Digital Inputs - Terminal X30/1-4
Parameters for set-up: 5-16, 5-17 and 5-18
Number of
digital in-
puts
Voltage
level
Voltage levels
Tolerance
Max. Input impedance
3
0-24 V DC PNP type:
Common = 0 V
Logic “0”: Input < 5 V DC
Logic “0”: Input > 10 V DC
NPN type:
Common = 24 V
Logic “0”: Input > 19 V DC
Logic “0”: Input < 14 V DC
± 28 V continuous
± 37 V in minimum
10 sec.
Approx. 5 k ohm
Analog Voltage Inputs - Terminal X30/10-12
Parameters for set-up: 6-3*, 6-4* and 16-76
Number of analog voltage in-
puts
Standardized input
signal
Tolerance
Resolu-
tion
Max. Input impe-
dance
2
0-10 V DC
± 20 V continuously
10 bits
Approx. 5 K ohm
Digital Outputs - Terminal X30/5-7
Parameters for set-up: 5-32 and 5-33
Number of digital outputs
Output level
Tolerance
Max.impedance
2
0 or 24 V DC
± 4 V
≥ 600 ohm
Analog Outputs - Terminal X30/5+8
Parameters for set-up: 6-6* and 16-77
Number of analog outputs
Output signal level
Tolerance
Max.impedance
1
0/4 - 20 mA
± 0.1 mA
< 500 ohm
4
TR200 Series VFD General Purpose I/O Option Module MCB 101 Instruction
Summary of Contents for TR200 MCB 101
Page 8: ......