Operation
35
BAS-SVX08D-E4
Data
Type
Offset
Point Description
Function
Modbus
Index
10041
40
Transition contactor 1 ( 1 = ON, 0 = OFF)
bit
10042
41
Reset relay 2 ( 1 = ON, 0 = OFF)
bit
10047
46
Oil line solenoid valve 2,
female slide valve step load solenoid for 70-125 Ton ( 1 = ON, 0 = OFF)
bit
10048
47
Transition contactor 2 ( 1 = ON, 0 = OFF)
bit
10049
48
Reset relay 2 ( 1 = ON, 0 = OFF)
bit
10054
53
Oil line solenoid valve 2,
female slide valve step load solenoid for 70-125 Ton ( 1 = ON, 0 = OFF)
bit
10055
54
Transition contactor 2 ( 1 = ON, 0 = OFF)
bit
10059
58
Unit type RTXA (1 = true)
bit
10060
59
Circuit 2 oil bypass (1 = on)
bit
10061
60
Circuit 1 oil bypass (1 = on)
bit
10062
61
Circuit 2 reversed (1 = yes (heating), 0 = no)
bit
10063
62
Circuit 1 reversed (1 = yes (heating), 0 = no)
bit
10065
64
Informational warning (1 = active)
bit
10066
65
Circuit 2 auto reset (1 = active)
bit
10067
66
Circuit 1 auto reset (1 = active)
bit
10068
67
Circuit 2 manual reset required (1 = active)
bit
10069
68
Circuit 1 manual reset required (1 = active)
bit
30001
0
Evaporator leaving water temperature
Temperature
30002
1
Evaporator entering water temperature
Temperature
30003
2
Condenser leaving water temperature
Temperature
30004
3
Condenser entering water temperature
Temperature
30005
4
Average % current for chiller
Percentage
30006
5
Operating code
None
30007
6
Last diagnostic code
None
30008
7
Active chiller water/ice term setpoint
Temperature
30009
8
Copy of function 2 binary points
bitfield
30010
9
00h = 130-400 Ton RTAA (Intermediate screw),
01h = 70-125 Ton (General purpose screw)
None
30011
10
00h = 130-400 Ton RTAA, 06h = 70-125 Ton
None
30012
11
00h = 130-400 Ton RTAA (Required by the Remote Display)
None
30013
12
CPM module software revision level
None
30014
13
CSR module software revision level
None
30015
14
Master EXV module software revision level
None
30016
15
MSCP module # 1 software revision level
None
30017
16
MSCP module # 2 software revision level
None
30018
17
MSCP module # 3 software revision level
None
30019
18
MSCP module # 4 software revision level
None
Bit 2-0 = Number of compressors on unit
Bit 4-3 = Number of circuits on unit
Bit 6-5 = Manifolded pair identification
00h = AB/CD (4 CPRSR UNIT), AB/C (3 CPRSR UNIT), A/B (2 CPRSR UNIT)
01h, 10h, 11h = UNDEFINEDBit 7 = Water cooled unit (1 = Yes, 0 = No)
Bit 7 = Water cooled unit (1 = Yes, 0 = No)"
bitfield
Bit 1-0 = 00h (Stop/reset), 01h (Auto/remote), 10h = Auto/Local
Bit 2 = Evaporator pump status (1 = ON, 0 = OFF)
Bit 3 = Night noise setback bit (1 = ON, 0 = OFF)
Bit 4 = Compressor running bit (1 = any compressor running)
Bit 5 = Alarm bit (1 = alarm)
Bit 6 = Actively ice making bit (1 = making ice)
Bit 7 = Max capacity bit (1 = max capacity)"
bitfield
Analog
Inputs
4
Binary
Inputs
2
30020
19
30021
20
Unit
Table 14 - Continued