Mounting and Wiring the WCI

Figure 6.

Wiring the WCI to a Tracer SC

Figure 7.

Wiring multiple WCIs to a Tracer SC

Tracer SC

PM014

WCI wiring

LINK +

LINK –

+ 24VDC

IMC– IMC+

Ground 24 

Vdc

Gray = LINK -
Blue = LINK +
Black = Ground
Red = 24 Vdc

Connect both 2-connector 
screw terminal blocks to 
either of the IMC terminals 
on the PM014.

WCI

WCI

WCI

WCI

WCI

WCI

WCI

WCI

Tracer SC

PM014

Notes:

A maximum of eight WCIs can be
daisy-chained to the Tracer SC.

Use both IMC terminals on the

PM014 for wiring multiple WCIs
(see the detail in Figure 6).

• The WCIs on both links can span a

total of 200 meters.

Summary of Contents for MOD02422

Page 1: ...knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the...

Page 2: ...at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks referenced in this document are the trademarks of their resp...

Page 3: ...WCI 13 Controller Applications 13 Repeater Applications 17 Establishing the Network 18 WCI LEDs and Buttons 18 Three Ways to Establish a Wireless Network 20 Establishing the Network After Tracer SC I...

Page 4: ...ppendix Using the Tracer TU Service Tool with Wireless Networks 28 Requirements for Joining 28 Joining Tracer TU with a Wireless Network 28 Managing a Wireless Network and Devices 30 Connecting to a D...

Page 5: ...s that can be installed at a site is determined by the applicable Tracer SC license which specifies the total number of controllers For information about installing aWCI on aTracer SC see Mounting and...

Page 6: ...rness and mounting hardware intended for indoor installations X13790902010 NO BAY SEN01807 For flush mount applications Wiring harness not included X13790941010 BAYWCII200A MOD02422 Outdoor model incl...

Page 7: ...Equipment FCC CFR47 Sec 15 247 subpart E Digital Modulation Transmission with no SAR FCC ID TPF 251701 This device complies with part 15 of the FCC Rules Operation is subject to the following two cond...

Page 8: ...lectriques ou de t l vision ceci pouvant tre d termin en allumant et en teignant l quipement l utilisateur est encourag essayer de corriger l interf rence en utilisant un ou plusieurs des moyens suiva...

Page 9: ...eater to bridge the signal between a WCI that is out of the radio range of the other WCIs see Repeater Applications p 17 When choosing a location for a repeater WCI consider the availability of a 24 V...

Page 10: ...10 BAS SVX40B EN Location Considerations Consequently the design range between these devices is shorter Based on our tests we recommend a design range of 100 feet...

Page 11: ...rs to all of the networks that communicate with the sameTracer SC 2 Set the right NET rotary address switch for eachWCI that is to be on the same network to an identical number If there are multiple n...

Page 12: ...sses so that no two wireless zone sensors sharing the same address are within radio range of each other Addresses above 127 may be used for Wireless Comm systems See the Wireless Comm Network Design B...

Page 13: ...er 3 Secure the backplate to the mounting surface using appropriate hardware M3 5 x 20 mm self drilling screws are provided 4 Attach the 4 connector screw terminal block on the wiring harness to the r...

Page 14: ...I remotely then you only need to run one piece ofTrane purple wire 2 conductors 1 shield for the comm link Trane recommends that you ground the shield at the UC the BCI or the PM014 Note To wire the W...

Page 15: ...Gray LINK Blue LINK Black Ground Red 24 Vdc Connect both 2 connector screw terminal blocks to either of the IMC terminals on the PM014 WCI WCI WCI WCI WCI WCI WCI WCI Tracer SC PM014 Notes A maximum o...

Page 16: ...LINK Blue LINK Black Ground Red 24 Vdc VAC 24 BI1 BI2 BI3 LINK IMC 24 VDC IMC Jumper LINK LINK 24 Vdc WCI BCI I Attach jumper at BI1 to enable wireless communication Gray LINK Blue LINK Black Ground R...

Page 17: ...wiring harness 6 Connect the red 24Vdc Vac wire and black ground wire through the opening in the backplate Figure 5a or the bottom exit port Figure 5b to a 24 V power source AC or DC Figure 11 Wiring...

Page 18: ...cer SC designates a WCI as the network coordinator and opens the network for joining Removes a member WCI from the network see Removing a WCI from a Network p 24 Disbands the network see Disbanding a...

Page 19: ...ith the WCI Coordinator LED yellow CRD On solid WCI is network coordinator Open Net LED yellow OPEN NET On solid Network is open for joining Off Network is closed Reception LED yellow RX LINK Flickers...

Page 20: ...seTracerTU to open the network 3 Observe the green NWK LED illuminate On the coordinator WCI indicating that it has joined its own network On each additional WCI as it joins the network Note Typically...

Page 21: ...conds The network will disband 2 Install an addressed WCI on theTracer SC following addressing and wiring instructions see WCI Addressing p 11 and Mounting and Wiring the WCI p 13 After power is resto...

Page 22: ...n see Setting Wireless Zone Sensor Receiver Addressing p 12 Figure 13 Wireless zone sensor receiver association Notes To observe the radio signal strength between the sensor and receiver press theTest...

Page 23: ...tton on a member WCI will open only that one WCI 2 Observe the green NWK LED illuminate on a WCI that joins the network Adding Coordinators to aTracer SC ATracer SC can have a total of eightWCIs insta...

Page 24: ...ol of the unit controller Replacing a WCI on a Network See Replacing a Failed WCI p 26 Closing the Network To preventWCIs from joining an open network indicated by an illuminated OPEN_NET LED you can...

Page 25: ...er to the WCI Ensure that the WCI is wired properly to the Tracer SC Wireless link on the Tracer SC Ensure that the wireless link on the Tracer SC is enabled and configured to match WCI address and is...

Page 26: ...dinator WCI will re initiate the network as soon as power is returned Signal obstruction If an obstruction causes communication to be lost the coordinator WCI will re initiate the network as soon as c...

Page 27: ...er SC The network will re form itself New coordinator WCI when noTracer SC is present 1 Set or verify if pre addressed the rotary address switches on the new WCI 2 Attach the terminal block on the wir...

Page 28: ...nts for joiningTracerTU to a wireless network are TracerTU version 8 2 minimum TheTracerTU Communications Adapter Wireless connected to the service tool laptop Note For instructions onTracerTU Communi...

Page 29: ...required An open padlock icon indicates that noTracer SC login is required Figure 15 Wireless Network Utilities 4 Select the network you wantTracerTU to join Click the Join button Note TracerTU can j...

Page 30: ...manage the network and the devices on it by connecting to a device on the network Connecting to a Device To connect to a device 1 From the Wireless Network Utilities screen select the Network Devices...

Page 31: ...ment To access the menu select Wireless from theTools menu Figure 19 Wireless menu TheseTools menu options perform the following functions Network Health Displays theWireless Network Summary Report sh...

Page 32: ...onse to a comm request from each device You can also access the Wireless Network Summary Report by clicking Report on the Network Devices tab Figure 20 Wireless Network Summary Report Click Load Map t...

Page 33: ...Network Details tab see Figure 22 p 33 Figure 22 Network Details tab Sensor Health Status Provides an alternate way to view the Wireless Sensor Status tab see Figure 23 Figure 23 Wireless Sensor Stat...

Page 34: ...st be attached to the network coordinator Join Network Select to join the network Appears when you are connecting to a member WCI It is grayed out if you have already joined the network Create Network...

Page 35: ...troller but a wireless sensor is in the area the wireless sensor has priority and the unit controller may start using the wireless sensor even though a sensor is wired to it In such a case you must di...

Page 36: ...controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and reserves the rig...

Reviews: