Refrigerant Piping Guidelines

Figure 1

Refrigerant Piping

To ensure the return of oil in the 
refrigerant lines, it is necessary to
follow these recommendations:

1. Select the tube lengths with care 

and try to avoid having a final few 
meters of tube to use up. Refer to 
table 2 for tube sizes.

2. Pitch all horizontal suction lines 

down towards the unit to assist 
gravity oil drainage back to the 
compressor.

3. Avoid creating large oil traps in 

horizontal suction lines as this will 
reduce oil circulating in the system 
and may eventually lead to failure 
of the compressor.

4. A small oil trap at the end of a 

horizontal suction line before a long 
vertical riser (of more that 2.5 
metres) has the advantage of 
assisting the high velocity gas to 
carry the oil up the vertical pipe.

5. The installation of a liquid line 

sight is recommended. It is veryu 
seful during the maintenance 
procedures.

Refrigerant Piping Guidelines

A. Maximum recommended line 

lengths: (per circuit) 
Maximum linear length

200 Ft.

Maximum suction line lift

60 Ft.

Maximum liquid line lift

60 Ft.

B. Maximum allowable pressure

drops (R407C):
Suction line

6 psi.

Liquid line

35 psi.

(without subcooler)
Route refrigerant piping for 
minimum linear length, 
minimum number of bends and 
fittings (no reducers) and minimum 
amount of line exposed to outdoor 
ambients.

C. Recommended line sizes:

TTA060FD (Single Circuit)
TTA075ED (Single Circuit)
TTA150ED (Dual Circuit)

Suction line

Liquid line 

1 1/8 inch sealed type L

refrigerant tubing.

1/2 inch sealed type L

refrigerant tubing.

D. Recommended line sizes:

TTA100ED, TTA120FD and 
TTA120ED (Single Circuit)
TTA180ED, TTA200ED and 
TTA240ED (Dual Circuit)

Suction line

Liquid line

E. Recommended line sizes: 

TTA150ED0G, TTA180ED0G, 
TTA200ED0G, TTA240FD and 
TTA240ED0G (Manifolded 
Compressor) TTA150ED (New/
Single Circuit)

Suction line

Liquid line

1 3/8 inch sealed type L

refrigerant tubing.

1/2 inch sealed type L

refrigerant tubing.

1 5/8 inch sealed type L

refrigerant tubing.

5/8 inch sealed type L

refrigerant tubing.

Note:

 Insulate all refrigerant piping

and connections.

Table 2 - Recommended Interconnecting Lines

(W/o accumulator)

TTA 060 FD 

1/2 

1 1/8 

1/2 

1 1/8 

1/2 

1 1/8 

1/2 

1 1/8

TTA 120 FD 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8

TTA 240 FD 

1/2 

1 3/8 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8

Length of Interconnecting Line (feet)

0-20 21-40 

41-60 

61-80

Liq.  Suct. Liq. Suct. Liq. Suct. Liq.  Suct.

TTA 075 ED 

1/2 

1 1/8 

1/2 

1 1/8 

1/2 

1 1/8 

1/2 

1 1/8

TTA 100 ED 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8

TTA 120 ED 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8

Model

TTA 150 ED 

1/2 

1 1/8 

1/2 

1 1/8 

1/2 

1 1/8 

1/2 

1 1/8

TTA 180 ED0G 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8

TTA 200 ED0G 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8

TTA 240 ED0G 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8

TTA 180 ED 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8

TTA 200 ED 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8

TTA 240 ED 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8 

1/2 

1 3/8

TTA 150 ED0G 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8

Notes: 1. Two line sets are required for dual circuits units.

2. For line lengths over 80 linear feet and 15 feet liquid line riser,

consult your local Trane representative.

TTA 150 ED (New)  5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8 

5/8 

1 5/8

TUBE CONNECTON

CAP 

CHARGING 

PORT

CAP VALVE PORT

BODY (FORGED)

TUBE CONNECTON

O - RING

O - RING 

SEAL

PLUNGER

VALVE CORE

TTA-R407C-EN1113.indd   6

TTA-R407C-EN1113.indd   6

12-Sep-16   13:28:23

12-Sep-16   13:28:23

Summary of Contents for ODYSSEY TTA 060 FD

Page 1: ...le Circuit TTA 075 ED TTA 100 ED TTA 120 ED TTA 150 ED New Dual Circuit TTA 150 ED TTA 180 ED TTA 200 ED TTA 240 ED Manifolded Compr TTA 150 ED0G TTA 180 ED0G TTA 200 ED0G TTA 240 ED0G Single Circuit...

Page 2: ...2 Model Nomenclature 060 60 MBH F R407C Hi Eff B Mirror Design Sequence S New Design 1 Fan New comp change R Fourth Design Sequence TTA R407C EN1113 indd 2 TTA R407C EN1113 indd 2 12 Sep 16 13 28 22 1...

Page 3: ...nt Piping Guidelines 6 Refrigerant Charging and Evacuation 8 General Data 10 Refrigerant Circuit 13 Electrical Wiring 14 Dimensional Data 19 Operation 23 Maintenance 24 Maintenance Log1 24 Trouble Sho...

Page 4: ...the unit Check for obvious damage to the unit or packing material Inspect the unit for concealed damage before it is stored and as soon as possible after delivery Concealed damage must be reported wit...

Page 5: ...enough space around the unit to allow unrestricted access to all service points Refer to unit dimensional data for minimum required service and free air clearances Observe the following points to ins...

Page 6: ...ED Single Circuit TTA180ED TTA200ED and TTA240ED Dual Circuit Suction line Liquid line E Recommended line sizes TTA150ED0G TTA180ED0G TTA200ED0G TTA240FD and TTA240ED0G Manifolded Compressor TTA150ED...

Page 7: ...ge system components and the unit nish 6 Shut off nitrogen supply 7 Shut off the manifold valve for the line that is connected to the suction line service valve Disconnect the line from the gauge port...

Page 8: ...nt needed based on notes above Note There is holding charge of refrigerant and N2 charged from factory However when install the unit system must be vacuumed and recharged refrigerant in the eld Table...

Page 9: ...For the additional amount using the table 4 for recommended amounts Recommended Charging Amount 4Caution R407C charge in liquid phase only Always evacuate air from the tubing before adding refrigeran...

Page 10: ...TTA R407C EN1113 10 General Data 1 20 3 40 34 80 TTA R407C EN1113 indd 10 TTA R407C EN1113 indd 10 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 11: ...TTA R407C EN1113 11 General Data 31 45 27 08 25 20 1 20 3 40 1 20 3 40 1 20 3 40 TTA R407C EN1113 indd 11 TTA R407C EN1113 indd 11 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 12: ...5 439 428 474 462 1100 x 2200 x 1140 1050 x 2200 x 1050 1180 x 2290 x 1140 1050 x 2200 x 1050 1180 x 2290 x 1140 1050 x 2200 x 1050 1180 x 2290 x 1140 1050 x 2200 x 1050 2 200 1 750 380 3 50 1 06 2 27...

Page 13: ...110 19 2 140 22 9 145 1 06 2 27 1 06 2 27 1 20 3 40 1 06 2 27 1 20 3 40 1 20 3 40 1 20 3 40 1 06 2 27 1 20 3 40 1 20 3 40 1 20 3 40 30 30 30 30 30 30 30 30 30 30 30 1 1 2 1 1 1 1 2 2 2 2 1 1 2 1 1 1...

Page 14: ...lems Important All wiring must comply with applicable local and national NEC codes Type and location of disconnect switches must comply with all applicable codes disconnect switch and lock in open pos...

Page 15: ...TTA R407C EN1113 15 Electrical Wiring TTA R407C EN1113 indd 15 TTA R407C EN1113 indd 15 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 16: ...TTA R407C EN1113 16 Electrical Wiring TTA R407C EN1113 indd 16 TTA R407C EN1113 indd 16 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 17: ...TTA R407C EN1113 17 Electrical Wiring TTA R407C EN1113 indd 17 TTA R407C EN1113 indd 17 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 18: ...TTA R407C EN1113 18 Electrical Wiring TTA R407C EN1113 indd 18 TTA R407C EN1113 indd 18 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 19: ...E TTA060FD TTA075ED TTA100 120ED TTA150ED New 950 950 950 950 1060 1060 1060 1060 778 778 778 778 888 888 888 888 1060 1060 1060 1260 1050 1050 1050 1250 A B C D E F 1 1 8 1 1 8 1 3 8 1 5 8 1 2 1 2 1...

Page 20: ...ensional Data TTA060FD TTA060FD TTA075ED TTA100 120ED 950 950 950 1060 1060 1060 778 778 778 888 888 888 1 1 8 1 1 8 1 3 8 1 2 1 2 1 2 TTA R407C EN1113 indd 20 TTA R407C EN1113 indd 20 12 Sep 16 13 28...

Page 21: ...TTA R407C EN1113 21 Dimensional Data TTA120FD TTA240FD 1 3 8 1 3 8 1 2 1 2 TTA120 240FD TTA150 180 200 240ED TTA R407C EN1113 indd 21 TTA R407C EN1113 indd 21 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 22: ...TTA R407C EN1113 22 TTA120FD TTA240FD 1 3 8 1 5 8 1 2 5 8 Dimensional Data TTA120 240FD TTA150 180 200 240ED0G TTA R407C EN1113 indd 22 TTA R407C EN1113 indd 22 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 23: ...ut Out s setting Internal Overload Protector IOL This device is a current thermal actuated warp switch imbedded in the compressor motor windings If will shut off the compressor if the temperature or c...

Page 24: ...enance Log Observe indoor fan operation and correct any unusual or excessive vibration Clean blower wheels as needed Annually Cooling Season The following maintenance procedures must be performed at t...

Page 25: ...v O l a n r e t n I r o s s e r p m o C r o t i c a p a C n u R r o t i c a p a C t r a t S y a l e r t r a t S s t c a t n o c r o t c a t n o C g n i r i W e g a t l o V w o L r e m r o f s n a r T...

Page 26: ...sibility that serious damage will occur Finally regular maintenance ensures the maximum operating life of your equipment We would remind you that failure to respect these installation and maintenance...

Page 27: ...TTA R407C EN1113 27 Note TTA R407C EN1113 indd 27 TTA R407C EN1113 indd 27 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 28: ...nd Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice For more information contact your local district offi...