background image

18-GE01D1-9

5

Installer’s Guide

face velocity of the filter being used. The factory
installed filter should then be removed
from the unit.

b. Unit is shipped from the factory in the upflow or

horizontal right configuration. Unit conversion is
not required.

c. The unit is designed for suspension using 1/4" -

20 threaded rods. Other means of suspension are
allowed as long as the unit is supported from
both ends as well as the middle to prevent sag-
ging and service access is not obstructed.

d. If the unit is not suspended it must be isolated

carefully to prevent sound transmission. Vibra-
tion isolators (purchased locally) must be placed
under the unit.

e. It is always recommended that an auxiliary drain

pan be installed under a horizontal air handler
(See Condensate Drain Piping) to prevent possible
damage to ceilings.

f. Isolate the auxiliary drain pan from the unit or

from the structure.

g. Connect the auxiliary drain line to a separate

drain line (no trap is needed in this line) and ter-
minate according to local codes.

h. If a return duct is connected to the Air Handler,

it must be the same dimensions as the return
opening shown in the outline drawings.

i.  Openings where field wiring enters the cabi-

net must be completely sealed.  Location of
power entry is shown on the outline drawing.
Use 2.5" clear stickers to seal all unused electrical
knockouts and cage nut openings.

C. DUCT CONNECTIONS

The supply and return air ducts should be connected to
the unit with flame retardant duct connectors.

Convertible duct flanges are provided on the discharge
opening to provide a “flush fit” for 3/4" or 1-1/2" duct board
applications, see the Outline drawing on page 10 for sizes
of the duct connections. After the duct is secured, seal
around the supply duct to prevent air leakage.

NOTE:
If the convertible duct flanges are not used, they must be
removed and discarded for proper airflow.

D. REFRIGERANT PIPING

IMPORTANT:
Refrigerant piping must be routed to maintain service access
to blower compartment and provide easy removal of filter
access panel and filter.

NOTE:

Refrigerant piping must be sealed along with field wiring.

1. Refrigerant connections are made outside the cabi-

net.

NOTE:
TXV bulb MUST be protected (wrap a wet rag around the
suction line between the TXV bulb and the braze joint) or
removed, while brazing the tubing. Overheating of the
sensing bulb will affect the functional characteristics and
performance of the air handler.

NOTE:
The Referigerant lines must be sealed and Electrical
inlets need to be sealed at both the low and the high
voltage.

  2. Installation of refrigerant lines is covered in the in-
stallation instructions packaged with the outdoor unit.
Evacuation, leak testing and brazing procedures are in-
cluded in those instructions. Read those instructions be-
fore starting installation of refrigerant lines.

E. BRAZING TO EVAPORATOR SECTION

NOTE:
A brazing shield is provided in the information pack accom-
panying this unit. This shield fits over the refrigerant fittings
while brazing. Wet the shield before brazing. See Fig. 5.

IMPORTANT:

Do not unseal refrigerant tubing until ready to cut and fit
refrigerant lines.

1. Remove both sealing caps from indoor coil.

2. Field supplied tubing should be cut square, round

and free of burrs at the connecting end. Clean the
tubing to prevent contaminants from entering the
system.

BRAZE SHIELD

5

Summary of Contents for TWE031E13FB1

Page 1: ...on and are fully con vertible to downflow or horizontal left Refer to Section B beginning on page 3 for additional information INSPECTION Check carefully for any shipping damage This must be re ported...

Page 2: ...r or by oth ers then installation of the air handler must be made to allow access for refrigerant lines or attach refrigerant lines to air handler when installing a fossil fuel device be installed and...

Page 3: ...ee Figure 3 c Position unit on Pedestal or other suitable foun dation If Pedestal is not used a frame strong enough to support the total weight must be pro vided Provide a minimum height of 14 inches...

Page 4: ...shown in the outline drawing HORIZONTAL LEFT a For maximum efficiency and Customer ease of filter maintenance it is recommended that a prop erly sized remote filter and grille be installed for horizo...

Page 5: ...ush fit for 3 4 or 1 1 2 duct board applications see the Outline drawing on page 10 for sizes of the duct connections After the duct is secured seal around the supply duct to prevent air leakage NOTE...

Page 6: ...imary drain See Figure 6 Two secondary drain connections are provided for the different orientations See Figure 6 The lower of the two should be connected as a backup to prevent conden sate overflow b...

Page 7: ...SWITCHES AS SHIPPED COOLING HEATING AIRFLOW FAN OFF DELAY AUXILIARY HEAT SPEEDS 0 OFF OFF 50 80 100 if necessary 50 Dehumidify Fast Coil Cooling and Heating Efficiency 7 5 minutes 3 minutes 1 minute...

Page 8: ...8 18 GE01D1 9 Installer s Guide TWE E AIR HANDLERS WITH SINGLE STAGE COOLING 2 STAGE HEAT TWE E AIR HANDLERS WITH TWO STAGE COOLING 2 STAGE HEAT From Dwg No B801074...

Page 9: ...the unit 3 Field wiring diagrams are provided which show the low voltage wiring hookup for a single speed cooling only system with supplementary heaters and a heat pump system with supplementary heat...

Page 10: ...STIBLE MATERIAL REQUIRED SERVICE CLEARANCE RECOMMENDED SIDES 0 2 FRONT 0 21 BACK 0 0 INLET DUCT 0 1 OUTLET DUCT 1 1 FOR THE FIRST 3 FT OF OUTLET DUCT WHEN ELECTRIC HEATERS ARE INSTALLED EXCEPT MODELS...

Page 11: ...0 21 00 1 50 CAGE NUT MOUNTING LOCATION FOR TWE AIR HANDLERS FOR TWO PIECE CABINET ONLY Model No H W A B TWE031E13 43 00 21 50 17 00 39 00 TWE037E13 45 00 23 50 19 00 41 00 TWE040E13 51 75 26 00 23 80...

Page 12: ...e that grounding of unit is in accord with code 3 Make sure unit suspension if used is secure and that there are no tools or loose debris in around or on top of the unit 4 Check all duct outlets they...

Reviews: