RT-PRC010-EN
48
Performance
(30 Ton)
Data
Table PD-34 — Supply Fan Performance With VARIABLE FREQUENCY DRIVE or WITHOUT INLET VANES — 30 Ton
Cfm
Total Static Pressure
Std
.250
.500
.750
1.000
1.250
1.500
1.750
2.000
Air
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6000
316
.50
426
.89
519
1.36
598
1.88
666
2.42
728
2.99
784
3.59
835
4.22
7000
334
.65
430
1.05
521
1.56
600
2.12
669
2.71
731
3.32
788
3.97
841
4.64
8000
354
.85
440
1.27
523
1.78
602
2.37
671
3.01
733
3.67
791
4.36
844
5.08
9000
376
1.09
456
1.54
530
2.06
603
2.66
673
3.33
736
4.04
793
4.78
846
5.54
10000
399
1.38
474
1.87
542
2.40
609
3.00
674
3.69
737
4.43
795
5.22
849
6.02
11000
424
1.73
493
2.25
558
2.82
619
3.43
679
4.11
739
4.86
797
5.68
851
6.53
12000
450
2.13
515
2.70
576
3.30
633
3.93
688
4.62
744
5.37
798
6.19
852
7.07
13000
475
2.59
537
3.21
595
3.85
649
4.52
701
5.22
753
5.98
804
6.79
854
7.67
13500
488
2.85
549
3.50
605
4.15
658
4.83
709
5.55
758
6.32
808
7.13
856
8.01
Cfm
Total Static Pressure
Std
2.250
2.500
2.750
3.000
3.250
3.500
3.750
4.000
Air
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6000
883
4.86
927
5.51
968
6.18
1007
6.86
1043
7.54
1078
8.24
1111
8.94
1143
9.65
7000
890
5.33
936
6.04
979
6.78
1020
7.52
1059
8.28
1095
9.05
1130
9.83
1164
10.62
8000
894
5.82
941
6.57
985
7.35
1027
8.15
1067
8.97
1105
9.80
1142
10.65
1177
11.51
9000
896
6.32
944
7.13
989
7.95
1031
8.79
1072
9.66
1111
10.54
1149
11.43
1185
12.35
10000
899
6.85
946
7.70
991
8.57
1034
9.46
1075
10.37
1115
11.29
1153
12.24
1189
13.20
11000
901
7.41
949
8.30
994
9.22
1037
10.15
1078
11.11
1118
12.08
1156
13.07
1193
14.07
12000
903
7.99
951
8.94
996
9.90
1039
10.88
1080
11.88
1120
12.89
1158
13.93
1195
14.98
13000
904
8.61
952
9.60
998
10.61
1041
11.63
1083
12.68
1122
13.74
1161
14.82
1198
15.91
13500
905
8.95
953
9.94
998
10.97
1042
12.02
1084
13.09
1123
14.18
1162
15.28
1199
16.40
Cfm
Total Static Pressure
Std
4.250
4.500
4.750
5.000
5.250
5.500
5.750
6.000
Air
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
6000
1174
10.37
1203
11.10
1231
11.83
1259
12.57
1285
13.32
1311
14.08
1336
14.85
1361
15.62
7000
1196
11.41
1227
12.22
1256
13.03
1285
13.85
1313
14.68
1340
15.51
1366
16.35
8000
1210
12.38
1243
13.26
1274
14.14
1304
15.04
1333
15.94
1361
16.85
9000
1219
13.28
1253
14.22
1285
15.18
1316
16.14
1347
17.11
1376
18.10
10000
1225
14.17
1259
15.16
1292
16.17
1324
17.19
1355
18.23
11000
1228
15.09
1263
16.13
1297
17.18
1329
18.25
1361
19.33
12000
1231
16.04
1266
17.13
1300
18.22
1333
19.33
1365
20.46
13000
1234
17.03
1268
18.15
1302
19.30
1335
20.45
1368
21.62
13500
1235
17.53
1270
18.68
1303
19.85
1337
21.03
1369
22.22
Notes:
1. Shaded areas at table extremes note non-standard Bhp or Rpm selection. Contact your local Trane representative for more information.
2. Supply fan performance table includes internal resistance of rooftop. For total static pressure determination, system external static must be added to appropriate component
static pressure drops (evaporator coil, filters, optional economizer, optional exhaust fan, optional heating system, optional cooling only extended casing, optional roof curb).
3. Minimum motor horsepower is 5 hp, maximum motor horsepower is 20 hp. Maximum RPM is 1379.
4. Max Cfm (for UL approval) as follows: 30 Ton-13,500 Cfm.
5. See RT-EB-104 for further details.