The PIC is the gateway to allow communication between a TRANE
equipment and a BMS (Building Management Systems) vendor through the
Modbus protocol over a RS232 or a RS-485 link.
The PIC handles Modbus RTU according to Reference Guide: Modicon
PI-MBUS-300 Rev. D
Modicon
®
is a trademark of Modicon, Inc.
Jbus
®
is a trademark of April.
Modbus/Jbus Considerations:
Jbus is an extension of Modbus. Jbus supports more functions than
Modbus.
•
Functions supported by both Modbus and Jbus:
1, 2, 3, 4, 5, 6, 15 and 16
•
Functions supported by Jbus but not supported by Modbus: