TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION

Pub. No. 18-HD25D19-3

15

69-1790—3

Adaptive 
Intelligent 
Recovery™ 

0530

1

Adaptive Intelligent 
Recovery™ control is 
activated (system 
starts early so setpoint 
is reached by start of 
program period).

0

0

—conventional recovery 

(system starts recovery at 
programmed time)

Number of 
Periods

0540

4

Four periods available 
(Wake, Leave, Return, 
Sleep)

2

Two periods available (Wake 
and Sleep)

Not shown if
non-programmable is 
selected. 2 or 4 
applies to all days of 
the week.

Minimum 
Compressor 
Off Time

0580

5

Five minute minimum 
off time for 
compressor.

0, 2, 3, 
4

Minimum number of minutes 
compressor is off between 
calls for compressor.

Five minutes 
recommended

Heat 
Temperature 
Range Stop

0600

90

Highest heating 
setpoint.

40 to 89 Temperature range (1°F 

increments) of heating 
setpoint.

Shown in 1/2 °C.

Cool 
Temperature 
Range Stop

0610

50

Lowest cooling 
setpoint.

51 to 99 Temperature range (1°F 

increments) of cooling 
setpoint.

Shown in 1/2 °C.

Clock Format 0640

12

12-hour clock format 24

24-hour clock format

Extended Fan 
on time Heat

0650

0

No extended fan 
operation after call for 
heat ends.

90

Fan operation is extended 90 
seconds after call for heat 
ends.

Not shown if fan 
operation is set to 
fossil fuel or in Cool 
Only Systems

Extended Fan 
on time Cool

0660

0

No extended fan 
operation after call for 
cool ends.

90

Fan operation is extended 90 
seconds after call for cool 
ends.

Not shown in Heat 
Only Systems.

Keypad 
Lockout

0670

0

Unlocked keypad

1, 2

1

—partially locked keypad

2

—fully locked keypad

Unlocked—all 
functions are 
available.
Partially locked—only 
temperature up and 
down keys and ability 
to enter and modify 
Installer Setup mode 
are available. Fully 
locked—only ability to 
enter and modify 
Installer Setup mode 
are available.

Table 4. Installer Setup Menu. (Continued)

Select

Installer 

Setup 

Number

Factory Setting

Other Choices

Comments

Option

Description

Options

Description

Summary of Contents for TCONT802AS32DA

Page 1: ...this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Installer must be a trained experienced service technician...

Page 2: ...FIG 5 15 All wiring must comply with local electrical codes and ordinances 1 Select set of terminal identifications Table 2 that corresponds with system type heat cool or heat pump in Fig 3 2 Loosen...

Page 3: ...REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 RC S1 R S2 W1 Y G B HEAT COOL T B C W T T G Y R OIL FURNACE Y B COOLING UNIT O D SECTION SINGLE...

Page 4: ...O D SECTION SINGLE STAGE TO POWER SUPPLY PER LOCAL CODES 3 PH ONLY INDOOR OUTDOOR W1 Y2 F X2 O R O W3 TO POWER SUPPLY PER LOCAL CODES AND AS DEFINED IN FIELD WIRING TABLE SUPPL HTR CONTROL BOX I PF RE...

Page 5: ...STAT CABLE THE INSTALLER MUST JUMPER AT THE LVTB R TO O 1 2 2 RC S1 R S2 O Y G B HEAT PUMP T B C G Y YLO BK R VARIABLE SPEED AIR HANDLER B 16 SEER HEAT PUMP O D SECTION TWO STEP TO POWER SUPPLY PER LO...

Page 6: ...iable speed gas furnace 2H 1C heat pump W1 W2 G Y B C R T 1 1 2 FACTORY INSTALLED JUMPER OUTDOOR REMOTE SENSOR WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE Y R O BR T BR X2 OR BK B HEAT...

Page 7: ...ble speed gas furnace 3H 2C heat pump W1 W2 G Y Y2 B C R T 1 1 2 FACTORY INSTALLED JUMPER OUTDOOR REMOTE SENSOR WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE Y2 R O BR T X2 BK B F HEAT PU...

Page 8: ...ng freezing conditions Connect the 24 Vac Common B wire from the system transformer to the comfort control for proper operation when the battery power is drained Three AAA alkaline batteries can be us...

Page 9: ...calendar date to be entered See Fig 19 Fig 19 Setting calendar and time after initial powerup IMPORTANT The tab on the back of the comfort control in the lower left corner must be removed for this fe...

Page 10: ...Common Connection An LED indicator is located in the upper right corner of the comfort control It is only visible when lighted It indicates when the comfort control is in the Emergency Heat mode When...

Page 11: ...y five seconds until screen changes 4 Release the two blank keys when the screen on the comfort control matches the screen below 5 See screen below to review how the comfort control keys are used duri...

Page 12: ...3 wire or normally open zone valves 6 cool only 7 2 heat 1cool heat pump 8 2 heat 2 cool 9 2 heat 1cool 10 1 heat 2 cool oil furnace or 0H 2C 11 2 heat 2 cool heat pump with no auxiliary heat 12 3 hea...

Page 13: ...ur cph for Auxiliary Heat in 3H 2C Heat Pump Systems 1 12 1 12 available typical settings 1 1cph used for steam or gravity system 3 3 cph used for 2 stage fossil fuel forced air systems or hot water s...

Page 14: ...Features section for more details 3 indoor temperature sensor Defaults and Options depend on System Type selection Indoor Temperature Sensor uses an averaging network and does not include on board sen...

Page 15: ...ature Range Stop 0610 50 Lowest cooling setpoint 51 to 99 Temperature range 1 F increments of cooling setpoint Shown in 1 2 C Clock Format 0640 12 12 hour clock format 24 24 hour clock format Extended...

Page 16: ...less aggressive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp Choose 1 if getting temperature...

Page 17: ...est Avoid cycling compressor quickly Table 5 System Test s Select Installer Setup Number Factory Setting Other Choices Comments Options Description Options Description Installer Test Cool Test 1 0 Coo...

Page 18: ...W1 terminal Often there is only one source of non compressor heat and the X2 terminal is jumpered to the W1 terminal Heat Pump with Electric Auxiliary Backup Heat and Outdoor Temperature Sensor 1 Choo...

Page 19: ...eating or cooling does not come on Comfort control minimum off time is activated Wait up to five minutes for the system to respond System selection is not set to Heat or Cool Set system Selection to c...

Page 20: ...AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION Pub No 18 HD25D19 3 69 1790 3 M S Rev 01 06 U S Registered Trademark 2006 American Standard Inc All Rights Reserved American Standard Inc Troup H...

Reviews: