RLC-SVX19A-E4
8
General Data
RTAF Standard Effi ciency - Standard and Low Noise
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
090
105
125
145
155
175
190
205
Eurovent Performances
SE SN&LN SE SN&LN
SE SN&LN SE SN&LN
SE SN&LN
SE SN&LN SE SN&LN SE SN&LN
Net Cooling Capacity (3) (4)
(kW)
326
375
440
522
564
615
675
732
Power Input (5)
(kW)
104
121
146
165
184
206
221
244
EER (3) (4) (6)
(kW/kW)
3.14
3.10
3.02
3.16
3.06
2.98
3.05
3.00
ESEER (6)
(kW/kW)
3.86
3.86
3.94
3.91
3.84
3.95
3.92
3.92
Eurovent Effi ciency class Cooling
A
B
B
A
B
B
B
B
Sound power level (Standard Noise) (10)
(dBA)
95
95
95
96
96
97
97
97
Sound power level (Low Noise) (10)
(dBA)
92
92
92
93
93
94
94
94
Middle East design condition performances (7)
Gross cooling capacity
(tons)
77
88
103
124
133
145
160
172
Gross EER
(kW/ton)
1.5
1.5
1.6
1.5
1.5
1.6
1.5
1.6
MEW (Kuwait) rating point performances (8)
Gross cooling capacity
(tons)
73
84
97
117
125
135
150
162
Gross EER
(kW/ton)
1.6
1.7
1.7
1.6
1.7
1.7
1.7
1.7
Table 1 – General Data RTAF 090 – 205 Standard Effi ciency - Standard and Low Noise
Compressor
Quantity
#
2
2
2
2
2
2
2
2
Nominal Size (1)
tons
45/45
50/50
70/50
70/70
85/70
100/70
100/85
100/100
Evaporator
Evaporator Model
115B
115A
165B
165B
165A
200B
200B
250C
Water Storage
l
51
58
74
74
78
99
99
109
Two pass Evaporator
Minimum Flow
l/s
8.0
9.4
11.6
11.6
12.4
14.2
14.2
16.2
Maximum Flow
l/s
29.6
34.7
43.1
43.1
46.0
52.6
52.6
60.3
Two pass Evaporator – with Turbulators
Minimum Flow
l/s
6.6
7.8
9.7
9.7
10.3
11.8
11.8
13.5
Maximum Flow
l/s
26.6
31.2
38.7
38.7
41.3
47.2
47.2
54.1
Condenser
Quantity of Coils
#
4/4
4/4
4/4
5/5
5/5
6/4
6/6
6/6
Coil Length
mm
1967
1967
1967
1967
1967
1967
1967
1967
Coil Height
mm
1214
1214
1214
1214
1214
1214
1214
1214
Condenser Fans
Quantity (1)
#
4/4
4/4
4/4
5/5
5/5
6/4
6/6
6/6
Diameter
mm
800
800
800
800
800
800
800
800
Total Air Flow
m
3
/s
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
Nominal RPM
rpm
932
932
932
932
932
932
932
932
Motor
kW
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
Minimum Starting/Operating Ambient
Standard Unit
°C
-10
-10
-10
-10
-10
-10
-10
-10
Low-Ambient Unit (Option)
°C
-20
-20
-20
-20
-20
-20
-20
-20
Maximum ambient operation
Standard ambient (9)
°C
46
46
46
46
46
46
46
46
Maximum ambient operation
High ambient (9)
°C
55
55
55
55
55
55
55
55
General Unit
Refrigerant
HFC134a
HFC134a
HFC134a
HFC134a
HFC134a
HFC134a
HFC134a
HFC134a
Number of Independent
Refrigerant Circuits
#
2
2
2
2
2
2
2
2
Minimum Load (2)
%
15
15
15
15
15
15
15
15
Operating Weight
kg
3295
3315
3495
3990
4260
4405
4880
4995
Shipping Weight
kg
3236
3247
3409
3904
4170
4290
4765
4868
R134a refrigerant charge
Circuit1/Circuit 2
(kg)
38/38
36/36
40/39
44/43
47/42
57/48
58/55
66/63
Oil charge Circuit1/Circuit 2
(l)
6/6
6/6
6/6
6/6
7/6
7/6
7/7
8/8
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2.
2. Percent minimum load is for total machine at 10°C ambient and 7°C leaving chilled water temperature, not each
individual circuit.
3. Net cooling capacity at Eurovent conditions, 7°C leaving water temperature and 35°C entering condenser air
temperature.
4. Ratings based on sea level altitude and evaporator fouling factor 0.017645 m²K/kW.
5. Unit kW input, including fans.
6. Calculate with cooling capacity.
7. At Evaporator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 46°C (114.8°F).
8. At Evapotator water temperature: 6.6°C (44°F)/12.2°C (54°F) - Condenser air temperature 48°C (118.4°F),
according to Code of practice MEW/R-6/2010 issued by Kuwaiti Ministry of Electricity and Water (MEW).
9. Maximum ambient operation is for unit at 12°C/7°C.
10. At Eurovent conditions, with 1pW Reference Sound Power, according to ISO9614.