69-1591–1
6
ELECTRONIC HEAT PUMP THERMOSTAT
Pub. No. 11-HD28D2-1
Table 2. Thermostat Installer Setup Options (Continued).
Installer
Setup Number
Factory-Setting
Other Choices
(Press
▲
or
▼
key to change)
Select
Display
Description
Display
Description
Degree temperature
display
14
00
Temperature displays in
°
F
01
Temperature displays in
°
C
Extended fan operation in
heating
19
00
No extended fan
operation after the call
for heat ends
01, 02
or 03
01—Fan operation exends
30 seconds after the call
ends
02—Fan operation exends
60 seconds after the call
ends
03—Fan operation exends
90 seconds after the call
ends
Extended fan operation in
cooling
20
00
No extended fan
operation after the call
for cool ends
01, 02
or 03
01—Fan operation exends
30 seconds after the call
ends
02—Fan operation exends
60 seconds after the call
ends
03—Fan operation exends
90 seconds after the call
ends
Outdoor temperature
display (select models)
24
00
No outdoor temperature
displays.
01
Outdoor temperature is
displayed. Needs a
TAYSENS100A Outdoor
Sensor
Comfort-R Enable
28
00
No fan delay
01 or
02
01—30 seconds (maximum
delay)
02—15 seconds (maximum
delay)
Minimum deadband
between heating and
cooling in auto
changeover mode
30
04
Heating and cooling
setpoints can be set no
closer than 4
°
F (2
°
C)
03 thru
10
Heating and cooling
setpoints can be set no
closer than the chosen
value:
3—3
°
F (1.5
°
C)
4—4
°
F (2
°
C)
5—5
°
F (2.5
°
C)
6—6
°
F (3
°
C)
7—7
°
F (3.5
°
C)
8—8
°
F (4
°
C)
9—9
°
F (4.5
°
C)
10—10
°
F (5
°
C)
Minimum on time (heat)
32
10
Ten-minute minimum on
time for compressor
(heating)
00 thru
15
Minimum number of minutes
(0 thru 15) the compressor is
on during call for heat
Minimum on time
(cooling)
33
10
Ten-minute minimum on
time for compressor
(cooling)
00 thru
15
Minimum number of minutes
(0 thru 15) the compressor is
on during call for cool
Temperature range stops
in heating
34
85
Highest heating
sepoint setting
01
Temperature range (1
°
F
increments) of heating
setpoint setting
Temperature range stops
in cooling
35
65
Lowest cooling
sepoint setting
—
Temperature range (1
°
F
increments) of cooling
setpoint setting