background image

TTA-R407C-EN1113

23

Operation

Sequence of Operation

General

Operation of the system cooling
cycles is controlled by the position of
the system switch on the room
thermostat.

Evaporator Fan (Indoor Supply Air)

The evaporator fan is controlled by
an ON/AUTO switch on the room
thermostat. With the switch positioned
at AUTO and the system operating in
the cooling mode, fan operation
coincides with the cooling run cycles.
When the fan switch is positioned at
ON, fan operation is continuous.

Cooling Mode

With the disconnect switch in the
“ON” position, current is supplied
to the compressor crankcase heater
(s) and control transformer. The
crankcase heater (s) supplies heat to
the compressor (s) during the “OFF”
cycle. With the room thermostat
system switch positioned at COOL
and the fan switch at AUTO, the
compressor contactor energizes on a
call for cooling. When the contacts of
the compressor contactor energizes
on a call for cooling. When the
contacts of the compressor contactor
close, operation of the compressor
and condenser fan begins.
The evaporator fan contactor also
energizes on a call for cooling and
initiates evaporator fan operation.

On dual circuit units, when second
stage cooling is required, Y2 from the
indoor thermostat will energize 2nd
compressor.

Note:

 With the thermostat fan switch

in the ON position, the evaporator
fan will operate continuously,
regardless of compressor or
condenser fan operation.

Safety Controls

Note: All of these controls may not be
installed on your unit, check electrical
schematic.

Low Pressure Cut-Out (LPCO)

This control’s sensor is located in the
suction (gas line, near the compressor).
This control will stop the compressor
and the outdoor fans in suction
pressure drops below the Low
Pressure Cut-Out setting.

High Pressure Cut-Out (HPCO)

This control’s sensor is located in the
liquid line. This device will shut off the
compressor and the outdoor fan (s) if
the discharge pressure exceeds the
High Pressure Cut-Out’s setting.

Internal Overload Protector (IOL)

This device is a current/thermal
actuated warp switch, imbedded
in the compressor motor windings.
If will shut off the compressor if
the temperature or current of the
compressor motor windings exceeds
its design trip temperature.

Note:

 The IOL will put the

compressor back in operation once
the compressor motor heat has
dropped below the trip setting;
however, a check of the refrigerant
and electrical systems should be
made to determine the cause and
be corrected.

Installation Checklist

Complete this checklist once the
unit is installed to verify that all
recommended procedures have
been accomplished before starting
the system. Do not operate the
system until all items covered by this
checklist are complete.

Inspect unit location for proper
required service clearances.

Inspect unit location for proper free
air clearances.

Inspect unit location for secure.
Level mounting position.

Refrigerant Piping

Performed initial leak test?

Connected properly sized and
constructed liquid and suction lines
to the connection stubs at both the
indoor and outdoor units?

Insulated the entire suction line?

Insulated portions of liquid line
exposed to extremes in
temperature?

Charge each circuit with proper
amount of R407C?

Electrical Wiring

Provided unit power wiring (with
disconnect) to proper terminals in
the unit control Section?

Installed system indoor thermostat?

Installed system low voltage
interconnecting wiring to proper
terminals of outdoor unit, indoor
unit and system thermostat?

Unit Start-Up

Once the unit is properly installed and
pre-start procedures are complete,
start the unit by turning the System
Switch on the indoor thermostat to
either COOL or AUTO. The system
should operate normally.

the indoor air handler is closed before
operating the system. Operating the
outdoor unit without the indoor fan
energized, can cause unit trip-out on
high pressure control and/or liquid
flood-back to the compressors.

Evacuated each refrigerant circuit 
to 350 microns (-76 cm.Hg)?

4

Caution: 

Ensure the disconnect for

TTA-R407C-EN1113.indd   23

TTA-R407C-EN1113.indd   23

12-Sep-16   13:28:23

12-Sep-16   13:28:23

Summary of Contents for ODYSSEY TTA 060 FD

Page 1: ...le Circuit TTA 075 ED TTA 100 ED TTA 120 ED TTA 150 ED New Dual Circuit TTA 150 ED TTA 180 ED TTA 200 ED TTA 240 ED Manifolded Compr TTA 150 ED0G TTA 180 ED0G TTA 200 ED0G TTA 240 ED0G Single Circuit...

Page 2: ...2 Model Nomenclature 060 60 MBH F R407C Hi Eff B Mirror Design Sequence S New Design 1 Fan New comp change R Fourth Design Sequence TTA R407C EN1113 indd 2 TTA R407C EN1113 indd 2 12 Sep 16 13 28 22 1...

Page 3: ...nt Piping Guidelines 6 Refrigerant Charging and Evacuation 8 General Data 10 Refrigerant Circuit 13 Electrical Wiring 14 Dimensional Data 19 Operation 23 Maintenance 24 Maintenance Log1 24 Trouble Sho...

Page 4: ...the unit Check for obvious damage to the unit or packing material Inspect the unit for concealed damage before it is stored and as soon as possible after delivery Concealed damage must be reported wit...

Page 5: ...enough space around the unit to allow unrestricted access to all service points Refer to unit dimensional data for minimum required service and free air clearances Observe the following points to ins...

Page 6: ...ED Single Circuit TTA180ED TTA200ED and TTA240ED Dual Circuit Suction line Liquid line E Recommended line sizes TTA150ED0G TTA180ED0G TTA200ED0G TTA240FD and TTA240ED0G Manifolded Compressor TTA150ED...

Page 7: ...ge system components and the unit nish 6 Shut off nitrogen supply 7 Shut off the manifold valve for the line that is connected to the suction line service valve Disconnect the line from the gauge port...

Page 8: ...nt needed based on notes above Note There is holding charge of refrigerant and N2 charged from factory However when install the unit system must be vacuumed and recharged refrigerant in the eld Table...

Page 9: ...For the additional amount using the table 4 for recommended amounts Recommended Charging Amount 4Caution R407C charge in liquid phase only Always evacuate air from the tubing before adding refrigeran...

Page 10: ...TTA R407C EN1113 10 General Data 1 20 3 40 34 80 TTA R407C EN1113 indd 10 TTA R407C EN1113 indd 10 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 11: ...TTA R407C EN1113 11 General Data 31 45 27 08 25 20 1 20 3 40 1 20 3 40 1 20 3 40 TTA R407C EN1113 indd 11 TTA R407C EN1113 indd 11 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 12: ...5 439 428 474 462 1100 x 2200 x 1140 1050 x 2200 x 1050 1180 x 2290 x 1140 1050 x 2200 x 1050 1180 x 2290 x 1140 1050 x 2200 x 1050 1180 x 2290 x 1140 1050 x 2200 x 1050 2 200 1 750 380 3 50 1 06 2 27...

Page 13: ...110 19 2 140 22 9 145 1 06 2 27 1 06 2 27 1 20 3 40 1 06 2 27 1 20 3 40 1 20 3 40 1 20 3 40 1 06 2 27 1 20 3 40 1 20 3 40 1 20 3 40 30 30 30 30 30 30 30 30 30 30 30 1 1 2 1 1 1 1 2 2 2 2 1 1 2 1 1 1...

Page 14: ...lems Important All wiring must comply with applicable local and national NEC codes Type and location of disconnect switches must comply with all applicable codes disconnect switch and lock in open pos...

Page 15: ...TTA R407C EN1113 15 Electrical Wiring TTA R407C EN1113 indd 15 TTA R407C EN1113 indd 15 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 16: ...TTA R407C EN1113 16 Electrical Wiring TTA R407C EN1113 indd 16 TTA R407C EN1113 indd 16 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 17: ...TTA R407C EN1113 17 Electrical Wiring TTA R407C EN1113 indd 17 TTA R407C EN1113 indd 17 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 18: ...TTA R407C EN1113 18 Electrical Wiring TTA R407C EN1113 indd 18 TTA R407C EN1113 indd 18 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 19: ...E TTA060FD TTA075ED TTA100 120ED TTA150ED New 950 950 950 950 1060 1060 1060 1060 778 778 778 778 888 888 888 888 1060 1060 1060 1260 1050 1050 1050 1250 A B C D E F 1 1 8 1 1 8 1 3 8 1 5 8 1 2 1 2 1...

Page 20: ...ensional Data TTA060FD TTA060FD TTA075ED TTA100 120ED 950 950 950 1060 1060 1060 778 778 778 888 888 888 1 1 8 1 1 8 1 3 8 1 2 1 2 1 2 TTA R407C EN1113 indd 20 TTA R407C EN1113 indd 20 12 Sep 16 13 28...

Page 21: ...TTA R407C EN1113 21 Dimensional Data TTA120FD TTA240FD 1 3 8 1 3 8 1 2 1 2 TTA120 240FD TTA150 180 200 240ED TTA R407C EN1113 indd 21 TTA R407C EN1113 indd 21 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 22: ...TTA R407C EN1113 22 TTA120FD TTA240FD 1 3 8 1 5 8 1 2 5 8 Dimensional Data TTA120 240FD TTA150 180 200 240ED0G TTA R407C EN1113 indd 22 TTA R407C EN1113 indd 22 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 23: ...ut Out s setting Internal Overload Protector IOL This device is a current thermal actuated warp switch imbedded in the compressor motor windings If will shut off the compressor if the temperature or c...

Page 24: ...enance Log Observe indoor fan operation and correct any unusual or excessive vibration Clean blower wheels as needed Annually Cooling Season The following maintenance procedures must be performed at t...

Page 25: ...v O l a n r e t n I r o s s e r p m o C r o t i c a p a C n u R r o t i c a p a C t r a t S y a l e r t r a t S s t c a t n o c r o t c a t n o C g n i r i W e g a t l o V w o L r e m r o f s n a r T...

Page 26: ...sibility that serious damage will occur Finally regular maintenance ensures the maximum operating life of your equipment We would remind you that failure to respect these installation and maintenance...

Page 27: ...TTA R407C EN1113 27 Note TTA R407C EN1113 indd 27 TTA R407C EN1113 indd 27 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 28: ...nd Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice For more information contact your local district offi...

Reviews: