![Trane SCWM Installation, Operation And Maintenance Manual Download Page 12](http://html1.mh-extra.com/html/trane/scwm/scwm_installation-operation-and-maintenance-manual_1150283012.webp)
12
PKG-SVX027C-EN
Table 4.
SCWM refrigerant circuits, number of compressors by circuit (continued)
Tonnage
Model No.
Circuit
1
2
3
4
60
SCWMN06L
1-10T VS
1-15T FS
1-15T FS
N/A
SCWMN060
1-15T VS
1-15T FS
1-15T FS
N/A
70
SCWMN07L
1-10T VS
1-13T FS
1-13T FS
1-13T FS
SCWMN070
1-15T VS
1-13T FS
1-13T FS
1-13T FS
80
SCWMN08L
1-10T VS
1-15T FS
1-15T FS
1-15T FS
SCWMN080
1-15T VS
1-15T FS
1-15T FS
1-15T FS
Note:
VS - Variable Speed Compressor, S - Fixed Speed Compressor
Table 5.
Waterside economizer coil physical data
Model
Unit Size
Rows
FPF
Height
Length
MSC
40 Ton
4
150
75
49
MSC
50 Ton
4
150
75
65
MSC
60 Ton
4
150
75
73
MSC
(a)
70 Ton
4
150
75
38
4
150
75
64
MSC
80 Ton
4
150
75
38
4
150
75
64
(a)
Split coils
Table 6.
Hot water coil physical data
Model
Unit Size
Rows
FPF
Height
Length
MSC
40 Ton
1
156
75
49
MSC
50 Ton
1
156
75
65
MSC
60 Ton
1
156
75
73
MSC
(a)
70 Ton
1
156
75
45
1
156
75
45
MSC
80 Ton
1
156
75
45
1
156
75
45
(a)
Split coils
IIm
mp
po
orrtta
an
ntt:: All performance data is provided in the
Performance Selection Program. Contact
your local Trane Sales office for more
information.