46
18-GJ06D2-2A
Filters
Table 22.
Filter Considerations
•
A filter must be installed within the system.
•
A filter channel is provided in the unit at the bottom of the Blower/
Filter compartment.
•
For customer ease of filter maintenance, it is recommended that a
properly sized remote filter grill(s) be installed for units that are
difficult to access. Airflow should not exceed the maximum rated
velocity of the filter being used.
Table 23.
Filter Sizes
Cabinet Size *
A
B
C
Filter Size
16 x 20
20 x 20
22 x 20
* Cabinet size is indicated by the 7th digit in model number.
Filte r in a ir h a n d le r
cabi net
(Up flo w Ap p lica tio n )
System Charge Adjustments
System Matched with:
Indoor Unit Model No.
Outdoor Unit Model No.
Subcooling
Single Compressor
2–Stage HP
TAM7A0B30H21SC
4A6H6024E/G, 4TWX6024E/G
4A6H7024, 4TWX8024
9°
TAM7A0C36H31SC
4A6H6036E/G, 4TWX6036E/G
4A6H7036, 4TWX8036
10°
TAM7A0C48H41SC
4A6H6048E/G, 4TWX6048E/G
4A6H7048, 4TWX8048
8°
Single Compressor
2–Stage AC
TAM7A0B30H21SC
4A7A6024E/G, 4TTX6024E/G
4A7A7024, 4TTX8024
8°
TAM7A0C36H31SC
4A7A6036E/G, 4TTX6036E/G
4A7A7036, 4TTX8036
8°
TAM7A0C48H41SC
4A7A6048E/G, 4TTX6048E/G
4A7A7048, 4TTX8048
8°
Two Compressor
2–Stage HP
TAM7A0B30H21SC
4TWZ0024A, 4A6Z0024A
9°
TAM7A0C36H31SC
4TWZ0036A/B, 4A6Z0036A/B
10°
TAM7A0C48H41SC
4TWZ0048A/B, 4A6Z0048A/B
12°
TAM7B0C60H51SB
4TWZ0060A, 4A6Z0060A
12°
Two Compressor
2–Stage HP
TAM7A0B30H21SC
4TTZ0036A/B, 4A7Z0024A
9°
TAM7A0C36H31SC
4ATTZ0036A/B, 4A7Z0036A/B
11°
TAM7A0C48H41SC
4TTZ0048A/B, 4A7Z0048A/B
13°
NOTES:
1. Variable Speed outdoor units must be charged per the outdoor unit instructions.
2. All other matches must be charged per the nameplate charging instructions.