43
RT-PRC010-EN
Performance
Data
Table PD-31— Hot Water Heating Capacities (Q/ITD)
1
20, 25, 30 Nominal Tons
Hot Water
Water
Unit Standard Air Volume (Cfm)
Module
Gpm
PD (Ft)
4000
6000
8000
10000
12000
14000
Low
10
0.54
1.65
1.99
2.21
2.37
2.48
2.56
High
20
0.91
2.23
2.78
3.16
3.44
3.67
3.85
Low
20
0.91
1.88
2.35
2.69
2.94
3.12
3.27
High
30
1.49
2.36
3.00
3.46
3.81
4.09
4.31
Low
30
1.49
1.97
2.51
2.90
3.19
3.42
3.60
High
40
2.25
2.43
3.12
3.63
4.02
4.34
4.60
Low
40
2.25
2.02
2.60
3.02
3.34
3.60
3.79
High
50
3.2
2.48
3.20
3.74
4.17
4.51
4.80
Low
60
4.31
2.08
2.69
3.16
3.51
3.79
4.02
High
70
5.65
2.54
3.30
3.88
4.35
4.73
5.04
40, 50, 55 Nominal Tons
Hot Water
Water
Unit Standard Air Volume (Cfm)
Module
Gpm
PD (Ft)
8000
11000
14000
17000
20000
23000
Low
20
0.70
3.00
3.44
3.75
3.98
4.14
4.29
High
30
1.05
3.85
4.46
4.91
5.26
5.54
5.76
Low
40
1.51
3.40
4.00
4.43
4.76
5.02
5.21
High
50
2.10
4.20
4.95
5.52
5.97
6.34
6.64
Low
60
2.78
3.56
4.23
4.73
5.11
5.40
5.63
High
75
4.04
4.39
5.24
5.89
6.41
6.85
7.21
Low
80
4.50
3.65
4.36
4.89
5.31
5.63
5.88
High
90
5.54
4.46
5.34
6.03
6.58
7.04
7.42
Low
100
6.66
3.71
4.44
5.00
5.43
5.77
6.04
High
125
9.99
4.56
5.50
6.23
6.83
7.33
7.75
60, 70, 75 Nominal Tons
Hot Water
Water
Unit Standard Air Volume (Cfm)
Module
Gpm
PD (Ft)
12000
16000
20000
24000
28000
31500
Low
25
0.98
4.28
4.82
5.20
5.48
5.69
5.83
High
30
1.22
5.24
5.91
6.40
6.77
7.06
7.27
Low
50
2.48
4.90
5.63
6.18
6.60
6.92
7.15
High
60
3.33
6.01
6.94
7.66
8.22
8.69
9.03
Low
75
4.83
5.14
5.97
6.60
7.09
7.46
7.73
High
90
6.65
6.32
7.38
8.20
8.87
9.42
9.83
Low
100
8.0
5.28
6.16
6.84
7.36
7.78
8.07
High
120
11.15
6.49
7.62
8.51
9.23
9.84
10.30
Low
125
11.99
5.37
6.29
6.99
7.54
7.98
8.29
High
150
16.8
6.60
7.77
8.71
9.47
10.11
10.60
90, 105, 115, 130 Nominal Tons
Hot Water
Water
Unit Standard Air Volume (Cfm)
Module
Gpm
PD (Ft)
27000
30000
33000
36000
39000
42000
Low
30
0.77
6.68
6.87
7.04
7.18
7.30
7.41
High
40
1.02
8.51
8.80
9.04
9.26
9.45
9.62
Low
60
1.69
8.07
8.38
8.64
8.87
9.07
9.25
High
80
2.6
10.21
10.64
11.03
11.38
11.69
11.98
Low
100
3.71
8.82
9.19
9.52
9.80
10.05
10.26
High
120
5.07
10.95
11.46
11.92
12.33
12.71
13.05
Low
140
6.59
9.19
9.60
9.96
10.27
10.55
10.79
High
160
8.37
11.37
11.93
12.43
12.88
13.30
13.67
Low
175
9.8
9.39
9.82
10.20
10.53
10.82
11.07
High
200
12.52
11.64
12.23
12.76
13.24
13.68
14.08
Note:
1. Capacities expressed as MBh per initial temperature difference (ITD) between the entering air temperature to
the hot water coil and the entering water temperature. Ethylene glycol or other capacities can be determined
from the Trane heating coil computer program. Capacity and pressure drop of ethylene glycol varies greatly
with temperature and concentration.