Operation
39
BAS-SVX08D-E4
Data
Type
Offset
Point Description
Function
Modbus
Index
10036
35
external auto/stop
bit
10037
36
emergency stop
bit
10038
37
CTV: external free cooling
bit
10039
38
CTV/RTH: external ice making
bit
10040
39
CTV: external heat pump
bit
10041
40
Manual Chilled Water Pump (1= ON; 0 = AUTO)
bit
10042
41
External Input Type (0 = 4-20mA; 1 = 2 - 10V)
bit
10043
42
CTV: Manual Oil Pump (1= ON, 0 = AUTO)
bit
30001
0
Leaving Chilled Water Temperature
Temperature
30002
1
Entering Chilled Water Temperature
Temperature
30003
2
Condenser Leaving Water Temperature
Temperature
30004
3
Condenser Entering Water Temperature
Temperature
30005
4
Average % Current Draw
Percentage
30006
5
Operating Code
None
30007
6
Last Active Diagnostic Code
None
30008
7
Active Chilled Water Setpoint
Temperature
30009
8
copy of function 2 binary points 10001 to 10011
bitfield
30010
9
Last Operating Mode at Time of Last Diag
None
Bit 0 UNUSED
Bit 1 UNUSED
Bit 2 UNUSED
30011
10
Bit 3 Limit Warning (1=Warning)
Bit 4 Chilled Water Pump (1 = On, 0 = Off)
Bit 5 Condenser Water Pump (1 = On, 0 = Off)
Bit 6 Compr/Unit Running (1 = Yes, 0 = No)
Bit 7 Alarm (1 = On, 0 = Off)
bitfield
Bit 0 UNUSED
Bit 1 UNUSED
Bit 2 UNUSED
30012
11
Bit 3 UNUSED
Bit 4 UNUSED
Bit 5 CTV/RTH: Actively Ice Making (1 = Yes, 0 = No)
Bit 6 Reset Relay (1 = On, 0 = Off)
Bit 7 CTV/ABS: Max Capacity (1 = Yes, 0 = No)"
bitfield
Bit 0 Chilled Water Flow (1 = On, 0 = Off)
Bit 1 Condenser Water Flow (1 = On, 0 = Off)
Bit 2 MMR exits
30013
12
Bit 3 MAR exits
Bit 4 IFW exists
Bit 5 RESERVED
Bit 6 RESERVED
Bit 7 RESERVED
bitfield
30014
13
Active Outdoor Air Temperature
Temperature
Bit 0 RESERVED
Bit 1 RESERVED
Bit 2 Tracer
Bit 3 External Direct Capacity Control
Bit 4 future 2
Bit 5 future 1
Bit 6 External Input
Bit 7 Front Panel"
bitfield
30016
15
CTV/RTH: Active Ice Termination Setpoint
Temperature
Analog
Inputs
4
Binary
Inputs
2
Table 15 - Continued
Unit