background image

TCONT802AS32DA TOUCH SCREEN AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION 

Pub. No. 18-HD25D19-3
69-1790—3

18

ADVANCED FEATURES

Outdoor or Indoor Temperature Sensor

For accuracy, the initial reading of the indoor and outdoor 
temperature sensors require five minutes to stabilize. See 
the Sensor instructions for installation information.

Special Heat Pump Features

Heat Pump with Fossil Fuel Auxiliary Heat (Dual 
Fuel) and Outdoor Temperature Sensor

In this operation there is no external fossil fuel kit (dual 
fuel kit) installed; the comfort control controls this function.

1.

Choose correct heat pump application in Installer 
Setup Number 0170.

2.

Choose 

Fossil Fuel Option

 as the backup heat 

source in Installer Setup Number 0200.

3.

Choose 

No External Fossil Fuel Kit Option 

as 

controlling backup heat in installer Setup Number 
0210.

4. Outdoor Temperature Sensor for Control Option

 

is automatically chosen in Installer Setup Number 
0340.

5.

Choose appropriate 

Balance Point Temperature 

in Installer Setup Number 0350.

OPERATION IN HEAT MODE ABOVE BALANCE POINT 
(OUTDOOR TEMPERATURE)

When the outdoor temperature is above the selected 
Balance Point Temperature (ISU 0350), only the 
compressor operates and the fan (G terminal) energizes 
when the comfort control calls for heat.

OPERATION IN HEAT MODE BELOW BALANCE POINT 
(OUTDOOR TEMPERATURE)

When the outdoor temperature is below the selected 
Balance Point Temperature (ISU 0350), only the Fossil 
Fuel (auxiliary heat) operates and the fan (G terminal) 
does not energize when the comfort control calls for heat.

OPERATION IN EMERGENCY HEAT MODE

The balance point (outside) temperature is not used in the 
Emergency heat mode. When the comfort control is 
moved to the Emergency Heat position, the compressor is 
locked out. The first stage of heat is whatever is 
connected to the X2 terminal. The second stage of heat is 
what is connected to the W1 terminal. Often there is only 
one source of non-compressor heat and the X2 terminal is 
jumpered to the W1 terminal.

Heat Pump with Electric Auxiliary (Backup) Heat 
and Outdoor Temperature Sensor

1.

Choose correct heat pump application in Installer 
Setup Number 0170.

2.

Choose Electric as 

Auxiliary (Backup) Heat 

Source

 in Installer Setup Number 0200.

3.

Choose 

Outdoor Temperature Sensor for 

Control Option 

in Installer Setup Number 0340.

4.

Choose 

Compressor Lockout Temperature

 in 

Installer Setup Number 0350.

5.

Choose 

Auxiliary Lockout Temperature 

in 

Installer Setup Number 0360.

NOTE: There is a 5°F deadband between the Compres-

sor and Auxiliary Heat Lockout Temperatures

OPERATION IN HEAT MODE

When the outdoor temperature is below the Compressor 
Lockout Temperature, only the Auxiliary Heat operates.

When the outdoor temperature is above the Auxiliary 
Lockout Temperature, only the Compressor operates. 
See Fig. 21.

Fig. 21. Heat Pump Operation with Lockout 

Temperatures Set.

When the outdoor temperature is between the two 
temperatures, both the Compressor and Auxiliary Heat 
operate.

OPERATION IN THE EMERGENCY HEAT MODE

Once the comfort control is placed into the Emergency 
Heat mode, the compressor and auxiliary lockout features 
are turned off. In the Emergency heat mode, the 
compressor is locked out. The first stage of heat is 
whatever is connected to the X2 terminal. The second 
stage of heat is connected to the W1 terminal. Usually the 
emergency and auxiliary heat sources are electric strip 
heat in these cases.

Dehumidification Droop Control

The dehumidification control attempts to control to the 
user's humidity setpoint by turning on the air conditioner. 
In extremely high humidity conditions, the comfort control 
keeps the air conditioner running for up to 3

°

F below the 

temperature setpoint. It does this while trying to achieve 
the desired humidity setpoint and balancing that with the 
temperature setpoint.

35

M19950

COMPRESSOR
LOCKOUT
TEMPERATURE

AUXILIARY
LOCKOUT
TEMPERATURE

COMPRESSOR ONLY

BOTH COMPRESSOR AND

AUXILIARY HEAT

AUXILIARY ONLY

50

OUTDOOR TEMPERATURE

Summary of Contents for TCONT802AS32DA

Page 1: ...this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Installer must be a trained experienced service technician...

Page 2: ...FIG 5 15 All wiring must comply with local electrical codes and ordinances 1 Select set of terminal identifications Table 2 that corresponds with system type heat cool or heat pump in Fig 3 2 Loosen...

Page 3: ...REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 RC S1 R S2 W1 Y G B HEAT COOL T B C W T T G Y R OIL FURNACE Y B COOLING UNIT O D SECTION SINGLE...

Page 4: ...O D SECTION SINGLE STAGE TO POWER SUPPLY PER LOCAL CODES 3 PH ONLY INDOOR OUTDOOR W1 Y2 F X2 O R O W3 TO POWER SUPPLY PER LOCAL CODES AND AS DEFINED IN FIELD WIRING TABLE SUPPL HTR CONTROL BOX I PF RE...

Page 5: ...STAT CABLE THE INSTALLER MUST JUMPER AT THE LVTB R TO O 1 2 2 RC S1 R S2 O Y G B HEAT PUMP T B C G Y YLO BK R VARIABLE SPEED AIR HANDLER B 16 SEER HEAT PUMP O D SECTION TWO STEP TO POWER SUPPLY PER LO...

Page 6: ...iable speed gas furnace 2H 1C heat pump W1 W2 G Y B C R T 1 1 2 FACTORY INSTALLED JUMPER OUTDOOR REMOTE SENSOR WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE Y R O BR T BR X2 OR BK B HEAT...

Page 7: ...ble speed gas furnace 3H 2C heat pump W1 W2 G Y Y2 B C R T 1 1 2 FACTORY INSTALLED JUMPER OUTDOOR REMOTE SENSOR WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE Y2 R O BR T X2 BK B F HEAT PU...

Page 8: ...ng freezing conditions Connect the 24 Vac Common B wire from the system transformer to the comfort control for proper operation when the battery power is drained Three AAA alkaline batteries can be us...

Page 9: ...calendar date to be entered See Fig 19 Fig 19 Setting calendar and time after initial powerup IMPORTANT The tab on the back of the comfort control in the lower left corner must be removed for this fe...

Page 10: ...Common Connection An LED indicator is located in the upper right corner of the comfort control It is only visible when lighted It indicates when the comfort control is in the Emergency Heat mode When...

Page 11: ...y five seconds until screen changes 4 Release the two blank keys when the screen on the comfort control matches the screen below 5 See screen below to review how the comfort control keys are used duri...

Page 12: ...3 wire or normally open zone valves 6 cool only 7 2 heat 1cool heat pump 8 2 heat 2 cool 9 2 heat 1cool 10 1 heat 2 cool oil furnace or 0H 2C 11 2 heat 2 cool heat pump with no auxiliary heat 12 3 hea...

Page 13: ...ur cph for Auxiliary Heat in 3H 2C Heat Pump Systems 1 12 1 12 available typical settings 1 1cph used for steam or gravity system 3 3 cph used for 2 stage fossil fuel forced air systems or hot water s...

Page 14: ...Features section for more details 3 indoor temperature sensor Defaults and Options depend on System Type selection Indoor Temperature Sensor uses an averaging network and does not include on board sen...

Page 15: ...ature Range Stop 0610 50 Lowest cooling setpoint 51 to 99 Temperature range 1 F increments of cooling setpoint Shown in 1 2 C Clock Format 0640 12 12 hour clock format 24 24 hour clock format Extended...

Page 16: ...less aggressive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp Choose 1 if getting temperature...

Page 17: ...est Avoid cycling compressor quickly Table 5 System Test s Select Installer Setup Number Factory Setting Other Choices Comments Options Description Options Description Installer Test Cool Test 1 0 Coo...

Page 18: ...W1 terminal Often there is only one source of non compressor heat and the X2 terminal is jumpered to the W1 terminal Heat Pump with Electric Auxiliary Backup Heat and Outdoor Temperature Sensor 1 Choo...

Page 19: ...eating or cooling does not come on Comfort control minimum off time is activated Wait up to five minutes for the system to respond System selection is not set to Heat or Cool Set system Selection to c...

Page 20: ...AND TCONT803AS32DA TOUCH SCREEN WITH DEHUMIDIFICATION Pub No 18 HD25D19 3 69 1790 3 M S Rev 01 06 U S Registered Trademark 2006 American Standard Inc All Rights Reserved American Standard Inc Troup H...

Reviews: