background image

6

18-GE01D1-9

Installer’s Guide

NOTE:

Torque specification for TXV equals 1/6 turn past finger

tight.

3. Run refrigerant tubing into the stub sockets of in-

door unit coil.

4. Braze and evacuate according to indoor and outdoor

installation instructions.

PAINTED AREAS OF UNIT MUST BE SHIELDED DUR-
ING BRAZING

WARNING

!

TO PREVENT INJURY OR DEATH DUE TO ELECTRICAL 
SHOCK OR CONTACT WITH MOVING PARTS, LOCK 
UNIT DISCONNECT SWITCH IN OPEN POSITION 
BEFORE SERVICING UNIT.

F. CONDENSATE DRAIN PIPING

NOTE:
Make certain that the unit has been installed in a level
position to ensure proper draining.

3/4" NPT Secondary
drain connection

3/4" NPT Primary
drain connection

Figure 6

Field fabricated trap

2" MINIMUM 

2" MINIMUM 

Manufactured traps

EZT-105

2" MIN.

2" MIN.

CAP OR PLUG

Trap must be within 4' 
of air handler condensate
drain connection.

Close as possible

Figure 7

Figure 8

The indoor blower is downstream of the evaporator coil
which creates a negative pressure at the condensate
drain connections during operation. The condensate
drain connections in front of the indoor coil are 3/4"
NPT. The lower connection is the primary drain. See
Figure 6.

Two secondary drain connections are provided for the
different orientations (See Figure 6). The lower of the
two should be connected as a backup to prevent conden-
sate overflow by a blocked primary drain.

For proper drainage of condensate, the following steps
should be followed:

1. The primary drain line must be trapped with a

minimum of 2" water seal as shown in Figures 7 & 8.
Do not use preformed 3/4" PVC running traps.

The use of Field fabricated or manufactured traps
as shown in Figures 7 & 8

 

 is acceptable. The

manufactured trap shown in Figure 7 allows for a
float switch option to be added.
Refer to the manufacturers data and instructions
for details.

2. The trap must be located within 4 feet of the air

handler drain outlet connection.

3. It  is recommended that a clean-out tee or cross be

installed in the primary drain line for future mainte-
nance  (See Figure 7 & 8).

4. Do not use reducing fittings in the condensate drain

lines.

5. Slope the drain lines downward a minimum of 1/4"

per foot.

6. Insulate the primary drain to prevent sweating.

7. Provide means for drainage to prevent winter

freeze-up of condensate line.

8. Do not connect the drain line to a closed drain system.

9. Use Teflon

®

 tape on the air handler drain line

connections! Do Not Use pipe joint compound or
PVC/CPVC cement!

Summary of Contents for TWE031E13FB1

Page 1: ...on and are fully con vertible to downflow or horizontal left Refer to Section B beginning on page 3 for additional information INSPECTION Check carefully for any shipping damage This must be re ported...

Page 2: ...r or by oth ers then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing a fossil fuel device be installed and...

Page 3: ...ee Figure 3 c Position unit on Pedestal or other suitable foun dation If Pedestal is not used a frame strong enough to support the total weight must be pro vided Provide a minimum height of 14 inches...

Page 4: ...shown in the outline drawing HORIZONTAL LEFT a For maximum efficiency and Customer ease of filter maintenance it is recommended that a prop erly sized remote filter and grille be installed for horizo...

Page 5: ...ush fit for 3 4 or 1 1 2 duct board applications see the Outline drawing on page 10 for sizes of the duct connections After the duct is secured seal around the supply duct to prevent air leakage NOTE...

Page 6: ...imary drain See Figure 6 Two secondary drain connections are provided for the different orientations See Figure 6 The lower of the two should be connected as a backup to prevent conden sate overflow b...

Page 7: ...SWITCHES AS SHIPPED COOLING HEATING AIRFLOW FAN OFF DELAY AUXILIARY HEAT SPEEDS 0 OFF OFF 50 80 100 if necessary 50 Dehumidify Fast Coil Cooling and Heating Efficiency 7 5 minutes 3 minutes 1 minute...

Page 8: ...8 18 GE01D1 9 Installer s Guide TWE E AIR HANDLERS WITH SINGLE STAGE COOLING 2 STAGE HEAT TWE E AIR HANDLERS WITH TWO STAGE COOLING 2 STAGE HEAT From Dwg No B801074...

Page 9: ...the unit 3 Field wiring diagrams are provided which show the low voltage wiring hookup for a single speed cooling only system with supplementary heaters and a heat pump system with supplementary heat...

Page 10: ...STIBLE MATERIAL REQUIRED SERVICE CLEARANCE RECOMMENDED SIDES 0 2 FRONT 0 21 BACK 0 0 INLET DUCT 0 1 OUTLET DUCT 1 1 FOR THE FIRST 3 FT OF OUTLET DUCT WHEN ELECTRIC HEATERS ARE INSTALLED EXCEPT MODELS...

Page 11: ...0 21 00 1 50 CAGE NUT MOUNTING LOCATION FOR TWE AIR HANDLERS FOR TWO PIECE CABINET ONLY Model No H W A B TWE031E13 43 00 21 50 17 00 39 00 TWE037E13 45 00 23 50 19 00 41 00 TWE040E13 51 75 26 00 23 80...

Page 12: ...e that grounding of unit is in accord with code 3 Make sure unit suspension if used is secure and that there are no tools or loose debris in around or on top of the unit 4 Check all duct outlets they...

Reviews: