RLC-SVX19A-E4
37
General Electrical Recommendations
Wire Sizing and Electrical Data
Table 13
–
Electrical Data RTAF 090 - 205/Standard Effi ciency
Unit Wiring
400/3/50
Unit Size
Number of Power
Connections
Maximum Amps
(1)
Starting Amps
(2)
Power Factor (3)
Disconnect
Switch Size
Short Circuit
Rating (kA)
Standard noise level/Low noise level/Extra low noise level
090
1
255
302
0.89
400
35.0
105
1
293
357
0.88
400
35.0
125
1
335
436
0.89
500
35.0
145
1
394
495
0.89
630
35.0
155
1
433
527
0.89
630
35.0
175
1
471
591
0.87
630
35.0
190
1
523
643
0.87
800
35.0
205
1
560
680
0.85
800
35.0
Table 14
–
Electrical Data RTAF 090 - 205/High Effi ciency
Unit Wiring
400/3/50
Unit Size
Number of Power
Connections
Maximum Amps
(1)
Starting Amps
(2)
Power Factor (3)
Disconnect
Switch Size
Short Circuit
Rating (kA)
Standard noise level/Low noise level/Extra low noise level
090
1
263
302
0.89
400
35.0
105
1
301
357
0.88
400
35.0
125
1
343
436
0.89
500
35.0
145
1
401
495
0.89
630
35.0
155
1
440
527
0.89
630
35.0
175
1
478
591
0.87
630
35.0
190
1
531
643
0.87
800
35.0
205
1
568
680
0.85
800
35.0
Table 15
–
Electrical Data RTAF 090 - 205/Extra Effi ciency
Unit Wiring
400/3/50
Unit Size
Number of Power
Connections
Maximum Amps
(1)
Starting Amps
(2)
Power Factor (3)
Disconnect
Switch Size
Short Circuit
Rating (kA)
Standard noise level/Low noise level/Extra low noise level
090
1
263
310
0.90
400
35.0
105
1
301
365
0.88
400
35.0
125
1
343
444
0.89
500
35.0
145
1
401
502
0.89
630
35.0
155
1
440
534
0.89
630
35.0
175
1
478
598
0.87
800
35.0
190
1
531
651
0.87
800
35.0
205
1
568
688
0.85
800
35.0
Table 16
–
Electrical Data RTAF 090 - 205/High Seasonable Effi ciency
Unit Wiring
400/3/50
Unit Size
Number of Power
Connections
Maximum Amps
(1)
Starting Amps
(2)
Power Factor (3)
Disconnect
Switch Size
Short Circuit
Rating (kA)
Standard noise level/Low noise level/Extra low noise level
090
1
263
263
0.95
400
35.0
105
1
301
301
0.95
400
35.0
125
1
343
343
0.95
500
35.0
145
1
401
401
0.95
630
35.0
155
1
440
440
0.95
630
35.0
175
1
478
478
0.95
800
35.0
190
1
531
531
0.95
800
35.0
205
1
568
568
0.95
800
35.0
Notes:
1. Maximum Compressors FLA + All Fans FLA + Control Amps
2. Starting amps of the largest compressor plus RLA of second compressor plus RLA of all fans and control amps
3. Compressor Power Factor