   MS-SVX10A-EN

  25

Installation Indoor Unit

Extra Part 3
Extra Part 2
Extra Part 1

Fitting
pipe for
gas side

Power
connection
cord

Fitting pipe
for liquid
side

Drain
pipe

Heat
Insulation

Wrapping
tape

Figure 9

Installing Indoor Unit

Fitting pipe can come four directions, that is, right,
rear right, left and rear left.

1.  When laying the pipe line on either the left or right

side, cut out extra part as needed to accommodate
piping at the tube exit plate on the base of the unit.
See Figure 9.

         (1) When only drawing out the power line, cut
               Extra Part 1.
         (2) When drawing out the connecting pipe
               and the electric line, cut Extra Parts 1 and
               2 (or 1, 2, 3).

2.  Pull out the fitting pipe from bottom case. Use

adhesive tape to bind the fitting pipe, electric
cable and drain hose and then pass them
through the fitting pipe hole.  See Figure 10.

3.  Hang the brackets at the rear side of the indoor

unit to the hooks on the wall-mounting frame.
Shift the unit left and right to verify that it is
steady. See Figure 11.

4. The installation height of the indoor unit must be

at least 2.0 m.

Figure 10

Left

Left Rear

Right Rear

Right

Figure 11

Support
Hook

Mounting
Plate

Mounting
Plate

Summary of Contents for TXK

Page 1: ...MS SVX10A EN Installation Operation Maintenance MXW TXK R410A Split System Wall Unit Heat Pump Up To 16 9 SEER 9 000 18 000 Btu Hr MXWA09 TXKA09 MXWA12 TXKA12 MXWA18 TXKA18...

Page 2: ...2007 American Standard Inc...

Page 3: ...perating Instructions 10 System Description 11 Remote Control Description 12 Care and Maintenance 15 Troubleshooting 17 Installation Installation Recommendations 20 Installation Location 22 Installati...

Page 4: ...70 higher pressures than R 22 Use only R 410A approved service equipment Refrigerant cylinders are painted a rose color to indicate the type of refrigerant and may contain a dip tube to allow for char...

Page 5: ...MS SVX10A EN 5 Safety Precautions...

Page 6: ...MS SVX10A EN 6 Safety Precautions...

Page 7: ...MS SVX10A EN 7 Safety Precautions...

Page 8: ...MS SVX10A EN 8 Specifications and Technical Data...

Page 9: ...MS SVX10A EN 9 Specifications and Technical Data...

Page 10: ...effect in the room When this occurs the defrost cycle is automati cally activated temporarily halting the heating mode function for a period of 8 to 10 minutes Both the indoor fan and outdoor fan wil...

Page 11: ...MS SVX10A EN 11 System Description...

Page 12: ...HEAT modes press this button to select the Fan Speed Auto Low Medium or High In the DRY mode the fan speed is Low The FAN SPEED setting can be saved in the system s memoriy under various modes MODE Bu...

Page 13: ...tton once to cancel all TIMER settings T OFF Button Press this button once to set the function The OFF icon on the screen will flash This function is available in both ON or OFF modes For setting refe...

Page 14: ...peration If the wireless remote control is lost or broken use the manual switch inside de unit This will place the system in the AUTO mode thus settings for fan speed and temperature cannot be changed...

Page 15: ...MS SVX10A EN 15 Care and Maintenance...

Page 16: ...MS SVX10A EN 16 Care and Maintenance...

Page 17: ...MS SVX10A EN 17 Troubleshooting...

Page 18: ...MS SVX10A EN 18 Troubleshooting...

Page 19: ...MS SVX10A EN 19 Troubleshooting...

Page 20: ...MS SVX10A EN 20 Installation Recommendations...

Page 21: ...MS SVX10A EN 21 Installation Recommendations...

Page 22: ...MS SVX10A EN 22 Installation Location...

Page 23: ...rt the weight of an adult 60 kg and the fixing screws should bear stress evenly Wall Opening and Wall Pipe 1 After deciding the position of the hole for the fitting pipe according to Figure 6 drill a...

Page 24: ...ws in place to clamp de connecting cable 6 Install the front panel back into position Figure 8 Terminal Board Ground Power Cable Cable Groove Notes If the connecting power cable is not long enough con...

Page 25: ...e Figure 9 1 When only drawing out the power line cut Extra Part 1 2 When drawing out the connecting pipe and the electric line cut Extra Parts 1 and 2 or 1 2 3 2 Pull out the fitting pipe from bottom...

Page 26: ...e cables in place The line sequence must be consistent with the outdoor unit 3 Replace the cable clamp to secure the power cable in place 4 Confirm that lines are secure 5 Replace the panel with the s...

Page 27: ...serve the micron gauge If gauge pressure rises above 500 microns in one 1 minute then evacuation is incomplete or system has a leak 6 If vacuum gauge does not rise above 500 microns in one 1 minute th...

Page 28: ...unit and the water generated by defrosting will be drained through the drain pipe to the outside Installation method As shown in the right hand figure insert the drain joint of the oudoor unit into t...

Page 29: ...MS SVX10A EN 29 Testing and Operating Verification...

Page 30: ...A business of American Standard Company www trane com Literature Order Number MS SVX10A EN File Date April 2007 Supersedes New Stocking Location Electronic Since Trane has a policy of continuous prod...

Reviews: