2CH
396 (187)
8.9 (2.6)
7.1 (2.1)
1.90 (0.12)
4.6 (13.7)
26.0 (7.6)
.24
1.73 (0.11)
3.3 (9.8)
170
180
170
3CH
484 (228)
14.0 (4.1)
10.2 (3.0)
2.94 (0.19)
13.9 (41.5)
38.6 (11.3)
.35
2.57 (0.16)
9.1 (27.0)
210
210
210
4CH
453 (214)
16.0 (4.7)
11.0 (3.2)
3.35 (0.21)
22.3 (66.7)
42.2 (12.4)
.38
2.81 (0.18)
13.4 (39.9)
210
210
210
6
2CH
668 (315)
15.8 (4.6)
12.1 (3.5)
3.32 (0.21)
15.3 (45.6)
43.1 (12.6)
.39
2.87 (0.18)
9.9 (29.5)
245
240
240
3CH
780 (368)
20.1 (5.9)
15.5 (4.5)
4.24 (0.27)
7.5 (22.3)
59.5 (17.4)
.54
3.96 (0.25)
5.9 (17.7)
320
320
320
4CH
725 (342)
23.9 (7.0)
16.8 (4.9)
4.99 (0.31)
11.9 (35.6)
65.6 (19.2)
.60
4.37 (0.28)
8.2 (24.6)
320
320
320
8
2CH
907 (428)
18.4 (5.4)
15.2 (4.5)
3.90 (0.25)
5.7 (16.9)
55.7 (16.3)
.51
3.71 (0.23)
4.7 (14.2)
320
320
320
3CH
886 (418)
24.6 (7.2)
17.9 (5.3)
5.13 (0.32)
11.8 (35.2)
71.2 (20.9)
.65
4.74 (0.30)
9.1 (27.1)
320
320
320
4CH
835 (394)
27.3 (8.0)
18.9 (5.5)
5.68 (0.36)
16.9 (50.6)
78.3 (22.9)
.71
5.22 (0.33)
12.7 (37.8)
320
320
320
10
2CH
1117 (527)
24.7 (7.3)
19.5 (5.7)
5.23 (0.33)
10.8 (32.2)
70.8 (20.7)
.65
4.71 (0.30)
8.1 (24.1)
415
420
410
3CH
1230 (580)
33.9 (9.9)
24.5 (7.2)
7.14 (0.45)
24.2 (72.3)
97.6 (28.6)
.89
6.50 (0.41)
18.1 (54.0)
530
530
530
4CH
1152 (544)
36.2(10.6)
24.8 (7.3)
7.63 (0.48)
32.8 (98.1)
107.1 (31.4)
.97
7.13 (0.45)
25.3 (75.6)
530
530
530
12
2CH
1270 (600)
30.1 (8.8)
23.0 (6.8)
6.35 (0.40)
16.6 (49.5)
82.2 (24.1)
.75
5.48 (0.35)
11.4 (34.0)
490
500
490
3CH
1350 (637)
38.1 (11.2)
27.9 (8.2)
7.98 (0.50)
18.5 (55.3)
108.0 (31.6)
.98
7.19 (0.45)
14.5 ( 43.2)
530
530
530
4CH
1274 (601)
45.6 (13.4)
30.6 (9.0)
9.47 (0.60)
25.2 (75.4)
120.0 (35.2)
1.09
8.00 (0.50)
16.7 (50.0)
530
530
530
Table PD-7. High Static Motor, Two-Pipe, Group 2
Cooling
Heating
CFM
TMBH
SMBH
GPM
WPD
TMBH
GPM
WPD
115V
230V
277V
FC
Coil
(L/s)
(TkW)
(SkW)
(L/s)
(kPa)
(TkW)
Q/ITD
(L/s)
(kPa)
Watt
Watt
Watt
2
2CH
256 (121)
5.6 (1.6)
4.4 (1.3)
1.22 (0.08)
8.0 (23.9)
16.6 (4.9)
.15
1.11 (0.07)
5.2 (15.5)
145
145
145
3CH
250 (118)
8.0 (2.3)
5.7 (1.7)
1.69 (0.11)
21.5 (64.1)
20.9 (6.1)
.19
1.39 (0.09)
11.8 (35.3)
145
145
145
4CH
234 (111)
8.2 (2.4)
5.8 (1.7)
1.74 (0.11)
5.5 (16.4)
22.0 (6.5)
.20
1.47 (0.09)
3.3 (9.9)
145
145
145
3
2CH
330 (156)
7.1 (2.1)
5.4 (1.6)
1.51 (0.10)
13.1 (39.0)
21.5 (6.3)
.20
1.43 (0.09)
9.2 (27.4)
140
140
140
3CH
309 (146)
8.3 (2.4)
6.3 (1.9)
1.76 (0.11)
4.9 (14.6)
25.3 (7.4)
.23
1.68 (0.11)
3.7 (11.1)
145
140
135
4CH
290 (137)
10.3 (3.0)
7.1 (2.1)
2.15 (0.14)
8.8 (26.4)
27.6 (8.1)
.25
1.84 (0.12)
5.4 (16.3)
145
140
135
4
2CH
367 (173)
8.5 (2.5)
6.8 (2.0)
1.82 (0.11)
4.3 (12.7)
24.6 (7.2)
.22
1.64 (0.10)
3.0 (8.9)
170
180
170
3CH
440 (208)
13.3 (3.9)
9.6 (2.8)
2.80 (0.18)
12.8 (38.1)
36.0 (10.5)
.33
2.40 (0.15)
8.0 (23.8)
210
210
210
4CH
416 (196)
15.3 (4.5)
10.4 (3.1)
3.20 (0.20)
20.6 (61.6)
39.5 (11.6)
.36
2.63 (0.17)
11.8 (35.3)
210
210
210
6
2CH
610 (288)
15.0 (4.4)
11.4 (3.4)
3.17 (0.20)
14.1 (42.1)
40.5 (11.9)
.37
2.70 (0.17)
8.8 (26.4)
245
240
240
3CH
704 (332)
19.0 (5.6)
14.5 (4.2)
4.02 (0.25)
6.8 (20.2)
55.3 (16.2)
.50
3.68 (0.23)
5.2 (15.4)
320
320
320
4CH
662 (312)
22.7 (6.6)
15.9 (4.7)
4.75 (0.30)
10.9 (32.5)
61.1 (17.9)
.56
4.07 (0.26)
7.2 (21.5)
320
320
320
8
2CH
834 (394)
17.6 (5.2)
14.5 (4.2)
3.74 (0.24)
5.3 (15.7)
52.7 (15.5)
.48
3.51 (0.22)
4.3 (12.7)
320
320
320
3CH
815 (385)
23.6 (6.9)
17.1 (5.0)
4.94 (0.31)
10.9 (32.7)
66.9 (19.6)
.61
4.46 (0.28)
8.1 (24.1)
320
320
320
4CH
775 (366)
26.2 (7.7)
18.1 (5.3)
5.47 (0.34)
15.8 (47.1)
73.7 (21.6)
.67
4.91 (0.31)
11.3 (33.8)
320
320
320
10
2CH
1029 (486)
23.7 (6.9)
18.5 (5.4)
5.02 (0.32)
10.0 (29.8)
67.0 (19.6)
.61
4.46 (0.28)
7.3 (21.8)
415
420
410
3CH
1117 (527)
32.3 (9.5)
23.2 (6.8)
6.83 (0.43)
22.3 (66.6)
91.0 (26.7)
.83
6.06 (0.38)
15.9 (47.4)
530
530
530
4CH
1057 (499)
34.9 (10.2)
23.7 (7.0)
7.34 (0.46)
30.6 (91.4)
100.0 (29.3)
.91
6.66 (0.42)
22.3 (66.6)
530
530
530
12
2CH
1175 (554)
28.9 (8.5)
22.0 (6.4)
6.12 (0.39)
15.5 (46.2)
78.0 (22.8)
.71
5.19 (0.33)
10.3 (30.8)
490
500
490
3CH
1242 (586)
36.5 (10.7)
26.5 (7.8)
7.66 (0.48)
17.1 (51.2)
101.5 (29.8)
.92
6.77 (0.43)
12.8 (38.4)
530
530
530
4CH
1181 (557)
43.8 (12.8)
29.3 (8.6)
9.12 (0.58)
23.5 (70.3)
113.0 (33.1)
1.03
7.53 (0.47)
14.9 (44.6)
530
530
530
Note:
1. CFM = Cubic feet per minute
2. TMBH = Total capacity (MBH)
3. GPM = Gallons per minute
4. WPD = Water pressure drop (feet of water)
5. Q/ITD = MBH (kW)/(Entering water temperature - Entering air temperature) when
∆
T and GPM (L/s) remain constant. To determine heating capacities at a different entering water
temperature or entering air temp, compute the new ITD and multiply it by the Q/ITD shown.
6. Medium and low speed capacities are approximately 80 percent and 60 percent respectively of the high speed capacity.
7. High static motors need the appropriate length of duct to prevent poor acoustical applications.
Summary of Contents for UniTrane Fan-Coil
Page 16: ...General Data UNT PRC001 EN 16 Piping Packages Automatic Circuit Setter C ...
Page 77: ......
Page 78: ......
Page 79: ......