BAS-SVP18D-EN

31

Table 10.

All object types sorted by object name (continued)

Object Type

Object Name

Min / Max

When the Point Exists

Description

AV81

Outdoor Air Humidity
BAS

0 - 100%

All Units.

Communicated outdoor air
relative humidity.

AV71

Outdoor Air Minimum
Flow Setpoint

350 -

13500

cfm

Units that are VAV, have
Outdoor Air Flow
Monitoring, and
Modulating Dampers.

Setpoint to modulate the
dampers.

AV72

Outdoor Air Minimum
Flow Setpoint Active

350 -

13500

cfm

Units that are VAV, have
Outdoor Air Flow
Monitoring, and
Modulating Dampers.

Actively used setpoint to
modulate the dampers.

AV13

Outdoor Air Minimum
Flow Setpoint BAS

0 - 13500

cfm

VAV Units with Outdoor air
flow Monitoring and
Modulating Dampers.

air flow setpoint used to
modulate dampers.

AI22

Outdoor Air Relative
Humidity Local

0 - 100%

All Units.

Local outside air humidity
sensor.

AV76

Outdoor Air Temperature
Active

-100 to

200 °F

All Units.

Actively used outdoor air
temperature.

AV75

Outdoor Air Temperature
BAS

-100 to

200 °F

All Units.

Communicated outdoor air
temperature.

AI21

Outdoor Air Temperature
Local

-50 to 135

°F

All Units.

Local outside air temperature
sensor.

AO4

PEVFD Command

0 – 100%

Units with Powered
Exhaust.

Analog exhaust fan VFD speed.

AV40

PEVFD Setpoint

0 - 100%

OAD, OAK, or OAN that
does NOT have
Modulating Dampers or
Powered Exhaust.

Fan speed setpoint used to
control the indoor fan speed.

BO10

Powered Exhaust Enable

Units with Isolation
Dampers or has Dual Point
Power.

• 0 = Off
• 1 = On

BO13

Pre-Heat Enable

Units with Pre-Heat.

• 0 = Off
• 1 = On

AV58

Pre-Heat Enable
Temperature

-10 to 35 °F

Units with an ERV and an
Electric Pre-Heater.

Below this temperature pre-
heat will be enabled.

BV33

Pre-Purge Status

Units with Gas as the
Primary Heat.

• 0 = Disabled
• 1 = Enabled

MV13

Program Control Type

All Units.

• 1 = Space Control
• 2 = Discharge Control
• 3 = Single Zone VAV
• 4 = Multi Zone VAV

BV18

Return Air Damper
Option

All Units.

• 0 = Not Installed
• 1 = Installed

AI14

Return Air Humidity Local

0 - 100%

Units with Modulating
Dampers.

Local return air humidity
sensor.

AI6

Return Air Temperature
Local

-25 to 135

°F

Units with Modulating
Dampers.

Local return air temperature
sensor.

AI12

Return Duct/Space
Pressure Local

0 - 2 in(H

2

O)

Units with Powered
Exhaust and Modulating
Dampers.

Local return duct or space
pressure sensor

AV56

Return Duct/Space
Pressure Setpoint

0 - 2 in(H

2

O)

Units with Modulating
Dampers and Exhaust
Fan(s).

Setpoint used to modulate
exhaust fan speed.

AV50

Space CO2
Concentration Setpoint

0 – 3000

ppm

All Units.

Space CO2 concentration
setpoint.

AV35

Space Dewpoint Active

-58 to 482

°F

All Units.

Actively used space dewpoint.

AV34

Space Dewpoint Setpoint
(SPDS)

-10 – 150

°F

Units with Space Control,
Discharge Control, or
Single Zone VAV.

If the outdoor air dewpoint is
greater than OADS, the unit
will enable dehumidification.

AI16

Space Occupancy
Request Override

-58 to 482

Units with Thumbwheel
Installed.

Local input that overrides
Occupancy Request.

AI2

Space Relative Humidity
Local

0 – 100%

Units with Space Humidity
Sensor Installed

Local space relative humidity
sensor.

AV7

Space RH Active

-150 to

150%

Units with Space Humidity
Sensor Installed.

Actively used space relative
humidity.

AV8

Space RH BAS

-150 to

150%

All Units.

Communicated space relative
humidity.

BV20

Space Temp/Humidity
Sensor Installed

Units that are Space
Control or Single Zone
VAV.

• 0 = Not Installed
• 1 = Installed

AV23

Space Temperature
Active

-58 to 482

°F

All Units.

Actively used space
temperature.

AV20

Space Temperature BAS

-58 to 482

°F

All Units.

Communicated space
temperature.

AI1

Space Temperature Local

-25 to 135 °F

Units with Space
Temperature Sensor
Installed

Local space temperature
sensor.

O

Ob

bjje

ecctt a

an

nd

d D

Diia

ag

gn

no

ossttiicc D

Da

atta

a P

Po

oiin

nttss

Summary of Contents for Tracer UC600

Page 1: ...uires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all prec...

Page 2: ...ctices are important to the environment our customers and the air conditioning industry All technicians who handle refrigerants must be certified according to local rules For the USA the Federal Clean...

Page 3: ...o of f e en ne er rg gi iz ze ed d e el le ec ct tr ri ic ca al l c co on nt ta ac ct t a ar rc c o or r f fl la as sh h t te ec ch hn ni ic ci ia an ns s M MU US ST T p pu ut t o on n a al ll l P PP...

Page 4: ...0 3rd Party BAS Integration 10 Tracer SC BAS Integration 11 BAS Unit Control 11 Initiating System Control 12 Routinely Updating BAS Values 12 Alarm Reset 12 BACnet Data Points and Configuration Proper...

Page 5: ...utomation and Control Network BACnet protocol is ANSI ASHRAE Standard 135 This standard allows building automation systems or components from different manufacturers to share information and control f...

Page 6: ...RX TX UC600 ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 0 1 2 3 4 5 6 7 8 9 x100 BO4 BO3 BO2 BO1 ADDRESS 0 1 2 3 4 5 6 7 8 9 x1 0 1 2 3 4 5 6 7 8 9 x10 0 1 2 3 4 5 6 7 8 9 x100 Rotary switc...

Page 7: ...on solid yellow Reverse polarity is present LED not illuminated The controller is not detecting communication Cycle the power to re establish communication Verify that the controller is capable of com...

Page 8: ...8 BAS SVP18D EN U UC C6 60 00 0 R Ro ot ta ar ry y S Sw wi it tc ch he es s a an nd d L LE ED Ds s...

Page 9: ...on USB cable radio button if it is not already selected 4 Click the Connect button and the Unit Summary page displays after successful connection Configuration At the Unit Summary page 1 Enter a meani...

Page 10: ...e ID box and enter a BACnet Device ID 8 Click Save 9 Cycle power to the device to have the new value take effect MS TP MAC Address Each device on a BACnet MS TP network must be assigned a unique physi...

Page 11: ...e the new value take effect N No ot te e When the software method is enabled the hardware method is automatically disabled Figure 3 Example showing rotary dial settings and the BACnet device ID Tracer...

Page 12: ...itions This may result in decreased occupant comfort and damage to building systems Alarm Reset The UC600 control system monitors the operation of the HVAC equipment If an abnormal condition is detect...

Page 13: ...TP communications interface for Trane IntelliPak ReliaTel and CH530 controls Standardized Device Profile Annex L Profile Description Supported Profile BACnet Advanced Application Controller B AAC BAC...

Page 14: ...t_State Out_Of_Service Units Object_Name Description Out_Of_Service Present_Value Reliability Min_Pres_Value Max_Pres_Value COV_Increment Time_Delay Notification_Class High_Limit Low_Limit Deadband Li...

Page 15: ...able Polarity Notify_Type Description Inactive_Text Active_Text Change_Of_State_Time Change_Of_State_Count Time_Of_State_Count_ Reset Elapsed_Active_Time Time_Of_Active_Time_ Reset Time_Delay Notifica...

Page 16: ..._Status Vendor_Name Vendor_Identifier Model_Name Firmware_Revision Application_Software_ Version Protocol_Version Protocol_Revision Protocol_Services_ Supported Protocol_Object_Types_ Supported Object...

Page 17: ...Object_Type Present_Value Status_Flags Event_State Out_Of_Service Number_Of_States Object_Name Description State_Text Out_Of_Service Present_Value Reliability Priority_Array Relinquish_Default Time_De...

Page 18: ...e 10 Baud Rate s 9600 19200 38400 Device Address Binding Device Address Binding Supported Static Device Binding Supported Networking Options Networking Descriptions Supported Option Annex H BACnet Tun...

Page 19: ...flow Monitoring Local outside air flow AI11 Discharge Air Temperature Local 25 to 135 F All Units Local discharge air temperature sensor AI12 Return Duct Space Pressure Local 0 2 in H2O Units with Pow...

Page 20: ...4 Discharge Air Temperature BAS 10 to 150 F All Units Communicated discharge air temperature AV5 Discharge Air Temperature Active 10 to 150 F All Units Actively used discharge air temperature AV6 DAT...

Page 21: ...100 F Units with Discharge Air Control Discharge air setpoing during heating mode AV33 Outdoor Air Heating Setpoint OAHS 40 75 F Units with Space Control Discharge Control or Single Zone VAV Setpoint...

Page 22: ...tic Pressure Active 6 to 6 in H2O Units with Multi Zone VAV Actively used duct static pressure AV66 Discharge Air Temperature Setpoint Active 38 130 F Units with Multi Zone VAV Actively used discharge...

Page 23: ...BO2 Outdoor Air Damper Command All Units 0 Open 1 Closed BO3 Heat 1 Command Units with Primary Heat 0 Off 1 On BO4 Inducer Command Units with Gas as the Primary Heat 0 Off 1 On BO5 Compressor 3 Comman...

Page 24: ...gnostic Space Humidity Source Failure Units that are Space Control or Single Zone VAV Auto Reset diagnostic 0 Normal 1 Fail BV13 Diagnostic Outdoor Air Temperature Source Failure All Units Auto Reset...

Page 25: ...ic Pressure Failure Units that are Multi Zone VAV Auto Reset diagnostic 0 Normal 1 Fail BV37 Unoccupied Dehumid Mode BAS All Units 0 Disabled 1 Enabled BV38 Unoccupied Heating Mode BAS All Units 0 Dis...

Page 26: ...nalog digital scroll or variable speed output command AI18 Circuit 1 Liquid Line Pressure Local 0 500 psi Units with Head Pressure Control and is an Air Source Heat Pump Local refrigerant pressure sen...

Page 27: ...erature is greater than the discharge air high limit for AV16 minutes the controller signals an alarm and shuts down the unit AV15 DAT Low Temp Cutout 35 50 F All Units If the discharge air temperatur...

Page 28: ...e air temperature setpoint AV65 Duct Static Pressure Active 6 to 6 in H2O Units with Multi Zone VAV Actively used duct static pressure AV64 Duct Static Pressure BAS 6 to 6 in H2O Units with Multi Zone...

Page 29: ...Gas Heat 6 Hot Water Steam AV69 Heat Cool Mode Deadband 58 to 482 F Units with Multi Zone VAV Heat is enabled when Outdoor Air Temperature drops below Discharge Temperature Setpoint Heat Cool Mode Dea...

Page 30: ...l Installed Time that Unoccupied Mode is delayed when Occupied Button is pressed AV1 Occupied Cooling Setpoint 55 85 F Units with Space Control or Single Zone VAV Space cooling setpoint used in occupi...

Page 31: ...All Units 1 Space Control 2 Discharge Control 3 Single Zone VAV 4 Multi Zone VAV BV18 Return Air Damper Option All Units 0 Not Installed 1 Installed AI14 Return Air Humidity Local 0 100 Units with Mod...

Page 32: ...0 Disabled 1 Enabled BV22 Unoccupied Cooling Mode BAS All Units 0 Disabled 1 Enabled AV26 Unoccupied Cooling Setpoint 60 90 F Units with Space Temperature Humidity Sensor Installed Space cooling setpo...

Page 33: ...red with Alarm Reset or power cycle 2 BV11 Diagnostic Space Temperature Source Failure 0 Normal 1 Fail Latching diagnostic Cleared with Alarm Reset or power cycle 2 BV12 Diagnostic Space Humidity Sour...

Page 34: ...pplication Guide BAS APG008 Tracer TU Online Help Tracer TU Service Tool Getting Started Guide TTU SVN01 Tracer UC600 Installation Instructions X39641178 01 Tracer XM30 Expansion Module Installation I...

Page 35: ...BAS SVP18D EN 35 N No ot te es s...

Page 36: ...For more information please visit trane com or tranetechnologies com Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications w...

Reviews: