background image

TTA-R407C-EN1113

24

Notes:

1. Perform each inspection once per month (during cooling season) while unit is operating.

Maintenance Log

1

Evaporator

Ambient Entering 

air 

Compressor 

Superheat 

Subcooling

Temp Dry  Wet  Suction Discharge  Circuit 

Circuit

Date 

(F) 

Bulb 

Bulb 

Pressure 

pressure 

No. 1 (1) 

No. 1 (F)

Maintenance

Maintenance

Perform all of the indicated
maintenance procedures at the
intervals scheduled. This will prolong
the life of the unit and reduce the
possibility of costly equipment failure.

Monthly

Conduct the following maintenance
inspections once per month.

disconnect to prevent injury or death
from electrical shock or contact with
moving parts.

•  Inspect air filters and clean if

necessary.

•  Check unit wiring to ensure all

connections are tight and that the
wiring insulation is intact.

•  Check drain pans and condensate

piping to insure they are free of
obstacles.

•  Manually rotate the outdoor fan to

insure proper operation. Inspect
the fan mounting hardware for
tightness.

•  Inspect the evaporator and

condenser coils for dirt and debris.
If the coils appear dirty, clean them.

•  With the unit operating in the

cooling mode, check the suction
and discharge pressures and
compare them with the values
provided in “Pressure Curves”.
Record these readings on the
“Maintenance Log”.

•  Observe indoor fan operation and

correct any unusual or excessive
vibration. Clean blower wheels as
needed.

Annually (Cooling Season)

The following maintenance procedures
must be performed at the beginning of
each cooling season to insure efficient
unit operation.

•  Perform all of the monthly

maintenance inspections.

•  With the unit operating, check unit

superheat and record the reading
in the “Maintenance Log”.

•  Remove any accumulation of dust

and/or dirt from the unit casing.

•  Remove any accumulation of dust

and/or dirt from the unit casing.

•  Remove corrosion from any surface

and re-paint. Check the gasket
around the control panel door to
insure it fits correctly and is in good
condition to prevent water leakage.

•  Remove corrosion from any surface

and re-paint. Check the gasket
around the control panel door to
insure it fits correctly and is in good
condition to prevent water leakage.

•  Inspect the evaporator fan belt. If it

is worn or frayed, replace it.

•  Inspect the control panel wiring to

insure that all connections are tight
and that the insulation is intact.

Lubricate the indoor fan motor
bearings with a non-detergent,
20-weight oil. (To insure good bearing
lubrication, condenser fan motor
bearings should be lubricated once
every six months).

Note: Some motors are permanently
lubricated.

•  Check refrigerant piping and fittings

for leaks.

4

Warning:

 Open and lock unit

TTA-R407C-EN1113.indd   24

TTA-R407C-EN1113.indd   24

12-Sep-16   13:28:23

12-Sep-16   13:28:23

Summary of Contents for ODYSSEY TTA 060 FD

Page 1: ...le Circuit TTA 075 ED TTA 100 ED TTA 120 ED TTA 150 ED New Dual Circuit TTA 150 ED TTA 180 ED TTA 200 ED TTA 240 ED Manifolded Compr TTA 150 ED0G TTA 180 ED0G TTA 200 ED0G TTA 240 ED0G Single Circuit...

Page 2: ...2 Model Nomenclature 060 60 MBH F R407C Hi Eff B Mirror Design Sequence S New Design 1 Fan New comp change R Fourth Design Sequence TTA R407C EN1113 indd 2 TTA R407C EN1113 indd 2 12 Sep 16 13 28 22 1...

Page 3: ...nt Piping Guidelines 6 Refrigerant Charging and Evacuation 8 General Data 10 Refrigerant Circuit 13 Electrical Wiring 14 Dimensional Data 19 Operation 23 Maintenance 24 Maintenance Log1 24 Trouble Sho...

Page 4: ...the unit Check for obvious damage to the unit or packing material Inspect the unit for concealed damage before it is stored and as soon as possible after delivery Concealed damage must be reported wit...

Page 5: ...enough space around the unit to allow unrestricted access to all service points Refer to unit dimensional data for minimum required service and free air clearances Observe the following points to ins...

Page 6: ...ED Single Circuit TTA180ED TTA200ED and TTA240ED Dual Circuit Suction line Liquid line E Recommended line sizes TTA150ED0G TTA180ED0G TTA200ED0G TTA240FD and TTA240ED0G Manifolded Compressor TTA150ED...

Page 7: ...ge system components and the unit nish 6 Shut off nitrogen supply 7 Shut off the manifold valve for the line that is connected to the suction line service valve Disconnect the line from the gauge port...

Page 8: ...nt needed based on notes above Note There is holding charge of refrigerant and N2 charged from factory However when install the unit system must be vacuumed and recharged refrigerant in the eld Table...

Page 9: ...For the additional amount using the table 4 for recommended amounts Recommended Charging Amount 4Caution R407C charge in liquid phase only Always evacuate air from the tubing before adding refrigeran...

Page 10: ...TTA R407C EN1113 10 General Data 1 20 3 40 34 80 TTA R407C EN1113 indd 10 TTA R407C EN1113 indd 10 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 11: ...TTA R407C EN1113 11 General Data 31 45 27 08 25 20 1 20 3 40 1 20 3 40 1 20 3 40 TTA R407C EN1113 indd 11 TTA R407C EN1113 indd 11 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 12: ...5 439 428 474 462 1100 x 2200 x 1140 1050 x 2200 x 1050 1180 x 2290 x 1140 1050 x 2200 x 1050 1180 x 2290 x 1140 1050 x 2200 x 1050 1180 x 2290 x 1140 1050 x 2200 x 1050 2 200 1 750 380 3 50 1 06 2 27...

Page 13: ...110 19 2 140 22 9 145 1 06 2 27 1 06 2 27 1 20 3 40 1 06 2 27 1 20 3 40 1 20 3 40 1 20 3 40 1 06 2 27 1 20 3 40 1 20 3 40 1 20 3 40 30 30 30 30 30 30 30 30 30 30 30 1 1 2 1 1 1 1 2 2 2 2 1 1 2 1 1 1...

Page 14: ...lems Important All wiring must comply with applicable local and national NEC codes Type and location of disconnect switches must comply with all applicable codes disconnect switch and lock in open pos...

Page 15: ...TTA R407C EN1113 15 Electrical Wiring TTA R407C EN1113 indd 15 TTA R407C EN1113 indd 15 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 16: ...TTA R407C EN1113 16 Electrical Wiring TTA R407C EN1113 indd 16 TTA R407C EN1113 indd 16 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 17: ...TTA R407C EN1113 17 Electrical Wiring TTA R407C EN1113 indd 17 TTA R407C EN1113 indd 17 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 18: ...TTA R407C EN1113 18 Electrical Wiring TTA R407C EN1113 indd 18 TTA R407C EN1113 indd 18 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 19: ...E TTA060FD TTA075ED TTA100 120ED TTA150ED New 950 950 950 950 1060 1060 1060 1060 778 778 778 778 888 888 888 888 1060 1060 1060 1260 1050 1050 1050 1250 A B C D E F 1 1 8 1 1 8 1 3 8 1 5 8 1 2 1 2 1...

Page 20: ...ensional Data TTA060FD TTA060FD TTA075ED TTA100 120ED 950 950 950 1060 1060 1060 778 778 778 888 888 888 1 1 8 1 1 8 1 3 8 1 2 1 2 1 2 TTA R407C EN1113 indd 20 TTA R407C EN1113 indd 20 12 Sep 16 13 28...

Page 21: ...TTA R407C EN1113 21 Dimensional Data TTA120FD TTA240FD 1 3 8 1 3 8 1 2 1 2 TTA120 240FD TTA150 180 200 240ED TTA R407C EN1113 indd 21 TTA R407C EN1113 indd 21 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 22: ...TTA R407C EN1113 22 TTA120FD TTA240FD 1 3 8 1 5 8 1 2 5 8 Dimensional Data TTA120 240FD TTA150 180 200 240ED0G TTA R407C EN1113 indd 22 TTA R407C EN1113 indd 22 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 23: ...ut Out s setting Internal Overload Protector IOL This device is a current thermal actuated warp switch imbedded in the compressor motor windings If will shut off the compressor if the temperature or c...

Page 24: ...enance Log Observe indoor fan operation and correct any unusual or excessive vibration Clean blower wheels as needed Annually Cooling Season The following maintenance procedures must be performed at t...

Page 25: ...v O l a n r e t n I r o s s e r p m o C r o t i c a p a C n u R r o t i c a p a C t r a t S y a l e r t r a t S s t c a t n o c r o t c a t n o C g n i r i W e g a t l o V w o L r e m r o f s n a r T...

Page 26: ...sibility that serious damage will occur Finally regular maintenance ensures the maximum operating life of your equipment We would remind you that failure to respect these installation and maintenance...

Page 27: ...TTA R407C EN1113 27 Note TTA R407C EN1113 indd 27 TTA R407C EN1113 indd 27 12 Sep 16 13 28 23 12 Sep 16 13 28 23...

Page 28: ...nd Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice For more information contact your local district offi...

Reviews: