RLC-SVX19A-E4
32
Evaporator Waterside
Evaporator Glycol Requirement
Standard tubes: Without Turbulator
Table 8 – Leaving water temperature cutout & glycol mass percent recommended for RTAF chillers with Standard
tubes
Table 9 – Leaving water temperature cutout & glycol mass percent recommended for RTAF chillers with Standard
tubes
Ethylene Glycol
Unit type
SE Units
HE/XE/HSE Units
dT
evaporator
coolant (K)
2
3
4
5
6
7
8
2
3
4
5
6
7
8
LWT
(°C)
LWTC
(°C)
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
%wt
Glycol
4
1.2
-
4
4
4
4
4
5
13
4
4
4
4
4
5
2
-0.8
-
8
8
9
10
12
-
18
8
8
9
10
12
-
0
-2.8
13
13
13
15
19
-
-
22
13
13
15
19
-
-
-2
-4.8
18
18
19
-
-
-
-
24
18
19
-
-
-
-
-4
-6.8
22
22
-
-
-
-
-
25
22
-
-
-
-
-
-5
-7.8
24
25
-
-
-
-
-
27
25
-
-
-
-
-
-6
-8.8
25
29
-
-
-
-
-
29
29
-
-
-
-
-
-7
-9.8
27
-
-
-
-
-
-
31
-
-
-
-
-
-
-8
-10.8
29
-
-
-
-
-
-
-
-
-
-
-
-
-
-9
-11.8
31
-
-
-
-
-
-
-
-
-
-
-
-
-
-10
-12.8
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-11
-13.8
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-12
-14.8
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Monopropylene Glycol
Unit type
RTAF Units
dT
evaporator
coolant (K)
2
3
4
5
6
7
8
LWT (°C)
LWTC (°C) %wt Glycol
%wt Glycol
%wt Glycol
%wt Glycol
%wt Glycol
%wt Glycol
%wt Glycol
4
1.2
-
4
4
4
4
5
-
2
-0.8
10
9
10
12
-
-
-
0
-2.8
15
16
21
-
-
-
-
-2
-4.8
20
-
-
-
-
-
-
-4
-6.8
27
-
-
-
-
-
-
-5
-7.8
-
-
-
-
-
-
-
-6
-8.8
-
-
-
-
-
-
-
-7
-9.8
-
-
-
-
-
-
-
-8
-10.8
-
-
-
-
-
-
-